FORT COLLINS, CO —
OSHA Inspection: JOHN BRUNNER AND COMPANY
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of JOHN BRUNNER AND COMPANY in 1000 LEMAY AVENUE, FORT COLLINS, CO 80524 (NAICS 000000). OSHA activity number 302766373.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- JOHN BRUNNER AND COMPANY
- Site address
- 1000 LEMAY AVENUE
- City
- FORT COLLINS
- State
- CO
- ZIP
- 80524
- Mailing
- 512 MAIN ST., WINDSOR, CO 80550
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 8051
- Employees
- 65
- Ownership type
- A
- Industry flags
- Manufacturing safety.
Citations
11 citations on file for this inspection.
5(a)(1)
- Issued
- Aug 19, 1999
- Abate by
- Sep 7, 1999
- Penalty
- Initial $1,875 · Current $1,875
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employmnent and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to the hazard of electrocution due to the lack of Ground Fault Circuit Interrupter (GFCI) protection on circuits in all wet locations throughout the facility including the dietary department, housekeeping/janitorial, utility areas, and laundry departments: Among other methods, one feasible and acceptable abatement method to correct these hazards is to install GFCI protected outlets and/or circuit breakers on all receptacles and equipemnt in required areas per the National Electrical Code Handbook (NFPA 70-1996), 517-20. a)Fort Collins Health Care, Fort Collins, CO: Electrical equipment and 110-volt a/c electrical receptacles in the dietary department, housekeeping/janitorial closets, laundry and other wet locations were not provided with GFCI overcurrent protection devices to prevent serious injury or death to employees. Condition exposed employees to the hazard of electric shocks and burns. Abatement Note: Abatement certification is required for this item. (See enclosed "Sample Abatement-Certification Letter")t-Certification
Recent events (2)
- — F (S) $1875.00
- — Z (S) $1875.00
1910.23 A05
- Issued
- Aug 19, 1999
- Abate by
- Aug 6, 1999
- Penalty
- Initial $956 · Current $500 Reduced
Recent events (2)
- — F (O) $500.00
- — Z (S) $956.00
1910.37 K02
- Issued
- Aug 19, 1999
- Abate by
- Sep 7, 1999
- Penalty
- Initial $1,125 · Current $500 Reduced
Recent events (2)
- — F (O) $500.00
- — Z (S) $1125.00
1910.37 Q01
- Issued
- Aug 19, 1999
- Abate by
- Sep 7, 1999
Recent events (2)
- — F (O)
- — Z (S)
1910.37 Q02
- Issued
- Aug 19, 1999
- Abate by
- Sep 7, 1999
Recent events (2)
- — F (O)
- — Z (S)
1910.147 C04 I
- Issued
- Aug 19, 1999
- Abate by
- Sep 7, 1999
- Penalty
- Initial $1,125 · Current $500 Reduced
Recent events (2)
- — F (O) $500.00
- — Z (S) $1125.00
1910.212 A01
- Issued
- Aug 19, 1999
- Abate by
- Sep 7, 1999
- Penalty
- Initial $1,125 · Current $1,000 Reduced
Recent events (2)
- — F (O) $1000.00
- — Z (S) $1125.00
1910.304 F04
- Issued
- Aug 19, 1999
- Abate by
- Aug 6, 1999
- Penalty
- Initial $956 · Current $500 Reduced
Recent events (2)
- — F (O) $500.00
- — Z (S) $956.00
1910.157 G02
- Issued
- Aug 19, 1999
- Abate by
- Dec 21, 1999
Recent events (2)
- — F (O)
- — Z (O)
1910.303 F
- Issued
- Aug 19, 1999
- Abate by
- Dec 21, 1999
Recent events (2)
- — F (O)
- — Z (O)
1910.305 B02
- Issued
- Aug 19, 1999
- Abate by
- Dec 21, 1999
Recent events (2)
- — F (O)
- — Z (O)
More inspections at John Brunner and Company
View John Brunner and Company's full OSHA safety record →
More inspections in this industry (NAICS 000000)
More inspections in CO
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 302766373.