OSHA Inspection: EXXON MOBIL

Referral inspection · Health discipline

On , OSHA opened a referral health inspection of EXXON MOBIL in 3000 BAYWAY DR., BAYTOWN, TX 77522 (NAICS 325998). OSHA activity number 308593177.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Exxon Mobil — free Get an email when a new federal OSHA severe-injury report for Exxon Mobil is published. One employer, no account, unsubscribe in one click.
Establishment
EXXON MOBIL
Site address
3000 BAYWAY DR.
City
BAYTOWN
State
TX
ZIP
77522
Mailing
5000 BAYWAY DR., BAYTOWN, TX 77520
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
Y
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325998
SIC code (legacy)
2869
Employees
1000
Ownership type
A

1 citation on file for this inspection.

5(a)(1)

Deleted Serious Gravity 10 1 instance 15 exposed
Issued
Dec 21, 2006
Abate by
Jan 8, 2007
Penalty
Initial $5,000
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm to
employees in that:
(a)On or about 7/2/06 and times prior to, employees were exposed to the
hazard of fire and/or explosion due to deflagration of flammable material
in the bromobutyl finishing process. (1) There was an accumulation of
flammable material within the combustible or explosive range, (2) The
rate of air exhausted, in the case of flammable gases and vapors, was not
sufficient to result at all times in a concentration, in the hood, duct
work,
and subsequent equipment, below 25 percent of the lower explosive limit
(3) A source of ignition was not prevented in the exhaust system, (4) A
complete inspection of the entire system was not performed at least once
each year, (5) Manufacturer's recommendations for the maintenance of
various components of the local exhaust ventilating system was not
included in the maintenance schedule.  Among other methods, feasible and
acceptable abatement methods to abate these hazards would include
compliance with recognized industry practices such as, but not limited to
NFPA 30 Code for Flammable and Combustible Liquids, ANSI Z9.2-2001
Fundamentals Governing the Design and Operation of Local Exhaust
Systems, NFPA No. 91 Blower and Exhaust Systems and NFPA 77
Recommended Practice on Static Electricity.
*** Certification and Documentation of Abatement Required ***
Recent events (2)
  • — R (S)
  • — Z (S) $5000.00

View Exxon Mobil's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 308593177.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.