ROTHSCHILD, WI —
OSHA Inspection: WESTON POWER PLANT
Referral inspection · Health discipline
At a glance
On , OSHA opened a referral health inspection of WESTON POWER PLANT in 2501 MORRISON AVE, ROTHSCHILD, WI 54474 (NAICS 221122). OSHA activity number 309841799.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- WESTON POWER PLANT
- Site address
- 2501 MORRISON AVE
- City
- ROTHSCHILD
- State
- WI
- ZIP
- 54474
- Mailing
- P.O. BOX 38, ROTHSCHILD, WI 54474
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221122
- SIC code (legacy)
- 4911
- Employees
- 205
- Ownership type
- A
Citations
1 citation on file for this inspection.
5(a)(1)
- Issued
- Oct 13, 2009
- Abate by
- Dec 22, 2010
- Penalty
- Initial $3,150 · Current $3,150
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employmnent and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to the hazard of dust explosions during coal handling and processing: a)Employees remain in an area subject to coal dust dispersion under pressure during pulverizer startup. b)Pulverizers and the associated duct work are not adequately designed and constructed to contain explosion pressures, and the system is not effectively inerted to prevent an internal explosion. c)Pulverizer start up procedures after an unplanned shutdown did not include means and methods to assure removal of all fuel sources, e.g., washing out fuel residue. Feasible means of abatement include but are not limited to: *Design, construct, operate and maintain the coal fuel system and facility according to the current best practices by established safety, health and construction standards including the most recent version of: *NFPA 68, Venting of Deflagrations *NFPA 69, Explosion Prevention Systems *NFPA 85, Boiler and Combustion Systems Hazards Code *NFPA 850, Recommended Practice for Fire Protection for Electric Generating Plants and High Voltage Direct Current Converter Stations *International Mechanical Code, Section 511, Dust Conveying Systems, as mandated by Wisconsin of Commerce, Chapter Comm 14. *Assure appropriate installation and continued maintenance of installed systems by company personnel or contractors, including comprehensive training in the requirements of the referenced standards. Abatement Certification and Abatement Documentation required.
Recent events (2)
- — F (S) $3150.00
- — Z (S) $3150.00
More inspections at Weston Power Plant
View Weston Power Plant's full OSHA safety record →
More inspections in this industry (NAICS 221122)
More inspections in WI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 309841799.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.