OSHA Inspection: SCALTECH INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of SCALTECH INC. in COASTAL EAGLE POINT OIL COMPANY, WESTVILLE, NJ 08093 (NAICS 000000). OSHA activity number 302714084.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Scaltech INC. for free Get an email when a new federal OSHA severe-injury report for Scaltech INC. is published. One employer, no account, unsubscribe in one click.
Establishment
SCALTECH INC.
Site address
COASTAL EAGLE POINT OIL COMPANY
City
WESTVILLE
State
NJ
ZIP
08093
Mailing
87 OATES RD., BLDG. #1, HOUSTON, TX 77013
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (N)
Opened
Closing conference
Case closed
Data loaded
NAICS code
000000
SIC code (legacy)
4953
Employees
2
Ownership type
Private (A)

1 citation on file for this inspection.

5(a)(1)

Serious Gravity 10 1 instance 1 exposed
Issued
Jun 2, 2000
Abate by
Jul 20, 2000
Penalty
Initial $3,500 · Current $2,625 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm to
employees in that employees
were exposed to a flash fire caused by ignition of flammable vapors by an
electrical spark from
a faulty control panel:
a). Establishment (Energy Recovery Facility) - Employees who were
operating a refinery
sludge to fuel facility were burned by a flashfire because the employer
failed to maintain
the gasket seals on the slurry drier. Flammable vapors escaping from the
slurry drier
were ingested by the electrical control panel because the employer failed
to maintain the
positive pressure environment inside the control panel (RE: NFPA #496).
This defect
was not detected because the employer failed to maintain a magnehelic
gauge which
monitored the internal pressure in the electrical control panel. On or
about
03/01/00.
A feasible method of abatement includes, but is not limited to, 1).
Relocation of the
control panel to a less hazardous location, 2). Providing a secure means
of pressurizing
the interior of the control panel and 3). Performing regular, periodic
inspections of the
system to ensure proper function of seals, detectors and alarms.
ABATEMENT NOTE: Among other methods, two feasible and acceptable means of
abatement would be to install additional permanent gas monitors at the
facility. The
second means of abatement would be to relocate the control panel outside
the vapor
generation zone.
NOTE:ABATEMENT DOCUMENTATION REQUIRED FOR THIS ITEM.
See page 2,"Notification of Corrective Action" for instructions.
Recent events (2)
  • · I (S) $2625.00
  • · Z (S) $3500.00

View Scaltech INC.'s full OSHA safety record →