DENVER, CO —
OSHA Inspection: KESTREL MANAGEMENT L.P.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of KESTREL MANAGEMENT L.P. in 1999 BROADWAY, SUITE 250, DENVER, CO 80201 (NAICS 561210). OSHA activity number 307528547.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- KESTREL MANAGEMENT L.P.
- Site address
- 1999 BROADWAY, SUITE 250
- City
- DENVER
- State
- CO
- ZIP
- 80201
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 561210
- SIC code (legacy)
- 8744
- Employees
- 200
- Ownership type
- A
Citations
5 citations on file for this inspection.
5(a)(1)
- Issued
- Apr 7, 2005
- Abate by
- May 31, 2005
- Penalty
- Initial $1,375 · Current $687 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed arc flash and arc blast: (a)Kestrel Management L.P. at 1999 Broadway Blvd., Denver, CO 80201: On March 1, 2005 two employees were exposed to electrical hazards when opening electrical panels without performing a Flash Hazard Analysis. Employees used a procedure to manually unlock the latch from the right side of the cabinet with a screw driver and move the latch on the top front to allow the panel to open. This procedure conducted without performing a Flash Hazard Analysis exposed the employees to arc flash and arc blast when they approached a bus from approximately 15 inches that was energized to 480 Volts phase to phase. Abatement Note: National Fire Protection Association 70E paragraph 130.3 Flash Hazard Analysis describes the flash hazard analysis process and equipment to protect personnel from the possibility of being injured by arc flash. The analysis shall determine the flash protection boundry and the personal protective equipment that employees within the flash protection boundry shall use. Among other methods, one feasible and acceptable abatement method to correct this hazard is to follow established procedures as described in NFPA 70E as well as ensure a detailed inspection of the cabinets is performed when the infrared scans are conducted. (b)Kestrel Management L.P. at 1999 Broadway Blvd., Denver, CO 80201: On March 1, 2005 two employees were exposed to electrical hazards when opening electrical panels in that the panels were not properly marked to warn of potential electric arc flash hazards. This condition exposed the employees to arc flash when they approached a bus energized to 480 Volts phase to phase from approximately 15 inches. Abatement Note: The National Electrical Code Handbook paragraph 110.16 gives direction that switchboards, panelboards, industrial control planels, and motor control centers shall be field marked to warn qualified persons of potential electric arc flash hazards. Among other methods, one feasible and acceptable abatement method to correct this hazard is to follow established procedures as described in the NEC paragraph 110.16. Abatement Note: Abatement certification is required for this item (see enclosed "Sample Abatement-Certification Letter").-Certification
Recent events (2)
- — I (S) $687.00
- — Z (S) $1375.00
1910.133 A03
- Issued
- Apr 7, 2005
- Abate by
- Apr 17, 2005
- Penalty
- Initial $1,375 · Current $688 Reduced
Recent events (2)
- — I (O) $688.00
- — Z (S) $1375.00
1910.335 A01 I
- Issued
- Apr 7, 2005
- Abate by
- Apr 17, 2005
Recent events (2)
- — I (O)
- — Z (S)
1910.303 B01
- Issued
- Apr 7, 2005
- Abate by
- Apr 17, 2005
- Penalty
- Initial $3,500 · Current $1,400 Reduced
Recent events (2)
- — I (O) $1400.00
- — Z (S) $3500.00
1910.332 B01
- Issued
- Apr 7, 2005
- Abate by
- Jul 19, 2005
- Penalty
- Initial $1,375 · Current $687 Reduced
Recent events (2)
- — I (O) $687.00
- — Z (S) $1375.00
More inspections in this industry (NAICS 561210)