Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: A. DUDA & SONS, INC.

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of A. DUDA & SONS, INC. in 6007 STATE ROAD 29, S., LA BELLE, FL 33975 (NAICS 311421). OSHA activity number 308405158.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch A. Duda & Sons, INC. — free Get an email when a new federal OSHA severe-injury report for A. Duda & Sons, INC. is published. One employer, no account, unsubscribe in one click.
Site address
6007 STATE ROAD 29, S.
City
LA BELLE
State
FL
ZIP
33975
Mailing
P.O. BOX 519, LA BELLE, FL 33975
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311421
SIC code (legacy)
2033
Employees
130
Ownership type
A

3 citations on file for this inspection.

5(a)(1)

Serious Gravity 03 1 instance 130 exposed
Issued
May 24, 2005
Abate by
Aug 23, 2005
Penalty
Initial $1,875 · Current $1,875
Section 5(a)1 of the Occupational Safety and Health Act of 1970:
The employer did not furnish to each of his employees employment and a
place of employment
which were free from recognized hazards that were causing or likely to
cause death or serious
physical harm to employees in that employees were exposed to anhydrous
ammonia refrigerant:
(a)On or about 05/19/05, the processing ammonia refrigeration system did
not meet
requirements for the safe design, construction, installation, and
operation as presented
in ANSI/ASHRAE Standard 15-2001, Safety Standard for Refrigeration
Systems, in that
the receiver's pressure relief devices did not discharge to the atmosphere
at a location
at least 15 feet (4.57 meters) above the adjoining ground level
(ANSI/ASHRAE 15-2001,
Section 9.7.8.2). A feasible and acceptable abatement method is to plumb
the safety
valve discharge to at least 15 feet above ground level.
PLEASE NOTE: DOCUMENTATION AND CERTIFICATION OF ABATEMENT
IS REQUIRED FOR THIS VIOLATION.ION

1910.151 C

Serious Gravity 03 1 instance 3 exposed
Issued
May 24, 2005
Abate by
Jul 12, 2005
Penalty
Initial $1,875 · Current $1,875

1910.212 A01

Serious Gravity 01 1 instance 4 exposed
Issued
May 24, 2005
Abate by
Jul 12, 2005
Penalty
Initial $1,125 · Current $1,125