ASHEVILLE, NC —
OSHA Inspection: CAROLINA POWER & LIGHT COMPANY
Unprogrammed Related inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Related safety inspection of CAROLINA POWER & LIGHT COMPANY in 201 CLINGMAN AVENUE, ASHEVILLE, NC 28801 (NAICS 000000). OSHA activity number 302649777.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CAROLINA POWER & LIGHT COMPANY
- Site address
- 201 CLINGMAN AVENUE
- City
- ASHEVILLE
- State
- NC
- ZIP
- 28801
- Mailing
- ATTN: MR. JON KERIN 411 FAYETTEVILLE ST., RALEIGH, NC 27602
What kind of inspection was it?
- Inspection type
- Unprogrammed Related (G)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 4911
- Employees
- 23
- Ownership type
- A
- Industry flags
- Manufacturing safety.
Citations
1 citation on file for this inspection.
95012901
- Issued
- Apr 13, 1999
- Abate by
- Apr 19, 1999
- Penalty
- Initial $7,000 · Current $7,000
General-duty citation text
North Carolina General Statute 95-129(1) of the Occupational Safety and Health Act of North Carolina: The employer did not furnish to each of his employees conditions of employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees: a)building at 201 Clingman Avenue in Asheville -- the two overhead transmission lines were closer to the roof of the building than the distance required by the National Electrical Code, and this resulted in the electrocution of an employee of Asheville Metal Finishing, Inc. on March 18, 1999. Reference: Table 234-1 of the National Electrical Safety Code which is referenced by the National Electrical Code. NOTE: Among other methods, one feasible and acceptable method to correct this hazard is to raise the overhead transmission lines so they are at least 12.5 feet above the roof of the building.ion
Recent events (2)
- — A (S) $7000.00
- — Z (S) $7000.00
More inspections at Carolina Power & Light Company
View Carolina Power & Light Company's full OSHA safety record →
More inspections in this industry (NAICS 000000)
More inspections in NC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 302649777.