Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: DEPT. OF VETERANS AFFAIRS

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of DEPT. OF VETERANS AFFAIRS in 3400 LEBANON PIKE, MURFREESBORO, TN 37129 (NAICS 622210). OSHA activity number 301508628.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Dept. of Veterans Affairs — free Get an email when a new federal OSHA severe-injury report for Dept. of Veterans Affairs is published. One employer, no account, unsubscribe in one click.
Site address
3400 LEBANON PIKE
City
MURFREESBORO
State
TN
ZIP
37129
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Y
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
622210
SIC code (legacy)
8063
Employees
3000
Ownership type
D

2 citations on file for this inspection.

1910.36 D01

Serious Gravity 03 1 instance 3 exposed
Issued
Mar 28, 2008
Abate by
Apr 23, 2008

1960.8 A

Serious Gravity 03 2 instances 4 exposed
Issued
Mar 5, 2008
Abate by
Apr 21, 2008
The agency did not furnish to each employee employment which was free from
recognized
hazards that are causing or are likely to cause death or serious physical
harm:
a)Chiller Plant - On or about 02/21/08, the employer did not fully comply
with ASHRAE
15 requirements in that  each entrance to the machinery room was not
appropriately
marked to prevent unauthorized employees from entering the room.
b)Compressor Room, Building 2, RM G02, On or about 02/21/08, the employer
did not
comply with ASHRAE 15 requirements in that the machinery room did not
contain a
detector system in case of a leak, a mechanical ventilation system vented
to the outdoors,
an audible and visual alarm inside the room and outside each entrance and
doors were
not clearly marked to indicate restriction to authorized personnel only.
Among other methods, one feasible and acceptable method to correct this
hazard is to comply
with ANSI/ASHRAE 15-2004 Safety Standard for Refrigeration Systems,
specifically
provide
visual and audible alarms inside the machinery room and outside each
entrance, install a
detection system and ventilation system, and post authorized entry signs.