MOOSIC, PA —
OSHA Inspection: VYCOM INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of VYCOM INC. in 801 E. COREY STREET, MOOSIC, PA 18507 (NAICS 326113). OSHA activity number 307912295.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- VYCOM INC.
- Site address
- 801 E. COREY STREET
- City
- MOOSIC
- State
- PA
- ZIP
- 18507
- Mailing
- 801 E. COREY STREET, MOOSIC, PA 18507
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 326113
- SIC code (legacy)
- 3081
- Employees
- 100
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.252 A02 XV
- Issued
- Jan 24, 2005
- Abate by
- Mar 11, 2005
- Penalty
- Initial $2,125 · Current $1,595 Reduced
Recent events (2)
- — I (S) $1595.00
- — Z (S) $2125.00
1910.252 B03
- Issued
- Jan 24, 2005
- Abate by
- Mar 11, 2005
- Penalty
- Initial $2,125 · Current $1,595 Reduced
Recent events (2)
- — I (S) $1595.00
- — Z (S) $2125.00
1910.252 A02 IIIB
- Issued
- Jan 24, 2005
- Abate by
- Mar 11, 2005
- Penalty
- Initial $2,125 · Current $2,125
Recent events (2)
- — I (S) $2125.00
- — Z (S) $2125.00
1910.22 A01
- Issued
- Jan 24, 2005
- Abate by
- Mar 11, 2005
- Penalty
- Initial $2,125 · Current $1,595 Reduced
Recent events (2)
- — I (S) $1595.00
- — Z (S) $2125.00
5(a)(1)
- Issued
- Jan 24, 2005
- Abate by
- Sep 30, 2005
- Penalty
- Initial $2,125 · Current $1,595 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to severe burn injuries from a dust explosion hazard that could have resulted from, or been exacerbated by, the propagation of a fire or explosion in the duct work that was not equipped with isolation devices and the dust collection systems that were located inside of the building structure. a) Building #4, Dry Blend: The dust collection systems for Tower #1 and Tower #2 were located inside of the building, on or about October 5, 2004. b) Building #4, Dry Blend: Duct work connecting pieces of equipment were not equipped with isolation devices, on or about October 5, 2004. "AMONG OTHER METHODS, ONE FEASIBLE AND ACCEPTABLE ABATEMENT METHOD TO CORRECT THESE HAZARDS IS TO RELOCATE THE DUST COLLECTION SYSTEMS TO AN OUTSIDE AREA PER NFPA 654, SECTION 3.13.1.1 AND TO INSTALL ISOLATION DEVICES IN THE DUCT WORK PER NFPA 654, SECTION 3.13.1.5." ABATEMENT CERTIFICATION REQUIREDATION
Recent events (3)
- — P (S) $1595.00
- — I (S) $1595.00
- — Z (S) $2125.00
More inspections at Vycom INC.