Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: CAROLINA POWER & LIGHT COMPANY

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of CAROLINA POWER & LIGHT COMPANY in 201 CLINGMAN AVENUE, ASHEVILLE, NC 28801 (NAICS 000000). OSHA activity number 302649777.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Carolina Power & Light Company — free Get an email when a new federal OSHA severe-injury report for Carolina Power & Light Company is published. One employer, no account, unsubscribe in one click.
Site address
201 CLINGMAN AVENUE
City
ASHEVILLE
State
NC
ZIP
28801
Mailing
ATTN: MR. JON KERIN 411 FAYETTEVILLE ST., RALEIGH, NC 27602
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Data loaded
NAICS code
000000
SIC code (legacy)
4911
Employees
23
Ownership type
A
Industry flags
Manufacturing safety.

1 citation on file for this inspection.

95012901

Deleted Serious 2 instances 3 exposed
Issued
Apr 13, 1999
Abate by
Apr 19, 1999
Penalty
Initial $7,000 · Current $7,000
North Carolina General Statute 95-129(1) of the Occupational Safety
and Health Act of North Carolina:  The employer did not furnish to
each of his employees conditions of employment and a place of
employment which were free from recognized hazards that were
causing or likely to cause death or serious physical harm to
employees:
a)building at 201 Clingman Avenue in Asheville  --  the two
overhead transmission lines were closer to the roof of
the building than the distance required by the National
Electrical Code, and this resulted in the electrocution
of an employee of Asheville Metal Finishing, Inc. on
March 18, 1999.
Reference:  Table 234-1 of the National Electrical Safety Code
which is referenced by the National Electrical Code.
NOTE: Among other methods, one feasible and acceptable
method to correct this hazard is to raise the
overhead transmission lines so they are at least
12.5 feet above the roof of the building.ion
Recent events (2)
  • — A (S) $7000.00
  • — Z (S) $7000.00

View Carolina Power & Light Company's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 302649777.