Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,193,745Inspections Most recent open 2026-08-06 Last loaded 2026-08-10

OSHA Inspection: LIEBERTS GLOBAL SERVICES

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of LIEBERTS GLOBAL SERVICES in 2500 LAKE COOK ROAD, RIVERWOODS, IL 60015 (NAICS 238210). OSHA activity number 305973588.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Lieberts Global Services for free Get an email when a new federal OSHA severe-injury report for Lieberts Global Services is published. One employer, no account, unsubscribe in one click.
Site address
2500 LAKE COOK ROAD
City
RIVERWOODS
State
IL
ZIP
60015
Mailing
610 EXECUTIVE CAMPUS DRIVE, WESTERVILLE, OH 43082
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Y
Opened
Closing conference
Case closed
Data loaded
NAICS code
238210
SIC code (legacy)
1731
Employees
2
Ownership type
A

1 citation on file for this inspection.

5(a)(1)

Serious Gravity 10 1 instance 6 exposed
Issued
Feb 21, 2003
Abate by
Feb 26, 2003
Penalty
Initial $4,500 · Current $3,000 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm to
employees in that employees
were exposed to electrical hazards:
a) Lieberts Global Services provided torque wrenches that were not listed
and insulated for the
maximum working voltage of the Uninterrupted Power Supply (UPS) Battery
System located in
the battery room of the Support Service Building at 2500 Lake Cook Road,
Riverwoods, Illinois.
The non-insulated torque wrenches were provided to employees of the Maron
Electric Company
for use during the bolt torquing portion of the Institute of Electrical
and Electronic Engineers
(IEEE) certification of the UPS Battery System.
A feasible means of abatement would be to provide listed and insulated
non-sparking type tools
as required by the 2000 Edition of the National Fire Protection
Association 70E (NFPA 70E),
Part IV, Chapter 3, Paragraph 3-9, Subparagraph 3-9.1.
or in the alternative:
a) Lieberts Global Services provided torque wrenches that were not tested
in accordance with
the standard specification for insulated and insulating hand tools and did
not meet the standard
specifications for tested insulated and insulating hand tools as
prescribed in ASTM F1505-01.
The torque wrenches were provided to employees of the Maron Electric
Company for use during
the bolt torquing portion of the Institute of Electrical and Electronic
Engineers (IEEE)
certification of the Uninterrupted Power Supply (UPS) Battery System
located in the battery
room of the Support Services Building at 2500 Lake Cook Road, Riverwoods,
Illinois.
A feasible means of abatement would be to provide listed and insulated
non-sparking type tools
that meet the standard specifications for insulated and insulating hand
tools as prescribed in
ASTM F1505-01.
No abatement documentation required for this item.
Recent events (2)
  • · I (S) $3000.00
  • · Z (S) $4500.00

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 305973588.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.