OSHA Inspection: JOSEPH DAVIS, INC.
Unprogrammed Other inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Other safety inspection of JOSEPH DAVIS, INC. in 300 CAMPUS DRIVE UNIV PITTSBURGH BRADFORD, BRADFORD, PA 16701 (NAICS 000000). OSHA activity number 303708564.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- JOSEPH DAVIS, INC.
- Site address
- 300 CAMPUS DRIVE UNIV PITTSBURGH BRADFORD
- City
- BRADFORD
- State
- PA
- ZIP
- 16701
- Mailing
- 120 WEST TUPPER STREET, BUFFALO, NY 14201
What kind of inspection was it?
- Inspection type
- Unprogrammed Other (I)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 1711
- Employees
- 200
- Ownership type
- A
- Industry flags
- Construction safety.
Citations
3 citations on file for this inspection.
5(a)(1)
- Issued
- Jun 11, 2002
- Abate by
- Jul 8, 2002
- Penalty
- Initial $900 · Current $557 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were potentially exposed to fire and explosion hazards from the ignition of natural gas leaks because the hose, hose connections, & manual shut-off valve associated with portable space heating devices were not installed correctly: a.) University of Pittsburgh ~ Bradford Campus/Bradford, PA/Sports Complex - From the T-connection in the corner of the gymnasium, a mainliner hose (red color) was routed vertically then horizontally along the gymnasium's wall. The mainliner hose was then routed through a hole in the wall into the corridor off of the buildings main lobby. The hose proceeded down the wall and was routed across the floor to a portable space heater (Silent glow/150,000 BTU). The mainliner hose, hose connections, and manual shut-off valve were not installed in accordance with the National Fuel Gas Code and ANSI A10.10 - 1990 in that: (1) The mainliner hose & its connectors were not listed/labeled for use with natural gas. (2) Slip-end connectors and ring keepers (circular clamp with screw tightener) were utilized to affix the hose to the T-connection and the portable space heater (3) The mainliner hose was routed through a hole in the wall to the corridor area (4) The total run of the mainliner hose exceeded 25-feet (5) The manual gas shut-off valve was not located within 6-feet of the Silent Glow space heater ABATEMENT NOTE: Among other methods, feasible and acceptable abatement methods to correct the hazard are to comply with applicable requirements noted in ANSI A10.10-1990 ~ Safety Requirements for Space Heating Devices - Section 7 & NFPA 54/ANSI Z223.1-1999 ~ National Fuel Gas Code Section 5.5 Hose & Hose Connections: National Fuel Gas Code (NFPA 54/ANSI Z223.1) Sections 5.5.1 & 5.5.2 requires gas utilization equipment to be connected to the buildings piping with listed hosed and hose connectors. ANSI A10.10 Section 7.3.11 requires hoses and fittings to be the correct type for the fuel that is utilized by the heating unit. National Fuel Gas Code (NFPA 54/ANSI Z223.1) Sections 5.5.2 & 5.5.3 requires gas hose to be the minium practical length and not pass through walls, partitions, ceilings, or floors. ANSI A10.10 Section 7.3.9 & 7.3.16 requires the hose and fittings to be protected against damage and located to minimize damage. ANSI A10.10 Section 7.3.10. requires the total run of the hose to be short as practicable and not exceed 25-feet. ANSI A10.10 Section 7.3.15 prohibits the use of slip-end connectors and ring keepers. ANSI A10.10 Section 7.3.14 requires the hose to be securely connected to fittings via a mechanical method. Manual Shut-off Valve: National Fuel Gas Code (NFPA 54/ANSI Z223.1) Section 5.5.4 requires the manual shut-off valve to be plainly marked and located within 6-feet of the equipment served.nt
Recent events (2)
- — I (S) $557.00
- — Z (S) $900.00
1926.350 A09
- Issued
- Jun 11, 2002
- Abate by
- Jun 14, 2002
- Penalty
- Initial $573 · Current $400 Reduced
Recent events (2)
- — I (S) $400.00
- — Z (S) $573.00
1926.501 B01
- Issued
- Jun 11, 2002
- Abate by
- Jul 8, 2002
More inspections at Joseph Davis, INC.
View Joseph Davis, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 000000)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 303708564.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.