LYONS, IL ·
OSHA Inspection: UNITED STATES COLD STORAGE, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of UNITED STATES COLD STORAGE, INC. in 8424 47TH STREET, LYONS, IL 60634 (NAICS 493120). OSHA activity number 310176193.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- UNITED STATES COLD STORAGE, INC.
- Site address
- 8424 47TH STREET
- City
- LYONS
- State
- IL
- ZIP
- 60634
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (Y)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493120
- SIC code (legacy)
- 4222
- Employees
- 75
- Ownership type
- Private (A)
- Industry flags
- Manufacturing safety.
Citations
1 citation on file for this inspection.
5(a)(1)
- Issued
- Jul 20, 2007
- Abate by
- Apr 14, 2008
- Penalty
- Initial $2,125 · Current $2,125
General-duty citation text
Section 5(a)(1) of the Occupational safety and Health Act of 1970: the employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to inhalation hazards associated with anhydrous ammonia. Engine Room - On or about April 27, 2007, employee(s) were not adequately protected against the potential release of anhydrous ammonia in that: a. Two of the machinery room doors opened inwards instead of outwards which could impede an evacuation of the room. b. Visual and audible alarms were not located on the outside of each entrance so that employees are fully aware of the conditions inside the room prior to entry. c. Pipes piercing the interior walls were not tightly sealed such that any release of anhydrous ammonia could potentially migrate to other areas of the workplace where employees are present. d. Not all controls and piping in anhydrous ammonia service were identified or labeled, to prevent employees from using the wrong control. e. Each entrance to a refrigerating machinery room was not appropriately marked to prevent unauthorized employees from entering the room. Among other methods, feasible and acceptable methods to control this hazard are: Adherence to the safe design, installation and operation of anhydrous ammonia refrigeration systems as prescribedd by ANSI/ASHRAE 15-2004, "Safety Standard for Refrigeration Systems", specifically: a. Provide refrigerating machinery room doors that open outward. (Section 8.11.2) b. Provide visible and audible alarms outside each entrance to the refrigerating machinery room. (Section 8.11.2.1) c. Tightly seal all wall penetrations from the refrigerating machinery room. (Section 8.12) d. Identify all controls and piping in anhydrous ammonia service. (Section 11.2.2) e. Provide each entrance to the refrigerating machinery room with signs to read "Machinery Room-Authorized Personnel Only." (Section 11.2.4)
Recent events (2)
- · D (S) $2125.00
- · Z (S) $2125.00
More inspections at United States Cold Storage, INC.
View United States Cold Storage, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 493120)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 310176193.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.