ROSCOE, TX —
OSHA Inspection: ROSCOE COOP GIN
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of ROSCOE COOP GIN in 4624 CR 111, ROSCOE, TX 79545 (NAICS 115111). OSHA activity number 307010470.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ROSCOE COOP GIN
- Site address
- 4624 CR 111
- City
- ROSCOE
- State
- TX
- ZIP
- 79545
- Mailing
- 102 PECAN ST., ROSCOE, TX 79545
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 115111
- SIC code (legacy)
- 0724
- Employees
- 30
- Ownership type
- A
Citations
3 citations on file for this inspection.
5(a)(1)
- Issued
- May 18, 2006
- Abate by
- May 31, 2006
- Penalty
- Initial $700 · Current $420 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to the condition(s) listed below: Roscoe Coop Gin: On 1/05/06, and times prior thereto, employees were exposed to electrical hazards while working in the gin facility. Numerous electrical boxes, junctions, etc. did not have appropriate covers, doors, etc. while equipment was energized. Under the National Electric Code (NEC 20005), Article 547.6 states "Switches, including pushbuttons, relays. And similar devices, receptacles, circuit breakers, controllers, and fuses shall be provided with enclosures as specified in 547.5(C)." Under the National Electric Code (NEC 20005), Article 547.5 (c)(1) states "Equipment enclosures, boxes, conduit boxes, and fittings installed in areas of buildings where excessive dust may be present shall be designed to minimize the entrance of dust and shall not have openings (such as holes for attachment screws) through which dust could enter the enclosure." Note: Abatement certification and supporting documentation are required for this item.
Recent events (2)
- — I (S) $420.00
- — Z (S) $700.00
5(a)(1)
- Issued
- May 18, 2006
- Abate by
- May 24, 2006
- Penalty
- Initial $525 · Current $315 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to the condition(s) listed below: Roscoe Coop Gin: On 1/05/06, and times prior thereto, employees were exposed to fire and struck-by hazards while working in the gin facility where acetylene and oxygen cylinders were stored adjacent to each other and not secured. Under the American National Standard Z49.1 1973, paragraph 3.2.3.3 states, "Oxygen cylinders in storage shall be separated from fuel-gas cylinders, reserve stocks of carbides, or highly combustible materials (especially oil or grease), a minimum distance of 20 feet or by a noncombustible barrier at least 5 feet high having a fire-resistance rating of at least one- half hour". Note: Abatement certification and supporting documentation are required for this item.
Recent events (2)
- — I (S) $315.00
- — Z (S) $525.00
1928.57 D01 I
- Issued
- May 18, 2006
- Abate by
- May 31, 2006
- Penalty
- Initial $700 · Current $420 Reduced
Recent events (2)
- — I (S) $420.00
- — Z (S) $700.00
More inspections in this industry (NAICS 115111)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 307010470.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.