DEER PARK, TX —
OSHA Inspection: INTERCONTINENTAL TERMINALS CO
Accident-driven inspection · Safety discipline
At a glance
On , OSHA opened an accident-driven safety inspection of INTERCONTINENTAL TERMINALS CO in 1943 BATTLEGROUND RD, DEER PARK, TX 77536 (NAICS 000000). OSHA activity number 304568876.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- INTERCONTINENTAL TERMINALS CO
- Site address
- 1943 BATTLEGROUND RD
- City
- DEER PARK
- State
- TX
- ZIP
- 77536
What kind of inspection was it?
- Inspection type
- Accident-driven (A)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 5171
- Employees
- 150
- Ownership type
- A
Citations
1 citation on file for this inspection.
5(a)(1)
- Issued
- Dec 19, 2001
- Abate by
- Jan 21, 2002
- Penalty
- Initial $4,900 · Current $2,940 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to: (a)burns when opening the main steam supply valve for the facility. Among other means, one way to abate this hazard is to: (1) use the proper sized bolts obtained from the chart in, "The Pipe Fitters Blue Book" published in 1973 by the Graves Publishing Company, page 109, for a series 150 flange. The bolt for an eight inch, 150 #, carbon steel, raised face, weld neck flange should be at a minimum of 3/4" x 3 1/2". (2) to establish a protocol for the installation and inspections of piping systems in accordance with the manufacturer's specifications and/or the American National Standard Institute ANSI B31.1. (3) establish bolting procedures, train employees to utilize those procedures, and ensure their understanding of the advantages and limitations. (4) Develop and implement a maintenance program for the inspection, maintenance and replacement of bolts in conformance with the requirements set forth in Chemical Manufacturing Association, Mechanical Integrity, Sections 4.4 and 5.0, September 1994. (5) Ensure that employees follow the industry standard practice of having two threads showing above the bolt. CERTIFICATION AND DOCUMENTATION OF ABATEMENT REQUIRED.
Recent events (2)
- — R (S) $2940.00
- — Z (S) $4900.00
More inspections at Intercontinental Terminals CO
View Intercontinental Terminals CO's full OSHA safety record →
More inspections in this industry (NAICS 000000)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 304568876.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.