WALDO, AR —
OSHA Inspection: DELTIC TIMBER CORPORATION
Accident-driven inspection · Safety discipline
At a glance
On , OSHA opened an accident-driven safety inspection of DELTIC TIMBER CORPORATION in 1720 HIGHWAY 82 WEST, WALDO, AR 71770 (NAICS 321912). OSHA activity number 311127906.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- DELTIC TIMBER CORPORATION
- Site address
- 1720 HIGHWAY 82 WEST
- City
- WALDO
- State
- AR
- ZIP
- 71770
What kind of inspection was it?
- Inspection type
- Accident-driven (A)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 321912
- SIC code (legacy)
- 2421
- Employees
- 175
- Ownership type
- A
Citations
5 citations on file for this inspection.
5(a)(1)
- Issued
- Jan 18, 2008
- Abate by
- Feb 7, 2008
- Penalty
- Initial $4,500 · Current $4,500
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to fire and deflagration hazards: On or about August 9, 2007 employees were exposed to fire and deflagration hazards in and around the planer room enclosure where the planer room enclosure was not built in accordance to NFPA 664, Section 6.4.2.1 to prevent or relieve deflagration pressures from propagating into adjacent interior spaces. Among other methods, the following are feasible and acceptable methods to abate or minimize the hazards: Install pressure-relief vents in the exterior walls of the planer room enclosure constructed to prevent breach and propagation of a dust explosion into adjacent areas occupied by employees.
Recent events (2)
- — F (S) $4500.00
- — Z (S) $4500.00
5(a)(1)
- Issued
- Jan 18, 2008
- Abate by
- Feb 7, 2008
- Penalty
- Initial $4,500 · Current $4,500
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to fire and deflagration hazards: On or about August 9, 2007 employees working in the planer mill were exposed to fire and deflagration hazards in the following instances: a) the dust collection system ducts conveying wood material from the planer was not equipped with spark detection, extinguishing system, and abort gates in accordance with NFPA 664, Section 8.2.2.2.2. b) the cyclone separator use for dust collection possessed a deflagration/explosion hazard and was not constructed to withstand the maximum deflagration pressure of the material collected, was not equipped with deflagration relief vents, or a deflagration suppression system in accordance with NFPA 664, Section 8.2.2.5.3. c) the dust collection system was not designed with hoods having a rate of airflow capable of capturing the wood dust and particles to minimize fugitive dust emissions in accordance with NFPA 664, Section 8.2.2.3.1 and 8.2.2.3.3. d) the dust collection system equipped with floor sweeps inlets was not designed to prevent metal and foreign material from entering the wood and dust process equipment in accordance with NFPA 664, Section 7.12.2. Among other methods, the following are feasible and acceptable methods to abate or minimize the hazards: Design and construct the dust collection system and all process equipment in accordance with NFPA 664 Standard for the Prevention of Fires and Explosions in Wood Processing and Woodworking Facilities.
Recent events (2)
- — F (S) $4500.00
- — Z (S) $4500.00
1910.22 A01
- Issued
- Jan 18, 2008
- Abate by
- Jan 31, 2008
- Penalty
- Initial $4,500 · Current $4,500
Recent events (2)
- — F (S) $4500.00
- — Z (S) $4500.00
5(a)(1)
- Issued
- Jan 18, 2008
- Abate by
- Feb 7, 2008
- Penalty
- Initial $4,500 · Current $7,000
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to fire and deflagration hazards: On or about August 9, 2007 employees were exposed to fire and deflagration hazards in and around the planer room enclosure where the planer room enclosure was not built in accordance to NFPA 664, Section 6.4.2.1 to prevent or relieve deflagration pressures from propagating into adjacent interior spaces. Among other methods, the following are feasible and acceptable methods to abate or minimize the hazards: Install pressure-relief vents in the exterior walls of the planer room enclosure constructed to prevent breach and propagation of a dust explosion into adjacent areas occupied by employees.
Recent events (2)
- — F (S) $7000.00
- — Z (S) $4500.00
5(a)(1)
- Issued
- Jan 18, 2008
- Abate by
- Feb 7, 2008
- Penalty
- Initial $4,500
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to fire and deflagration hazards: On or about August 9, 2007 employees working in the planer mill were exposed to fire and deflagration hazards in the following instances: a) the planer room enclosure was not built to prevent or relieve deflagration pressures from propagating into adjacent interior spaces. b) the dust collection system ducts conveying wood material from the planer was not equipped with spark detection, extinguishing system, and abort gates; c) the cyclone separator use for dust collection possessed a deflagration/explosion hazard and was not constructed to withstand the maximum deflagration pressure of the material collected, was not equipped with deflagration relief vents, or a deflagration suppression system. d) the dust collection system was not designed with hoods having a rate of airflow capable of capturing the wood dust and particles to minimize fugitive dust emissions in accordance. e) the dust collection system equipped with floor sweeps inlets was not designed to prevent metal and foreign material from entering the wood and dust process equipment. Among other methods, the following are feasible and acceptable methods to abate or minimize the hazards: Design and construct the dust collection system and all process equipment in accordance with NFPA 664 Standard for the Prevention of Fires and Explosions in Wood Processing and Woodworking Facilities.
Recent events (2)
- — F (S)
- — Z (S) $4500.00
More inspections at Deltic Timber Corporation
View Deltic Timber Corporation's full OSHA safety record →
More inspections in this industry (NAICS 321912)
More inspections in AR
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 311127906.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.