Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: TIMBER ROOTS MTD

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of TIMBER ROOTS MTD in 131 W INDUSTRIAL, PO BOX 257, VALLEY CENTER, KS 67147 (NAICS 321214). OSHA activity number 308640465.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Timber Roots MTD — free Get an email when a new federal OSHA severe-injury report for Timber Roots MTD is published. One employer, no account, unsubscribe in one click.
Establishment
TIMBER ROOTS MTD
Site address
131 W INDUSTRIAL, PO BOX 257
City
VALLEY CENTER
State
KS
ZIP
67147
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
321214
SIC code (legacy)
2439
Employees
85
Ownership type
A

3 citations on file for this inspection.

5(a)(1)

Serious Gravity 02 2 instances 4 exposed
Issued
Oct 25, 2005
Abate by
Jan 31, 2006
Penalty
Initial $1,500 · Current $1,200 Reduced
Section 5(a)1 of the Occupational Safety and Health Act of 1970: The
employer did not furnish
employment and a place of employment which were free from recognized
hazards that were
causing or likely to cause death or serious physical harm to employees in
that employees were
exposed to explosive fragmentation hazards:
Employees were exposed to explosive fragmentation hazards from plastic PVC
pipe being used
to distribute compressed air throughout both production buildings.
Employees were exposed to
the hazard of working around lengths of plastic PVC pipe being used to
distribute compressed
air (at 120 psi) throughout the buildings.
AMONG OTHER METHODS, ONE FEASIBLE AND ACCEPTABLE METHOD TO
CORRECT THIS HAZARD: Is to replace the PVC piping with a type of pipe that
is
approved for transporting compressed gases in above ground locations such
as metal pipe
as recommended by the Plastic Pipe Institute and ANSI/ASME B31.1 1973
Power Piping.
29 CFR 1903.19(d)(1) requires certification and documentation that the
abatement of the
above violation is complete.
Recent events (2)
  • — I (S) $1200.00
  • — Z (S) $1500.00

1910.24 B

Other-than-serious Gravity 01 2 instances 4 exposed
Issued
Oct 25, 2005
Abate by
Aug 4, 2006
Penalty
Initial $1,125 · Current $600 Reduced
Recent events (2)
  • — I (O) $600.00
  • — Z (S) $1125.00

1910.213 A12

Other-than-serious Gravity 02 5 instances 6 exposed
Issued
Oct 25, 2005
Abate by
Nov 4, 2005
Penalty
Initial $1,500 · Current $1,200 Reduced
Recent events (2)
  • — I (O) $1200.00
  • — Z (S) $1500.00

View Timber Roots MTD's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 308640465.