GAINESVILLE, GA —
OSHA Inspection: INDUSTRIAL BOILER & MECHANICAL CO., INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of INDUSTRIAL BOILER & MECHANICAL CO., INC. in 949 INDUSTRIAL BLVD, GAINESVILLE, GA 30501 (NAICS 811310). OSHA activity number 311037311.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- INDUSTRIAL BOILER & MECHANICAL CO., INC.
- Site address
- 949 INDUSTRIAL BLVD
- City
- GAINESVILLE
- State
- GA
- ZIP
- 30501
- Mailing
- 3325 N. HAWTHORNE ST/PO BOX 5100, CHATTANOOGA, TN 37406
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- Yes
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 811310
- SIC code (legacy)
- 7699
- Employees
- 1
- Ownership type
- A
Citations
3 citations on file for this inspection.
5(a)(1)
- Issued
- Jun 30, 2008
- Abate by
- Jul 25, 2008
- Penalty
- Initial $3,000
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to struck by hazards as the boiler exploded due to piping that was installed backward during initial installation. The employer did not assure all components of the boiler were installed correctly. Testing identified the #2 fuel oil burner input and return piping was reversed during original installation and nozzle screens were partially clogged. "Among other methods, feasible and acceptable abatement methods to correct this hazard is to:" 1. Test boiler equipment upon initial installation to assure correct installation of the boiler and all associated equipment. (Reference NFPA 85 Boiler and Combustion Systems Hazards Code, 2001 Edition, section 1.5 Installation). 2. Follow manufacturer recommendation on application. In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification. This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence of abatement, or other written records.
Recent events (2)
- — I (S)
- — Z (S) $3000.00
5(a)(1)
- Issued
- Jun 30, 2008
- Abate by
- Aug 15, 2008
- Penalty
- Initial $3,000
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to the hazard of being struck boiler parts. The employer did not produce a Maintenance program that addresses tasks employees performed including written comprehensive maintenance procedures incorporating the manufacturer's instructions to define the tasks and skills required. "Among other methods, feasible and acceptable abatement methods to correct this hazard is to:" 1. Create a Maintenance Program that includes well defined planning for making repairs or modifications using qualified personnel, tools and instruments designed for the work and written comprehensive maintenance procedures incorporating the manufacturer's instruction to define the tasks and skills required. (Reference NFPA 85 Boiler and Combustion Systems Hazard Code, 2001 Edition; section 1.7 Maintenance, Inspection, Training and Safety). 2. Follow manufacturer recommendation on application. In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification. This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence of abatement, or other written records.
Recent events (2)
- — I (S)
- — Z (S) $3000.00
5(a)(1)
- Issued
- Jun 30, 2008
- Abate by
- Aug 15, 2008
- Penalty
- Initial $3,000
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to struck by hazards as they were not provided training for switching the dual fuel 2005 Hurst boiler from natural gas to #2 Diesel fuel. While attempting to switch the boiler from natural gas to diesel the technician did not recognize piping on the boiler had been installed backward causing an overload of diesel fuel into the boiler resulting in the boiler exploding and boiler parts striking the employee. "Among other methods, feasible and acceptable abatement methods to correct this hazard is to:" 1. Create a training schedule for employees in a Maintenance Program that includes well defined planning for switching dual fuel boilers from natural gas to #2 diesel including recognition of part installation and/or equipment failure. (Reference NFPA 85 Boiler and Combustion Systems Hazards Code, 2001 Edition; section 1.7 Maintenance, Inspection Training and Safety, 1.7.2 Maintenance Training). 2. Follow manufacturer recommendation on application. In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification. This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence of abatement, or other written records.