Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: PARAGON NORTHEAST CORPORATION

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of PARAGON NORTHEAST CORPORATION in LANCASTER HIGH SCHOOL, 1 FORTON, LANCASTER, NY 14086 (NAICS 236220). OSHA activity number 306248758.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Paragon Northeast Corporation — free Get an email when a new federal OSHA severe-injury report for Paragon Northeast Corporation is published. One employer, no account, unsubscribe in one click.
Site address
LANCASTER HIGH SCHOOL, 1 FORTON
City
LANCASTER
State
NY
ZIP
14086
Mailing
434 DELAWARE AVENUE, BUFFALO, NY 14202
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
236220
SIC code (legacy)
1542
Employees
6
Ownership type
A
Industry flags
Construction safety.

1 citation on file for this inspection.

5(a)(1)

Deleted Serious Gravity 03 1 instance 3 exposed
Issued
Mar 20, 2003
Abate by
Mar 25, 2003
Penalty
Initial $625 · Current $625
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm to
employees in that employees
were exposed to fire/explosion hazard:
a) On or about 2/20/03, area A on west side of bldg., at the Lancaster
High School
construction site, Lancaster, NY:  Employees were exposed to a
fire/explosion hazard
because a 1000 gal. "above ground" container of propane located outside
the building
under construction, was being used to fuel temporary heaters inside the
building. The
minimum distance between this container and the masonry wall of the
building was only
8 ft. 9 inches.
Among others, a feasible method to eliminate or materially reduce this
hazard is to move the
propane container, so that all parts of the container are at least 10 ft.
away
from the wall of the
building. This would comply with NFPA code 58, Table 3-2.2.2.
ABATEMENT CERTIFICATION REQUIREDATION
Recent events (2)
  • — J (S) $625.00
  • — Z (S) $625.00

View Paragon Northeast Corporation's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 306248758.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.