Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,191,871Inspections Most recent open 2026-07-30 Last loaded 2026-08-03

OSHA Inspection: AMERIGAS EAGLE PROPANE, LIMITED PARTNERSHIP

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of AMERIGAS EAGLE PROPANE, LIMITED PARTNERSHIP in 632 SOUTH 84TH STREET, WEST ALLIS, WI 53214 (NAICS 454312). OSHA activity number 307060962.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Amerigas Eagle Propane, Limited Partnership for free Get an email when a new federal OSHA severe-injury report for Amerigas Eagle Propane, Limited Partnership is published. One employer, no account, unsubscribe in one click.
Site address
632 SOUTH 84TH STREET
City
WEST ALLIS
State
WI
ZIP
53214
Mailing
600 NORTH BROADWAY, AURORA, IL 60505
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
454312
SIC code (legacy)
5984
Employees
15
Ownership type
A

1 citation on file for this inspection.

5(a)(1)

Serious Gravity 10 1 instance 2 exposed
Issued
Aug 17, 2005
Abate by
Aug 22, 2005
Penalty
Initial $5,000 · Current $5,000
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The
employer did not furnish
employment and a place of employment which were free from recognized
hazards that were
causing or likely to cause death or serious physical harm to employees in
that employees were
exposed to the hazards of fire and explosions from ignition of flammable
gas escaping from
tanks being serviced or filled with liquid propane (LP):
(a)Ventilation in the fill Room at the facility on May 6, 2005, was not
adequate to
prevent the accumulation of flammable LP gas in all parts of the Fill Room
where
it may be released or settle.  Among other methods to correct this
condition , the
employer could: 1) Redesign and install an effective mechanical
ventilation system
which will provide an adequate purge of stagnate hydrocarbons in all parts
of the
room at no less than a minimum of 1 CFM (cubic foot per minute) of air flow
per square foot of floor area in the Fill Room so that the entire floor
area is
vented in accordance with an industry consensus standard, NFPA (National
Fire
Protection Association) #58, or, 2) Provide natural ventilation openings
in the Fill
Room designed in accordance with current engineering design principles, to
ensure the minimum 1 CFM per square foot of floor area and a uniform
venting
of the entire floor area as much as practical and in accordance with NFPA
#58.
No certification required.  Violation Abated.on