Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: BELL ELECTRICAL CONTRACTORS INC .

Referral inspection · Health discipline

On , OSHA opened a referral health inspection of BELL ELECTRICAL CONTRACTORS INC . in 7907 HWY N, DARDENNE PRAIRIE, MO 63368 (NAICS 238210). OSHA activity number 309917524.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Bell Electrical Contractors INC . — free Get an email when a new federal OSHA severe-injury report for Bell Electrical Contractors INC . is published. One employer, no account, unsubscribe in one click.
Site address
7907 HWY N
City
DARDENNE PRAIRIE
State
MO
ZIP
63368
Mailing
128 MILLWELL DRIVE, MARYLAND HEIGHTS, MO 63043
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
Y
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
SIC code (legacy)
1731
Employees
6
Ownership type
A

2 citations on file for this inspection.

5(a)(1)

Deleted Serious Gravity 03 1 instance 2 exposed
Issued
Oct 2, 2006
Abate by
Oct 6, 2006
Penalty
Initial $2,250 · Current $2,250
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm to
employees in that employees
were exposed to:
a/ Employees constructing a leg of a new 480 volt electrical service did
not use personal
protective clothing and equipment meeting the guidelines of NFPA 70E as
they reconnected
(reenergized) the service exposing one employee to an electrical arc blast.
While ultimate responsibility for correcting the hazards rests with the
employer, given his/her
superior knowledge of the work place, feasible and acceptable methods of
abatement to correct
this hazard, among others are:
1.  To follow the requirements of NFPA 70E Standard for Electrical Safety
in the
Workplace, latest edition (2004).  Utilize the protective clothing and
personal protective
equipment for conducting work within the flash protection boundary or
restricted
approach boundary.  Complete a flash hazard analysis, per 110.8(B)(1) of
NFPA 70E,
for the work that is to be performed, calculate the anticipated incident
energy exposure
of the worker (in calories per square centimeter) for voltages above 600
volts or use a
flash protection boundary of 4.0 feet for 600 volts and below. The
employer shall base
the energy exposure level on the working distance of the employee's face
and chest areas
from the prospective arc source for the specific task to be performed.
Flame Resistant
(FR) Clothing a nd Personal Protective Equipment shall then be selected
and used based
upon the incident energy exposure associated for the specific task, or as
an alternative,
the PPE requirements shall be designed in accordance with Annex C & D of
NFPA
70E's permitted uses in lieu of the detailed flash hazard analysis.
2.  To follow the requirements of 29 CFR 1910.335(a)(1) and use
appropriate face, hand,
arm and body protection against the effects of an electrical arc blast
during disconnect
and reconnect of an electrical circuit.
ABATEMENT CERTIFICATION AND ABATEMENT DOCUMENTATION IS REQUIRED
FOR THIS VIOLATION.  The documentation should include written verification
of abatement,
applicable measurements or monitoring results, and photographs or videos
which you believe
will be helpful.  The abatement certification sheet is enclosed with the
citation(s).
AND OR IN THE ALTERNATIVE
Recent events (2)
  • — I (S) $2250.00
  • — Z (S) $2250.00

1910.335 A01 I

Deleted Serious Gravity 03 1 instance 2 exposed
Issued
Oct 2, 2006
Abate by
Oct 6, 2006
Recent events (2)
  • — I (S)
  • — Z (S)

View Bell Electrical Contractors INC .'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 309917524.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.