MIAMI BEACH, FL —
OSHA Inspection: FLORIDA POWER & LIGHT
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of FLORIDA POWER & LIGHT in 9535 COLLINS AVENUE, MIAMI BEACH, FL 33154 (NAICS 000000). OSHA activity number 301882130.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- FLORIDA POWER & LIGHT
- Site address
- 9535 COLLINS AVENUE
- City
- MIAMI BEACH
- State
- FL
- ZIP
- 33154
- Mailing
- 700 UNIVERSE BLVD, JUNO BEACH, FL 33154
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 4911
- Employees
- 130
- Ownership type
- A
Citations
1 citation on file for this inspection.
5(a)(1)
- Issued
- Aug 27, 1999
- Abate by
- Sep 23, 1999
- Penalty
- Initial $5,000 · Current $3,750 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which was free from recognized hazards that were causing or likely to cause death or serious physical harm to employees that were exposed to an electric arc and fire hazard while upgrading switches in an underground vault: a. On or about February 27, 1999, at 9553 Collins Avenue in Miami Beach, Florida, two Cable Splicers were assigned to upgrade fuses in an underground vault that contained Oil Fuse Cutouts (OFC) and Oil Switches. During the work activity, oil from a transformer's OFC was blown onto a worker. Work activity was not discontinued to determine why this malfunction occurred. Additional transformer oil was lowered in to the vault. A phase transformer OFC fault fired causing an electric arc which ignited the oil. Additional OFC fault firing and excess oil were contributing factors in the severity of the accident. Among other methods, the following are considered to be feasible and acceptable methods to correct this hazard: Use personal protective equipment (blast blankets, shields and flame retardant clothing) to minimize the effects of electrical arcs and flash fires. Insure that employees are trained to recognize abnormal conditions that arise (i.e. oil blowing from equipment) and only proceed when an in-process evaluation has determined the cause of the malfunction and corrective measures have been taken. Insure that Oil Fuse Cutouts are set to non-automatic (one shot) mode of operation. PLEASE NOTE: CERTIFICATION AND DOCUMENTATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (2)
- — I (S) $3750.00
- — Z (S) $5000.00
More inspections at Florida Power & Light
View Florida Power & Light's full OSHA safety record →
More inspections in this industry (NAICS 000000)
More inspections in FL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 301882130.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.