WEST ALLIS, WI ·
OSHA Inspection: AMERIGAS EAGLE PROPANE, LIMITED PARTNERSHIP
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of AMERIGAS EAGLE PROPANE, LIMITED PARTNERSHIP in 632 SOUTH 84TH STREET, WEST ALLIS, WI 53214 (NAICS 454312). OSHA activity number 307060962.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- AMERIGAS EAGLE PROPANE, LIMITED PARTNERSHIP
- Site address
- 632 SOUTH 84TH STREET
- City
- WEST ALLIS
- State
- WI
- ZIP
- 53214
- Mailing
- 600 NORTH BROADWAY, AURORA, IL 60505
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 454312
- SIC code (legacy)
- 5984
- Employees
- 15
- Ownership type
- A
Citations
1 citation on file for this inspection.
5(a)(1)
- Issued
- Aug 17, 2005
- Abate by
- Aug 22, 2005
- Penalty
- Initial $5,000 · Current $5,000
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to the hazards of fire and explosions from ignition of flammable gas escaping from tanks being serviced or filled with liquid propane (LP): (a)Ventilation in the fill Room at the facility on May 6, 2005, was not adequate to prevent the accumulation of flammable LP gas in all parts of the Fill Room where it may be released or settle. Among other methods to correct this condition , the employer could: 1) Redesign and install an effective mechanical ventilation system which will provide an adequate purge of stagnate hydrocarbons in all parts of the room at no less than a minimum of 1 CFM (cubic foot per minute) of air flow per square foot of floor area in the Fill Room so that the entire floor area is vented in accordance with an industry consensus standard, NFPA (National Fire Protection Association) #58, or, 2) Provide natural ventilation openings in the Fill Room designed in accordance with current engineering design principles, to ensure the minimum 1 CFM per square foot of floor area and a uniform venting of the entire floor area as much as practical and in accordance with NFPA #58. No certification required. Violation Abated.on
More inspections at Amerigas Eagle Propane, Limited Partnership
View Amerigas Eagle Propane, Limited Partnership's full OSHA safety record →