CLARKS POINT, AK ·
OSHA Inspection: ICICLE SEAFOODS INC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of ICICLE SEAFOODS INC in P/V ARCTIC STAR, CLARKS POINT, AK 99569 (NAICS 311712). OSHA activity number 307506535.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ICICLE SEAFOODS INC
- Site address
- P/V ARCTIC STAR
- City
- CLARKS POINT
- State
- AK
- ZIP
- 99569
- Mailing
- PO BOX 79003, SEATTLE, WA 98119
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (N)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311712
- SIC code (legacy)
- 2092
- Employees
- 163
- Ownership type
- Private (A)
Citations
4 citations on file for this inspection.
1910.119 D02 IA
- Issued
- Aug 23, 2010
- Abate by
- Sep 9, 2010
- Penalty
- Initial $2,500 · Current $2,500
Recent events (2)
- · I (S) $2500.00
- · Z (S) $2500.00
1910.119 D02 IC
- Issued
- Aug 23, 2010
- Abate by
- Sep 23, 2010
Recent events (2)
- · I (S)
- · Z (S)
1910.119 D03 II
- Issued
- Aug 23, 2010
- Abate by
- Sep 23, 2010
- Penalty
- Initial $12,500 · Current $12,500
General-duty citation text
29 CFR 1910.119(d)(3)(ii): The employer did not document that the equipment in the process complied with recognized and generally accepted good engineering practices: (a)P/V Arctic Star: On or about July 8, 2010, and at times prior thereto, direction of flow and refrigerant state labeling had been removed and not replaced in areas including but not limited to the high pressure receiver deck, low pressure receiver and cold storage, and condenser room. Piping identification was not being maintained as required by the Process Safety Management (PSM) Program which incorporated by reference ASHRAE 15, ASHRAE 26, ANSI A13.1, and IIAR Bulletin 114. This condition exposed employees to inhalation and eye and skin burn hazards in the event of an uncontrolled release of anhydrous ammonia. (b)P/V Arctic Star: On or about July 8, 2010, and at times prior thereto, valve identification tags were either missing, removed, taped over, or painted over on equipment including but not limited to the high pressure receiver, Sullair Room oil separator, compressors including high stage, swing, boosters, condenser room, and air purger system. Valve identification was not being maintained as required by the PSM Program which incorporated by reference ASHRAE 15 and ASHRAE 26. This condition exposed employees to inhalation and eye and skin burn hazards in the event of an uncontrolled release of anhydrous ammonia. ICICLE SEAFOODS, INC. WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCCUPATIONAL SAFETY AND HEALTH STANDARD WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 307504050, CITATION NUMBER 1, ITEM NUMBER 2A, ISSUED ON 04/22/2009, WITH RESPECT TO A WORKPLACE LOCATED AT P/V BERING STAR, DUTCH HARBOR, ALASKA.
Recent events (2)
- · I (R) $12500.00
- · Z (R) $12500.00
1910.119 J04 II
- Issued
- Aug 23, 2010
- Abate by
- Sep 23, 2010
General-duty citation text
29 CFR 1910.119(j)(4)(ii): Inspections and testing procedures performed on process equipment to maintain its mechanical integrity, did not follow recognized and generally accepted good engineering practices: (a)P/V Arctic Star: On or about July 8, 2010, and at times prior thereto, the inspection frequency for temperature and pressure gauges for process equipment including but not limited to compressors, pressure vessels, condensers, and oil separators had not been completed. The Process Safety Management (PSM) program incorporated IIAR Bulletin 110 as an acceptable engineering practice. This condition exposed employees to inhalation and eye and skin burn hazards in the event of an uncontrolled anhydrous ammonia release onboard the vessel. (b)P/V Arctic Star: On or about July 8, 2010, and at times prior thereto, the calibration frequency for portable and fixed anhydrous ammonia monitoring equipment was not maintained. The Process Safety Management (PSM) program incorporated IIAR Bulletin 110 as an acceptable engineering practices. This condition exposed employees to inhalation and eye and skin burn hazards in the event of an uncontrolled anhydrous ammonia release onboard the vessel. (1)Manning Systems Model# EC-P1-NH3, Serial#'s 0321 and 0709, which were in use and due calibration "07/08." (2)International Sensor Technology Model# SM95, Serial# SM4785-9939 was in use and showed a last alarm inspection of "2-20-10." ICICLE SEAFOODS, INC. WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCCUPATIONAL SAFETY AND HEALTH STANDARD WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 307504050, CITATION NUMBER 1, ITEM NUMBER 2B, ISSUED ON 04/22/2009, WITH RESPECT TO A WORKPLACE LOCATED AT P/V BERING STAR, DUTCH HARBOR, ALASKA.
Recent events (2)
- · I (R)
- · Z (R)
More inspections at Icicle Seafoods INC
View Icicle Seafoods INC's full OSHA safety record →
More inspections in this industry (NAICS 311712)
More inspections in AK
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 307506535.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.