Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ROSCOE COOP GIN

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of ROSCOE COOP GIN in 4624 CR 111, ROSCOE, TX 79545 (NAICS 115111). OSHA activity number 307010470.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Roscoe Coop GIN — free Get an email when a new federal OSHA severe-injury report for Roscoe Coop GIN is published. One employer, no account, unsubscribe in one click.
Establishment
ROSCOE COOP GIN
Site address
4624 CR 111
City
ROSCOE
State
TX
ZIP
79545
Mailing
102 PECAN ST., ROSCOE, TX 79545
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
115111
SIC code (legacy)
0724
Employees
30
Ownership type
A

3 citations on file for this inspection.

5(a)(1)

Serious Gravity 02 1 instance 30 exposed
Issued
May 18, 2006
Abate by
May 31, 2006
Penalty
Initial $700 · Current $420 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm to
employees in that employees
were exposed to the condition(s) listed below:
Roscoe Coop Gin:  On 1/05/06, and times prior thereto, employees were
exposed to electrical
hazards while working in the gin facility.  Numerous electrical boxes,
junctions, etc. did not
have appropriate covers, doors, etc. while equipment was energized.
Under the National Electric Code (NEC 20005), Article 547.6 states
"Switches, including
pushbuttons, relays. And similar devices, receptacles, circuit breakers,
controllers, and fuses
shall be provided with enclosures as specified in 547.5(C)."
Under the National Electric Code (NEC 20005), Article 547.5 (c)(1) states
"Equipment
enclosures, boxes, conduit boxes, and fittings installed in areas of
buildings where excessive dust
may be present shall be designed to minimize the entrance of dust and
shall not have openings
(such as holes for attachment screws) through which dust could enter the
enclosure."
Note: Abatement certification and supporting documentation are required
for this item.
Recent events (2)
  • — I (S) $420.00
  • — Z (S) $700.00

5(a)(1)

Serious Gravity 01 1 instance 30 exposed
Issued
May 18, 2006
Abate by
May 24, 2006
Penalty
Initial $525 · Current $315 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards
that were causing or likely to cause death or serious physical harm to
employees in that
employees were exposed to the condition(s) listed below:
Roscoe Coop Gin:  On 1/05/06, and times prior thereto, employees were
exposed to fire and
struck-by hazards while working in the gin facility where acetylene and
oxygen cylinders
were stored adjacent to each other and not secured.
Under the American National Standard Z49.1 1973, paragraph 3.2.3.3 states,
"Oxygen
cylinders in storage shall be separated from fuel-gas cylinders, reserve
stocks
of carbides, or
highly combustible materials (especially oil or grease), a minimum
distance of 20 feet or by
a noncombustible barrier at least 5 feet high having a fire-resistance
rating of at least one-
half hour".
Note: Abatement certification and supporting documentation are required
for this item.
Recent events (2)
  • — I (S) $315.00
  • — Z (S) $525.00

1928.57 D01 I

Serious Gravity 02 2 instances 30 exposed
Issued
May 18, 2006
Abate by
May 31, 2006
Penalty
Initial $700 · Current $420 Reduced
Recent events (2)
  • — I (S) $420.00
  • — Z (S) $700.00

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 307010470.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.