PITTSBURGH, PA —
OSHA Inspection: EQUITABLE GAS COMPANY
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of EQUITABLE GAS COMPANY in 9TH STREET AND FORT DUQUESNE BLVD, PITTSBURGH, PA 15222 (NAICS 221210). OSHA activity number 305106270.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- EQUITABLE GAS COMPANY
- Site address
- 9TH STREET AND FORT DUQUESNE BLVD
- City
- PITTSBURGH
- State
- PA
- ZIP
- 15222
- Mailing
- 200 ALLEGHENY CENTER MALL, PITTSBURGH, PA 15212
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221210
- SIC code (legacy)
- 4924
- Employees
- 10
- Ownership type
- A
- Industry flags
- Construction safety.
Citations
2 citations on file for this inspection.
5(a)(1)
- Issued
- Apr 1, 2003
- Abate by
- Apr 4, 2003
- Penalty
- Initial $5,000
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to explosion hazards: (a) Jobsite located at 119 Ninth Street, Pittsburgh, PA: On or about 12-18-02 crews were working to install a new service line to the CAPA school. The job consisted of installing 50 feet of 6 inch steel gas service line with the a tie in from an 8 inch line. The 6 inch new gas line was purged with air, then after the air test, the entire six inch line was purged with natural gas through the butterfly vale and into the basement of the CAPA jobsite. The line was only purged to 60 percent natural gas at the flange drop inside the meter room. This created the potential for the air and gas to mix causing a flammable atmosphere. Among other methods, one feasible and acceptable means of abatement to correct this hazard is to purge to 100 percent natural gas in accordance with the National Fuel Gas Code Handbook, 1999 Edition, page 104, sections 4.3.2 thru 4.3.4; the National Safety Council, Natural Gas Safety Handbook for Utility Workers and Contractors, pages 65 and 66; and in accordance with the Equitable Resources, Inc. Planned Shutdown/Tie- In Procedures dated approximately 12-17-02.
Recent events (2)
- — J (S)
- — Z (S) $5000.00
1926.1053 A08
- Issued
- Apr 1, 2003
- Abate by
- Apr 4, 2003
Recent events (2)
- — J (O)
- — Z (O)
More inspections at Equitable GAS Company
View Equitable GAS Company's full OSHA safety record →
More inspections in this industry (NAICS 221210)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 305106270.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.