RALLS, TX —
OSHA Inspection: C & R GIN INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of C & R GIN INC. in 620 5TH, RALLS, TX 79357 (NAICS 115111). OSHA activity number 307010215.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- C & R GIN INC.
- Site address
- 620 5TH
- City
- RALLS
- State
- TX
- ZIP
- 79357
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 115111
- SIC code (legacy)
- 0724
- Employees
- 13
- Ownership type
- A
- Industry flags
- Manufacturing safety.
Citations
3 citations on file for this inspection.
5(a)(1)
- Issued
- Apr 13, 2006
- Abate by
- Apr 25, 2006
- Penalty
- Initial $300 · Current $300
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to the condition(s) listed below: C &R Gin: On 12/09/05, and times prior thereto, employees were exposed to electrical hazards while working in the gin facility. Numerous electrical boxes, junctions, etc. did not have appropriate covers, doors, etc. while equipment was energized. Under the National Electric Code (NEC 20005), Article 547.6 states "Switches, including pushbuttons, relays. And similar devices, receptacles, circuit breakers, controllers, and fuses shall be provided with enclosures as specified in 547.5(C)." Under the National Electric Code (NEC 20005), Article 547.5 (c)(1) states "Equipment enclosures, boxes, conduit boxes, and fittings installed in areas of buildings where excessive dust may be present shall be designed to minimize the entrance of dust and shall not have openings (such as holes for attachment screws) through which dust could enter the enclosure." Note: Abatement certification and supporting documentation are required for this item.
1928.57 A07 I
- Issued
- Apr 13, 2006
- Abate by
- Apr 25, 2006
- Penalty
- Initial $300 · Current $300
1904.2 A
- Issued
- Apr 13, 2006
- Abate by
- Apr 25, 2006
More inspections in this industry (NAICS 115111)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 307010215.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.