RIVERWOODS, IL —
OSHA Inspection: MARON ELECTRIC COMPANY
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of MARON ELECTRIC COMPANY in 2500 LAKE COOK ROAD, RIVERWOODS, IL 60015 (NAICS 238210). OSHA activity number 305973570.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MARON ELECTRIC COMPANY
- Site address
- 2500 LAKE COOK ROAD
- City
- RIVERWOODS
- State
- IL
- ZIP
- 60015
- Mailing
- 5401 WEST FARGO AVE., SKOKIE, IL 60077
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Data loaded
Establishment context
- NAICS code
- 238210
- SIC code (legacy)
- 1731
- Employees
- 39
- Ownership type
- A
Citations
2 citations on file for this inspection.
5(a)(1)
- Issued
- Feb 21, 2003
- Abate by
- Feb 26, 2003
- Penalty
- Initial $3,500 · Current $3,500
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to electrical hazards: a) Socket wrenches, combination wrenches, and torque wrenches provided for employee use were not listed and insulated for the maximum working voltage of the Uninterrupted Power Supply (UPS) Battery System located in the battery room of the Support Service Building at 2500 Lake Cook Road, Riverwoods, Illinois. The non-insulated wrenches were provided to employees for use during the bolt torquing portion of the Institute of Electrical and Electronic Engineers (IEEE) certification of the UPS Battery System. A feasible means of abatement would be to provide listed and insulated non-sparking type tools as required by the 2000 Edition of the National Fire Protection Association 70E (NFPA 70E), Part IV, Chapter 3, Paragraph 3-9, Subparagraph 3-9.1. or in the alternative: a) Socket wrenches, combination wrenches, and torque wrenches provided for employee use during the bolt torquing portion of the Institute of Electrical and Electronic Engineers (IEEE) certification of the Uninterrupted Power Supply (UPS) Battery System located in the battery room of the Support Service Building at 2500 Lake Cook Road, Riverwoods, Illinois, were not tested in accordance with the standard specification for insulated and insulating hand tools and did not meet the standard specifications for tested insulated and insulating hand tools as prescribed in ASTM F1505-01. A feasible means of abatement would be to provide listed and insulated non-sparking type tools that meet the standard specifications for insulated and insulating hand tools as prescribed in ASTM F1505-01. No abatement documentation required for this item.
5(a)(1)
- Issued
- Feb 21, 2003
- Abate by
- Feb 26, 2003
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to electrical hazards: a) Employees were permitted to work in, on, and around the cell line work zone located in the battery room of the Support Service Building at 2500 Lake Cook Road, Riverwoods, Illinois, without having been provided with safety training such as, Qualified Person and Safe Work Practices training specifc to the hazards and work practices of cell line work zones, as perscribed in the 2000 Edition of the National Fire Protection Association 70E (NFPA 70E), Part IV, Chapter 2. A feasible means of abatement would be to provide safety training as required by the 2000 Edition of the National Fire Protection Association 70E (NFPA 70E), Part IV, Chapter 2, Paragraph 2-3, Subparagraphs 2-3.1 and 2-3.2, Paragraph 2-4, Subparagraphs 2-4.1 and 2-4.2, Paragraph 2-5, Subparagraphs 2-5.4.6, 2-5.4.6.1 and 2-5.4.6.2. No abatement documentation required for this item.
More inspections at Maron Electric Company