NASHVILLE, TN —
OSHA Inspection: NASHVILLE ELECTRIC-JOB SITE
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of NASHVILLE ELECTRIC-JOB SITE in JAMES ROBERTSON PARKWAY, NASHVILLE, TN 37201 (NAICS 221122). OSHA activity number 310703962.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NASHVILLE ELECTRIC-JOB SITE
- Site address
- JAMES ROBERTSON PARKWAY
- City
- NASHVILLE
- State
- TN
- ZIP
- 37201
- Mailing
- 1214 CHURCH STREET, NASHVILLE, TN 37246
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221122
- SIC code (legacy)
- 4911
- Employees
- 984
- Ownership type
- B
Citations
5 citations on file for this inspection.
1910.269 A02
- Issued
- Feb 21, 2007
- Abate by
- Mar 11, 2007
1910.269 C
- Issued
- Feb 21, 2007
- Abate by
- Mar 11, 2007
1910.269 L01
- Issued
- Feb 21, 2007
- Abate by
- Mar 11, 2007
1910.269 L02
- Issued
- Feb 21, 2007
- Abate by
- Mar 11, 2007
503010501
- Issued
- Feb 21, 2007
- Abate by
- Mar 26, 2007
General-duty citation text
T.C.A. 50-3-105(1): The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to: On 12-20-06, the employer had not developed or implemented safe working procedures or policies in the specific safe work practices for those employees working on the Richards Manufacturing Model 313NP 1875 amp Network Protector that was located in a vault at the Metro Courthouse. Employees were making an adjustment to the shunt trip screw inside the inner door. The employees had removed the door in order to make the adjustment. As they were putting the door back on, the inner door hinge contacted the energized right side 480 volt outer crossbar clamp and caused an arc blast. The distance from the top hinge of the inner door to the energized 480 volt outer crossbar clamp is approximately 3/4 of an inch. The hinge pin of the inner door assembly is approximately 11/16 of an inch. This only allowed for 1/16 of an inch clearance from the live 480 volt when putting the door back on. Safety Information and Procedures in the instruction manual state that the protector has to be deenergized and racked out before any maintenance procedure is performed. The manufacturer's safety instructions and procedures were not followed by the employer. Safety Information and Procedures in the instruction manual state that the protector has to be deenergized and racked out before any maintenance procedure is performed. In order to deenergize the protector, the fuses and links must be removed. After these are removed, the protector has to be unracked to completely deenergize the protector. Among other methods, one feasible and acceptable abatement method to correct this hazard is, the establishment and implementation of EFFECTIVE Safety Procedures for working on the network protectors that includes the following: 1.Conduct a job hazard analysis to determine the potential electrical hazards associated with the protector. 2.Develop and implement written safe working procedures according to the manufacturer's instruction manual. 3.Effectively train managers, supervisors and employees to recognize electrical hazards or risks associated with the network protector and how to minimize or eliminate them, and how to manage the procedures and policies developed for working on the network protectors. 4.Develop effective safe work practice controls according to the manufacturer's instructions to minimize the potential for electrical incidents when working on the network protectors.
More inspections at Nashville Electric-Job Site
View Nashville Electric-Job Site's full OSHA safety record →
More inspections in this industry (NAICS 221122)
More inspections in TN
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 310703962.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.