Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: FLORIDA POWER & LIGHT

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of FLORIDA POWER & LIGHT in 9535 COLLINS AVENUE, MIAMI BEACH, FL 33154 (NAICS 000000). OSHA activity number 301882130.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Florida Power & Light — free Get an email when a new federal OSHA severe-injury report for Florida Power & Light is published. One employer, no account, unsubscribe in one click.
Site address
9535 COLLINS AVENUE
City
MIAMI BEACH
State
FL
ZIP
33154
Mailing
700 UNIVERSE BLVD, JUNO BEACH, FL 33154
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Y
Opened
Closing conference
Case closed
Data loaded
NAICS code
000000
SIC code (legacy)
4911
Employees
130
Ownership type
A

1 citation on file for this inspection.

5(a)(1)

Serious Gravity 10 1 instance 2 exposed
Issued
Aug 27, 1999
Abate by
Sep 23, 1999
Penalty
Initial $5,000 · Current $3,750 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which was free from
recognized hazards that
were causing or likely to cause death or serious physical harm to
employees that were exposed
to an electric arc and fire hazard while upgrading switches in an
underground vault:
a.  On or about February 27, 1999, at 9553 Collins Avenue in Miami Beach,
Florida, two Cable
Splicers were assigned to upgrade fuses in an underground vault that
contained Oil Fuse Cutouts
(OFC) and Oil Switches.  During the work activity, oil from a
transformer's OFC was blown
onto a worker.  Work activity was not discontinued to determine why this
malfunction occurred.
Additional transformer oil was lowered in to the vault.  A phase
transformer OFC fault fired
causing an electric arc which ignited the oil.  Additional OFC fault
firing and excess oil were
contributing factors in the severity of the accident.
Among other methods, the following are considered to be feasible and
acceptable methods to
correct this hazard:
Use personal protective equipment (blast blankets, shields and flame
retardant clothing) to
minimize the effects of electrical arcs and flash fires.
Insure that employees are trained to recognize abnormal conditions that
arise (i.e. oil blowing
from equipment) and only proceed when an in-process evaluation has
determined the cause of
the malfunction and corrective measures have been taken.
Insure that Oil Fuse Cutouts are set to non-automatic (one shot) mode of
operation.
PLEASE NOTE:  CERTIFICATION AND DOCUMENTATION OF ABATEMENT IS
REQUIRED FOR THIS VIOLATION.
Recent events (2)
  • — I (S) $3750.00
  • — Z (S) $5000.00

View Florida Power & Light's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 301882130.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.