RIVERWOODS, IL ·
OSHA Inspection: LIEBERTS GLOBAL SERVICES
Unprogrammed Related inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Related safety inspection of LIEBERTS GLOBAL SERVICES in 2500 LAKE COOK ROAD, RIVERWOODS, IL 60015 (NAICS 238210). OSHA activity number 305973588.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- LIEBERTS GLOBAL SERVICES
- Site address
- 2500 LAKE COOK ROAD
- City
- RIVERWOODS
- State
- IL
- ZIP
- 60015
- Mailing
- 610 EXECUTIVE CAMPUS DRIVE, WESTERVILLE, OH 43082
What kind of inspection was it?
- Inspection type
- Unprogrammed Related (G)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Data loaded
Establishment context
- NAICS code
- 238210
- SIC code (legacy)
- 1731
- Employees
- 2
- Ownership type
- A
Citations
1 citation on file for this inspection.
5(a)(1)
- Issued
- Feb 21, 2003
- Abate by
- Feb 26, 2003
- Penalty
- Initial $4,500 · Current $3,000 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to electrical hazards: a) Lieberts Global Services provided torque wrenches that were not listed and insulated for the maximum working voltage of the Uninterrupted Power Supply (UPS) Battery System located in the battery room of the Support Service Building at 2500 Lake Cook Road, Riverwoods, Illinois. The non-insulated torque wrenches were provided to employees of the Maron Electric Company for use during the bolt torquing portion of the Institute of Electrical and Electronic Engineers (IEEE) certification of the UPS Battery System. A feasible means of abatement would be to provide listed and insulated non-sparking type tools as required by the 2000 Edition of the National Fire Protection Association 70E (NFPA 70E), Part IV, Chapter 3, Paragraph 3-9, Subparagraph 3-9.1. or in the alternative: a) Lieberts Global Services provided torque wrenches that were not tested in accordance with the standard specification for insulated and insulating hand tools and did not meet the standard specifications for tested insulated and insulating hand tools as prescribed in ASTM F1505-01. The torque wrenches were provided to employees of the Maron Electric Company for use during the bolt torquing portion of the Institute of Electrical and Electronic Engineers (IEEE) certification of the Uninterrupted Power Supply (UPS) Battery System located in the battery room of the Support Services Building at 2500 Lake Cook Road, Riverwoods, Illinois. A feasible means of abatement would be to provide listed and insulated non-sparking type tools that meet the standard specifications for insulated and insulating hand tools as prescribed in ASTM F1505-01. No abatement documentation required for this item.
Recent events (2)
- · I (S) $3000.00
- · Z (S) $4500.00
More inspections in this industry (NAICS 238210)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 305973588.