Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: KESTREL MANAGEMENT L.P.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of KESTREL MANAGEMENT L.P. in 1999 BROADWAY, SUITE 250, DENVER, CO 80201 (NAICS 561210). OSHA activity number 307528547.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Kestrel Management L.P. — free Get an email when a new federal OSHA severe-injury report for Kestrel Management L.P. is published. One employer, no account, unsubscribe in one click.
Site address
1999 BROADWAY, SUITE 250
City
DENVER
State
CO
ZIP
80201
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
561210
SIC code (legacy)
8744
Employees
200
Ownership type
A

5 citations on file for this inspection.

5(a)(1)

Serious Gravity 03 1 instance 3 exposed
Issued
Apr 7, 2005
Abate by
May 31, 2005
Penalty
Initial $1,375 · Current $687 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards
that were causing or likely to cause death or serious physical harm to
employees in that
employees were exposed arc flash and arc blast:
(a)Kestrel Management L.P. at 1999 Broadway Blvd., Denver, CO 80201: On
March 1, 2005 two employees were exposed to electrical hazards when
opening electrical panels without performing a Flash Hazard Analysis.
Employees used a procedure to manually unlock the latch from the right side
of the cabinet with a screw driver and move the latch on the top front to
allow
the panel to open.  This procedure conducted without performing a Flash
Hazard Analysis exposed the employees to arc flash and arc blast when they
approached a bus from approximately 15 inches that was energized to 480
Volts phase to phase.
Abatement Note: National Fire Protection Association 70E paragraph 130.3
Flash Hazard
Analysis describes the flash hazard analysis process and equipment to
protect
personnel from
the possibility of being injured by arc flash.  The analysis shall
determine the flash protection
boundry and the personal protective equipment that employees within the
flash protection
boundry shall use.
Among other methods, one feasible and acceptable abatement method to
correct this hazard
is to follow established procedures as described in NFPA 70E as well as
ensure a detailed
inspection of the cabinets is performed when the infrared scans are
conducted.
(b)Kestrel Management L.P. at 1999 Broadway Blvd., Denver, CO 80201: On
March 1, 2005 two employees were exposed to electrical hazards when
opening electrical panels in that the panels were not properly marked to
warn
of potential electric arc flash hazards. This condition exposed the
employees to
arc flash when they approached a bus energized to 480 Volts phase to phase
from approximately 15 inches.
Abatement Note: The National Electrical Code Handbook paragraph 110.16
gives direction
that switchboards, panelboards, industrial control planels, and motor
control centers shall be
field marked to warn qualified persons of potential electric arc flash
hazards.
Among other methods, one feasible and acceptable abatement method to
correct this hazard
is to follow established procedures as described in the NEC paragraph
110.16.
Abatement Note:  Abatement certification is required for this item (see
enclosed "Sample
Abatement-Certification Letter").-Certification
Recent events (2)
  • — I (S) $687.00
  • — Z (S) $1375.00

1910.133 A03

Other-than-serious Gravity 03 1 instance 1 exposed
Issued
Apr 7, 2005
Abate by
Apr 17, 2005
Penalty
Initial $1,375 · Current $688 Reduced
Recent events (2)
  • — I (O) $688.00
  • — Z (S) $1375.00

1910.335 A01 I

Other-than-serious Gravity 03 1 instance 4 exposed
Issued
Apr 7, 2005
Abate by
Apr 17, 2005
Recent events (2)
  • — I (O)
  • — Z (S)

1910.303 B01

Other-than-serious Gravity 10 1 instance 3 exposed
Issued
Apr 7, 2005
Abate by
Apr 17, 2005
Penalty
Initial $3,500 · Current $1,400 Reduced
Recent events (2)
  • — I (O) $1400.00
  • — Z (S) $3500.00

1910.332 B01

Other-than-serious Gravity 03 1 instance 4 exposed
Issued
Apr 7, 2005
Abate by
Jul 19, 2005
Penalty
Initial $1,375 · Current $687 Reduced
Recent events (2)
  • — I (O) $687.00
  • — Z (S) $1375.00

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 307528547.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.