CHICAGO, IL ·
OSHA Inspection: KING KOLD
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of KING KOLD in 837 N CALIFORNIA AVENUE, CHICAGO, IL 60622 (NAICS 311613). OSHA activity number 307381830.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- KING KOLD
- Site address
- 837 N CALIFORNIA AVENUE
- City
- CHICAGO
- State
- IL
- ZIP
- 60622
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (N)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311613
- SIC code (legacy)
- 2013
- Employees
- 49
- Ownership type
- Private (A)
Citations
4 citations on file for this inspection.
1910.120 Q01
- Issued
- Apr 5, 2005
- Abate by
- Sep 28, 2005
- Penalty
- Initial $875 · Current $300 Reduced
Recent events (2)
- · I (S) $300.00
- · Z (S) $875.00
1910.120 Q02 I
- Issued
- Apr 5, 2005
- Abate by
- Sep 28, 2005
1910.120 Q09 I
- Issued
- Apr 5, 2005
- Abate by
- Sep 28, 2005
5(a)(1)
- Issued
- Apr 5, 2005
- Abate by
- Jan 3, 2006
- Penalty
- Initial $875 · Current $300 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to: Refrigerating Machinery Room: On or about November 04, 2004, employees were exposed to hazards arising from the employer's non-compliance with the prescribed safeguards of the ANSI/ASHRAE Standard 15-2001, "Safety Standard for Refrigeration Systems", or of an equivalent and generally accepted standard. Specifically: a. The refrigerating machinery room ammonia alarm did not have a manual reset located inside the room. (ANSI/ASHRAE 8.11.2.1) b. Two of the machinery room doors opened inwards instead of outwards. (ANSI/ASHRAE 8.11.2) c. Employer had no information concerning the capability of the machinery room mechanical ventilation system to exhaust an accumulation of refrigerant due to leaks or a rupture of the system in accord with the minimum requirements as prescribed by the ANSI/ASHRAE Standard, or equivalent. (ANSI/ASHRAE 8.11.5) d. A schematic was not provided, at a location convenient to the operation of the refrigeration system, giving directions for the operation of the system. (ANSI/ASHRAE 11.7) e. Emergency shutdown procedures, including precautions to be observed in case of a breakdown or leak, were not posted outside the refrigerating machinery room, immediately adjacent to each door. (ANSI/ASHRAE 11.7)
Recent events (2)
- · I (S) $300.00
- · Z (S) $875.00
More inspections at King Kold
View King Kold's full OSHA safety record →
More inspections in this industry (NAICS 311613)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 307381830.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.