WILMINGTON, NC —
OSHA Inspection: KOSA
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of KOSA in 4600 US HWY. 421 N., WILMINGTON, NC 28401 (NAICS 325211). OSHA activity number 306593534.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- KOSA
- Site address
- 4600 US HWY. 421 N.
- City
- WILMINGTON
- State
- NC
- ZIP
- 28401
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 325211
- SIC code (legacy)
- 2821
- Employees
- 500
- Ownership type
- A
- Industry flags
- Manufacturing safety.
Citations
5 citations on file for this inspection.
95012901
- Issued
- Feb 12, 2004
- Abate by
- Mar 31, 2004
- Penalty
- Initial $3,850 · Current $3,850
General-duty citation text
North Carolina General Statute 95-129(1) of the Occupational Safety and Health Act of North Carolina: The employer did not furnish each of his employees conditions of employment and a place of employment free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to: emergency venting of steam and condensate. a)facility, near Boiler #1 - Employees were exposed to an over pressurization of the A/B Letdown station and subsequent release of steam and condensate. Among other methods, one feasible and acceptable abatement method to correct this hazard is to establish a preventative maintenance program to insure that all monitoring devices are functional and calibrated.
Recent events (2)
- — I (S) $3850.00
- — Z (S) $3850.00
95012901
- Issued
- Feb 12, 2004
- Abate by
- Mar 31, 2004
- Penalty
- Initial $3,850
General-duty citation text
North Carolina General Statute 95-129(1) of the Occupational Safety and Health Act of North Carolina: The employer did not furnish each of his employees conditions of employment and a place of employment free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to: emergency discharge of steam and condensate. a)facility, near Boiler #1 - Employees were exposed to hazards associated with pressure relief capacity that was not sufficient on the vertical discharge stack on or about August 19th 2003, which caused a release of condensate and steam. Among other methods, one feasible and acceptable abatement method to correct this hazard is to re-size the discharge piping on the pressure relief vavles. Reference: 13 NCAC 7A Chapter 13, Title 13, section 0.0405(e) Reference: ASME B31.3-2002. Sect 322.6.3: The required relieving capacity of any pressure relieving device did not include consideration of all piping systems which it protected.
Recent events (2)
- — I (S)
- — Z (S) $3850.00
95012901
- Issued
- Feb 12, 2004
- Abate by
- Mar 31, 2004
- Penalty
- Initial $3,850
General-duty citation text
North Carolina General Statute 95-129(1) of the Occupational Safety and Health Act of North Carolina: The employer did not furnish to each of his employees conditions of employment and a place of employment free from recognized hazards that were causing or likely to cause death or serious physical harm to employees, in that employees were exposed to: emergency steam release from pressure relief valves. a)facility, near boiler #1 - an 18 inch gap existed in the vertical discharge stack which allowed steam and condensate to discharge 4 feet above grade, and 6 feet below an area where employees were working. b)facility, near boiler #1 - the fixed cap at the top of the vertical discharge stack was corroded which would allow condensate and steam to exit the pipe and travel towards the ground where employees were working. c)facility, near boiler #1 - the discharge from the vertical stack was not a safe distance from the work platform where employees were working. Among other methods one feasible and acceptable abatement method to correct this hazard is to insure the components within the piping system are interconnected with no gaps, and to insure that all components are not subjected to corrosion, and that all discharge stacks be directed away from employee work areas. Reference: 13 NCAC 7A Chapter 13, Title 13, section 0.405(h). Reference: ASME B31.3-2002, section 322.6.2
Recent events (2)
- — I (S)
- — Z (S) $3850.00
95012901
- Issued
- Feb 12, 2004
- Abate by
- Mar 31, 2004
- Penalty
- Initial $3,850
General-duty citation text
North Carolina General Statute 95-129(1) of the Occupational Safety and Health Act of North Carolina: The employer did not furnish to each of his employees conditions of employment and a place of employment free from recognized hazards that were causing or likely to cause death or serious physical harm to employees, in that employees were exposed to: emergency discharge of steam and condensate. a)facility, near boiler #1 - Employees were exposed to hazards associated with drip pan drains that were corroded and not working on the discharge stack on the A/B let down line. This resulted in the build up of condensate within the stack which discharged on or about Aug 18. Among other methods, one feasible and acceptable method is to redesign the drip pans and insure they are not corroded, to allow for drainage of the condensate. Reference: 13 NCAC 7A Chapter 13, Title 13, Sect 0.0405(h) Reference ASME B31.3-2002
Recent events (2)
- — I (S)
- — Z (S) $3850.00
1910.147 F02 I
- Issued
- Feb 12, 2004
- Abate by
- Mar 31, 2004
- Penalty
- Initial $3,850 · Current $3,850
Recent events (2)
- — I (S) $3850.00
- — Z (S) $3850.00
More inspections at Kosa
View Kosa's full OSHA safety record →
More inspections in this industry (NAICS 325211)
More inspections in NC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 306593534.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.