BAYTOWN, TX —
OSHA Inspection: EXXON MOBIL
Referral inspection · Health discipline
At a glance
On , OSHA opened a referral health inspection of EXXON MOBIL in 3000 BAYWAY DR., BAYTOWN, TX 77522 (NAICS 325998). OSHA activity number 308593177.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- EXXON MOBIL
- Site address
- 3000 BAYWAY DR.
- City
- BAYTOWN
- State
- TX
- ZIP
- 77522
- Mailing
- 5000 BAYWAY DR., BAYTOWN, TX 77520
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 325998
- SIC code (legacy)
- 2869
- Employees
- 1000
- Ownership type
- A
Citations
1 citation on file for this inspection.
5(a)(1)
- Issued
- Dec 21, 2006
- Abate by
- Jan 8, 2007
- Penalty
- Initial $5,000
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that: (a)On or about 7/2/06 and times prior to, employees were exposed to the hazard of fire and/or explosion due to deflagration of flammable material in the bromobutyl finishing process. (1) There was an accumulation of flammable material within the combustible or explosive range, (2) The rate of air exhausted, in the case of flammable gases and vapors, was not sufficient to result at all times in a concentration, in the hood, duct work, and subsequent equipment, below 25 percent of the lower explosive limit (3) A source of ignition was not prevented in the exhaust system, (4) A complete inspection of the entire system was not performed at least once each year, (5) Manufacturer's recommendations for the maintenance of various components of the local exhaust ventilating system was not included in the maintenance schedule. Among other methods, feasible and acceptable abatement methods to abate these hazards would include compliance with recognized industry practices such as, but not limited to NFPA 30 Code for Flammable and Combustible Liquids, ANSI Z9.2-2001 Fundamentals Governing the Design and Operation of Local Exhaust Systems, NFPA No. 91 Blower and Exhaust Systems and NFPA 77 Recommended Practice on Static Electricity. *** Certification and Documentation of Abatement Required ***
Recent events (2)
- — R (S)
- — Z (S) $5000.00
More inspections at Exxon Mobil