Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: FOAMEX L.P., LIMITED PARTNERSHIP

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of FOAMEX L.P., LIMITED PARTNERSHIP in 1351 GEMINI BLVD., ORLANDO, FL 32837 (NAICS 000000). OSHA activity number 301970182.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Foamex L.P., Limited Partnership — free Get an email when a new federal OSHA severe-injury report for Foamex L.P., Limited Partnership is published. One employer, no account, unsubscribe in one click.
Site address
1351 GEMINI BLVD.
City
ORLANDO
State
FL
ZIP
32837
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
000000
SIC code (legacy)
3086
Employees
130
Ownership type
A
Industry flags
Manufacturing safety.

5 citations on file for this inspection.

5(a)(1)

Serious Gravity 10 1 instance 8 exposed
Issued
Jul 21, 1998
Abate by
Jul 22, 1999
Penalty
Initial $5,000 · Current $2,000 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm in that
employees were exposed
to the hazard of explosion, fire and smoke inhalation from the ignition of
Polyurethane foam
material during the shredding, granulating and transfer process of foam
material to storage
hoppers.
(a)Shredder Area - Shredder/Granulator Machine - Pneumatic Conveyor -
Storage Hoppers
Employees operating the shredder/granulator machine and pneumatic conveyor
in which
an adequate fire and explosion protection and prevention system was not
provided to
prevent the ignition and transfer of combustible foam on or about 04/27/98.
ONE FEASIBLE AND ACCEPTABLE METHOD OF ABATEMENT WOULD BE TO:
1) Follow 1990 Edition of National Fire Protection Association Standard
650
Fire
standard for Pneumatic Conveying Systems for Handling Combustible
Materials which states:
a) Section 1.5.5 " Equipment and bins shall be provided with explosion
prevention or
explosion protection in accordance with either 1-5.5.1, 1-5.5.2, or
1-5.5.3.
b) Section 5.1." When material is introduced into the pneumatic system
through a hopper
and feeding device, such hopper shall be dust-tight and designed for
pressure equalization.
c) Section 6-2.2 " When the product has a tendency to stick to the rotor
or housing, the
rotor shall be cleaned periodically to maintain good balance, the housing
shall be cleaned
periodically to minimize the possibility of ignition, especially when
exposed to heated air.
d) Section 8-2.2 A through systemic inspection for safe operation. The
inspection shall
include, but not limited to the following: 1. Fire and explosion
protection and prevention
equipment, 2. Dust control equipment, 3. Housekeeping, 4. Electrical and
mechanical
equipment, relief valves, and interlocks, 5. Procedures.
Recent events (2)
  • — I (S) $2000.00
  • — Z (S) $5000.00

1910.147 C06 I

Repeat Gravity 10 1 instance 40 exposed
Issued
Jul 21, 1998
Abate by
Oct 22, 1998
Penalty
Initial $25,000 · Current $10,000 Reduced
Recent events (2)
  • — I (R) $10000.00
  • — Z (R) $25000.00

1910.157 G01

Repeat Gravity 10 1 instance 8 exposed
Issued
Jul 21, 1998
Abate by
Oct 22, 1998
Penalty
Initial $25,000 · Current $10,000 Reduced
Recent events (2)
  • — I (R) $10000.00
  • — Z (R) $25000.00

1910.157 G02

Repeat Gravity 10 1 instance 8 exposed
Issued
Jul 21, 1998
Abate by
Oct 22, 1998
Recent events (2)
  • — I (R)
  • — Z (R)

1910.157 D03

Repeat Gravity 10 1 instance 8 exposed
Issued
Jul 21, 1998
Abate by
Oct 22, 1998

View Foamex L.P., Limited Partnership's full OSHA safety record →