OSHA Inspection: FRITZ CHEMICAL CO. PET PRODUCTS DIVISION
Referral inspection · Health discipline
At a glance
On , OSHA opened a referral health inspection of FRITZ CHEMICAL CO. PET PRODUCTS DIVISION in 230 N. SAM HOUSTON RD., MESQUITE, TX 75149 (NAICS 000000). OSHA activity number 303907653.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- FRITZ CHEMICAL CO. PET PRODUCTS DIVISION
- Site address
- 230 N. SAM HOUSTON RD.
- City
- MESQUITE
- State
- TX
- ZIP
- 75149
- Mailing
- 230 SAM HOUSTON RD., MESQUITE, TX 75149
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 5169
- Employees
- 34
- Ownership type
- A
- Industry flags
- Manufacturing health.
Citations
2 citations on file for this inspection.
5(a)(1)
- Issued
- May 24, 2001
- Abate by
- Jun 22, 2001
- Penalty
- Initial $1,375 · Current $825 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees: fire and explosion The following requirements established by the National Fire Protection Association must be met when handling or processing combustible dust in order to minimize the risk of fire and explosion in the Glatt System Warehouse: 1. A vent in a enclosure (vessel) must be provided to limit the maximum pressure resulting from deflagration. The enclosure or vessel is referred to the entire Glatt system (Glatt machine, duct system, dust collector system and dust waste container). The enclosure must be designed to withstand fullforce of the deflageration. REFERENCE: National Fire Codes 1984, section 68, paragraph 3-1.1 2. The dust collector can be located inside a building only if one of the following exceptions is met: Exception 1: Dust collector is located adjacent to an exterior wall, is vented to the outside through straight ducts not exceeding 10 feet(3 meters) in length, and have explosion vents be located adjacent to an exterior wall, and the dust collector is vented to the outside through straight ducts not exceeding 10 ft in length, and have explosion vent. Exception 2: Dust collector is protected with an explosion suppression system. REFERENCE: National Fire Codes 1984, section 654, paragraph 4-1.3 3. All machines and equipment including duct work, storage bins, and permanently installed and portable vacuum cleaning systems shall be bonded and grounded. REFERENCE: National Fire Codes 1984, section 654, paragraph 5-5.2.4
Recent events (2)
- — I (S) $825.00
- — Z (S) $1375.00
1910.151 C
- Issued
- May 24, 2001
- Abate by
- Jun 6, 2001
- Penalty
- Initial $675 · Current $405 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees. The following requirements established by the National Fire Protection Association must be met when handling or processing combustible dust in order to minimize the risk of fire and explosion in the Glatt System Warehouse: 1. A vent in a enclosure (vessel) must be provided to limit the maximum pressure resulting from deflagration. The enclosure or vessel is referred to the entire Glatt system (Glatt machine, duct system, dust collector system and dust waste container). The enclosure must be designed to withstand fullforce of the deflageration. REFERENCE: National Fire Codes 1984, section 68, paragraph 3-1.1 2. The dust collector can be located inside a building only if one of the following exceptions is met: Exception 1: Dust collector is located adjacent to an exterior wall, is vented to the outside through straight ducts not exceeding 10 feet(3 meters) in length, and have explosion vents be located adjacent to an exterior wall, and the dust collector is vented to the outside through straight ducts not exceeding 10 ft in length, and have explosion vent. Exception 2: Dust collector is protected with an explosion suppression system. REFERENCE: National Fire Codes 1984, section 654, paragraph 4-1.3 3. All machines and equipment including duct work, storage bins, and permanently installed and portable vacuum cleaning systems shall be bonded and grounded. REFERENCE: National Fire Codes 1984, section 654, paragraph 5-5.2.4