OSHA Inspection: NORTH ARKANSAS ELECTRIC COOPERATIVE, INC.

Accident-driven inspection · Safety discipline

On , OSHA opened an accident-driven safety inspection of NORTH ARKANSAS ELECTRIC COOPERATIVE, INC. in 1520 HIGHWAY 62 EAST, MOUNTAIN HOME, AR 72653 (NAICS 221119). OSHA activity number 307881870.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch North Arkansas Electric Cooperative, INC. for free Get an email when a new federal OSHA severe-injury report for North Arkansas Electric Cooperative, INC. is published. One employer, no account, unsubscribe in one click.
Site address
1520 HIGHWAY 62 EAST
City
MOUNTAIN HOME
State
AR
ZIP
72653
Mailing
PO BOX 1000, SALEM, AR 72576
Inspection type
Accident-driven (A)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (N)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221119
SIC code (legacy)
4911
Employees
124
Ownership type
Private (A)

3 citations on file for this inspection.

5(a)(1)

Deleted Serious Gravity 10 1 instance 5 exposed
Issued
Dec 15, 2004
Abate by
Feb 3, 2005
Penalty
Initial $4,900 · Current $4,900
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The
employer did not furnish
employment and a place of employment which were free from recognized
hazards that were
causing or likely to cause death or serious physical harm to employees in
that employees were
exposed to:
Hazards of an electrical explosion on or about August 31, 2004 at the
Baxter sub-
station where the Cooper Systems Voltage Regulator manual #S 225-10-4C was
not consulted or followed, and the company safety procedures regarding
regulator
removal were not followed in that the regulator was not neutralized prior
to
operating the integral switch that closed the regulator bypass switch and
opened
the load and source regulator switch.
Among other methods, one feasible and acceptable abatement method to
correct this
hazard is to ensure crews working in substations with voltage regulators
follow the
established manufacturer's manual and procedures.r's
Recent events (2)
  • · F (S) $4900.00
  • · Z (S) $4900.00

1910.269 A02 VI

Other-than-serious Gravity 10 2 instances 2 exposed
Issued
Dec 15, 2004
Abate by
Feb 3, 2005
Penalty
Initial $4,900 · Current $4,900
Recent events (2)
  • · F (O) $4900.00
  • · Z (S) $4900.00

1910.269 M03 V

Deleted Serious Gravity 10 1 instance 5 exposed
Issued
Dec 15, 2004
Abate by
Feb 3, 2005
Penalty
Initial $4,900 · Current $4,900
Recent events (2)
  • · F (S) $4900.00
  • · Z (S) $4900.00

View North Arkansas Electric Cooperative, INC.'s full OSHA safety record →