MURFREESBORO, TN —
OSHA Inspection: DEPT. OF VETERANS AFFAIRS
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of DEPT. OF VETERANS AFFAIRS in 3400 LEBANON PIKE, MURFREESBORO, TN 37129 (NAICS 622210). OSHA activity number 301508628.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- DEPT. OF VETERANS AFFAIRS
- Site address
- 3400 LEBANON PIKE
- City
- MURFREESBORO
- State
- TN
- ZIP
- 37129
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 622210
- SIC code (legacy)
- 8063
- Employees
- 3000
- Ownership type
- D
Citations
2 citations on file for this inspection.
1910.36 D01
- Issued
- Mar 28, 2008
- Abate by
- Apr 23, 2008
1960.8 A
- Issued
- Mar 5, 2008
- Abate by
- Apr 21, 2008
General-duty citation text
The agency did not furnish to each employee employment which was free from recognized hazards that are causing or are likely to cause death or serious physical harm: a)Chiller Plant - On or about 02/21/08, the employer did not fully comply with ASHRAE 15 requirements in that each entrance to the machinery room was not appropriately marked to prevent unauthorized employees from entering the room. b)Compressor Room, Building 2, RM G02, On or about 02/21/08, the employer did not comply with ASHRAE 15 requirements in that the machinery room did not contain a detector system in case of a leak, a mechanical ventilation system vented to the outdoors, an audible and visual alarm inside the room and outside each entrance and doors were not clearly marked to indicate restriction to authorized personnel only. Among other methods, one feasible and acceptable method to correct this hazard is to comply with ANSI/ASHRAE 15-2004 Safety Standard for Refrigeration Systems, specifically provide visual and audible alarms inside the machinery room and outside each entrance, install a detection system and ventilation system, and post authorized entry signs.
More inspections at Dept. of Veterans Affairs
View Dept. of Veterans Affairs's full OSHA safety record →
More inspections in this industry (NAICS 622210)
More inspections in TN
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 301508628.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.