DEWEYVILLE, TX —
OSHA Inspection: BECON CONSTRUCTION, CO.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of BECON CONSTRUCTION, CO. in 976 C.R. ROAD 4213, DEWEYVILLE, TX 77614 (NAICS 236210). OSHA activity number 304511181.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BECON CONSTRUCTION, CO.
- Site address
- 976 C.R. ROAD 4213
- City
- DEWEYVILLE
- State
- TX
- ZIP
- 77614
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Data loaded
Establishment context
- NAICS code
- 236210
- SIC code (legacy)
- 1531
- Employees
- 20000
- Ownership type
- A
Citations
1 citation on file for this inspection.
5(a)(1)
- Issued
- Mar 12, 2003
- Abate by
- Apr 7, 2003
- Penalty
- Initial $7,000 · Current $7,000
General-duty citation text
Section 5 (a) (1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or physical harm to employees in that employees were exposed to: (a)Serious burns from steam release,where on or about December 6, 2002, company was preforming Turbine Trip Test in the 1AA01-07 piping system at the Cottonwood Power Project. Two employees received serious burns to the hands , face and arms.The release was due to a missing gasket in the system. Reference: ANSI B31.1-1977 Edition-for Gaskets, in section 108.4. Company did not follow the guidelines in this paragraph. (b)Company did not follow the industry practice of evacuating the area of all non- essential personnel when start-up testing is performed. This company acknowledged the policy, but did not follow it.Reference: Accident Prevention Manual for Industrial Operations 7th. Edition page 1405. The two seriously injured employees were not required to be in the area to assist in the testing. Among others, one feasible and acceptable method to correct the hazard is the development and implementation of the following: (a)Employees not required for testing procedures should be evacuated from area prior to test. (b)Warning systems, such as horns, should be used to warn employees prior to testing. (c)Foreman should monitor the operation to assure that employees have evacuated the area prior to test. (d)Employees should be trained on the warning systems. (e)Develop procedure for verification that the various combination of flange materials, the selection of bolting materials and related rules concerning flange faces and gaskets conforms to the requirements listed in Table 108.5.2 of ANSI B31.1-1977 Edition. *** Certification and Documentation of Abatement Required ***
Recent events (2)
- — I (S) $7000.00
- — Z (S) $7000.00
More inspections at Becon Construction, CO.
View Becon Construction, CO.'s full OSHA safety record →
More inspections in this industry (NAICS 236210)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 304511181.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.