PAHOKEE, FL ·
OSHA Inspection: R. P. ICE, INC.
Referral inspection · Health discipline
At a glance
On , OSHA opened a referral health inspection of R. P. ICE, INC. in 2780 E. MAIN ST., PAHOKEE, FL 33476 (NAICS 000000). OSHA activity number 301883765.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- R. P. ICE, INC.
- Site address
- 2780 E. MAIN ST.
- City
- PAHOKEE
- State
- FL
- ZIP
- 33476
- Mailing
- 500 NE 185TH STREET, MIAMI, FL 33179
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- Non-union (N)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 2097
- Employees
- 8
- Ownership type
- Private (A)
Citations
12 citations on file for this inspection.
5(a)(1)
- Issued
- May 5, 1999
- Abate by
- Jun 22, 1999
- Penalty
- Initial $750 · Current $400 Reduced
General-duty citation text
Section 5(A)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish to employees employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that: (a)Employees are exposed to an ammonia hazard from an improper gage glass on the ammonia receiver. The present glass is in an exposed location and is not protected against damage; as required by the national consensus standard, "Safety Code for Mechanical Refrigeration", The American Society of Heating, Refrigerating, and Air- Conditioning Engineers, Inc., ASHRAE 15 (1978), 8.5.2. A feasible and acceptable method of abatement is to replace the present gage glass with one of an armored type approved for ammonia service. (b)Employees are exposed to an ammonia hazard from a poorly maintained ammonia- receiver drain line. The line and associated valves are covered with a heavy deposit of surface rust and not maintained in a clean condition, as required by ASHRAE 15 (1978), 13.10. A feasible and acceptable method of abatement is to clean, repair and/or replace damaged parts, and paint the receiver drain line. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THESE VIOLATIONS.ON
Recent events (2)
- · I (S) $400.00
- · Z (S) $750.00
1910.23 C01
- Issued
- May 5, 1999
- Abate by
- May 19, 1999
- Penalty
- Initial $600 · Current $300 Reduced
Recent events (2)
- · I (S) $300.00
- · Z (S) $600.00
1910.23 D01 III
- Issued
- May 5, 1999
- Abate by
- May 19, 1999
Recent events (2)
- · I (S)
- · Z (S)
1910.23 E03 IV
- Issued
- May 5, 1999
- Abate by
- May 19, 1999
Recent events (2)
- · I (S)
- · Z (S)
1910.252 B02 IB
- Issued
- May 5, 1999
- Abate by
- Apr 19, 1999
- Penalty
- Initial $635 · Current $350 Reduced
Recent events (2)
- · I (S) $350.00
- · Z (S) $635.00
1910.305 B02
- Issued
- May 5, 1999
- Abate by
- May 13, 1999
- Penalty
- Initial $750 · Current $450 Reduced
Recent events (2)
- · I (S) $450.00
- · Z (S) $750.00
1910.305 E02
- Issued
- May 5, 1999
- Abate by
- May 19, 1999
- Penalty
- Initial $750 · Current $500 Reduced
Recent events (2)
- · I (S) $500.00
- · Z (S) $750.00
1910.179 J02 III
- Issued
- May 5, 1999
- Abate by
- May 19, 1999
Recent events (2)
- · I (S)
- · Z (S)
1910.179 M01
- Issued
- May 5, 1999
- Abate by
- May 19, 1999
Recent events (2)
- · I (S)
- · Z (S)
1910.120 Q01
- Issued
- May 5, 1999
- Abate by
- Jun 22, 1999
Recent events (2)
- · I (O)
- · Z (O)
1910.1200 E01
- Issued
- May 5, 1999
- Abate by
- Jun 22, 1999
Recent events (2)
- · I (O)
- · Z (O)
1910.1200 G01
- Issued
- May 5, 1999
- Abate by
- Jun 22, 1999
Recent events (2)
- · I (O)
- · Z (O)