BILLINGS, MT ·
OSHA Inspection: ASI PIPING, INC.
Programmed Related inspection · Safety discipline
At a glance
On , OSHA opened a programmed Related safety inspection of ASI PIPING, INC. in 401 SOUTH 23RD STREET, BILLINGS, MT 59101 (NAICS 237120). OSHA activity number 311217921.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ASI PIPING, INC.
- Site address
- 401 SOUTH 23RD STREET
- City
- BILLINGS
- State
- MT
- ZIP
- 59101
- Mailing
- B530 LAKEVIEW CUTOFF RD, VIDOR, TX 89101
What kind of inspection was it?
- Inspection type
- Programmed Related (I)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (N)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 237120
- SIC code (legacy)
- 1623
- Employees
- 18
- Ownership type
- Private (A)
Citations
7 citations on file for this inspection.
1910.119 H03 II
- Issued
- Jun 24, 2009
- Abate by
- Jul 2, 2009
- Penalty
- Initial $1,375 · Current $1,375
General-duty citation text
29 CFR 1910.119(h)(3)(ii): The contract employer did not assure that each employee was instructed in the applicable provisions of the emergency action plan: a. On or about March 18, 2009 and at times prior ASI Piping did not ensure that employees were protected from explosion/fire/chemical exposure hazards. The employees were not properly instructed concerning provisions of CFR 1910.38 Emergency Action Plans. 1. CFR 1910.38(c)(2): Calls for types of evacuations and exit route assignments. The employees were not given clear instructions on types of evacuations and specific techniques (wind direction and strength) to be used in making a safe escape. They were also not given a clear exit route when moved around the plant 2. CFR 1910.38(d): Calls for a distinctive signal for each purpose. The employees did not know how many signals or what each distinctive alarm meant.
Recent events (2)
- · I (S) $1375.00
- · Z (S) $1375.00
1926.56 A
- Issued
- Jun 24, 2009
- Abate by
- Jun 29, 2009
- Penalty
- Initial $3,500 · Current $3,500
General-duty citation text
29 CFR 1926.56(a): While work was in progress, construction areas, ramps, runways, corridors, offices, shops or storage areas were not lighted to the minimum illumination intensities listed in table D3 of subpart D of 29 CFR part 1926: a) On or about March 18, 2009 and at times prior ASI Piping Inc. did not ensure that employees were protected from lack of lighting hazards. Employees, doing demolition work with cut off tools, were not provided lighting behind the fire blankets used to contain sparks.
Recent events (2)
- · I (S) $3500.00
- · Z (S) $3500.00
1926.403 B01
- Issued
- Jun 24, 2009
- Abate by
- Jun 29, 2009
- Penalty
- Initial $3,500 · Current $3,500
General-duty citation text
29 CFR 1926.403(b)(1): Examinations of electrical equipment were not done to ensure the systems to be free from recognized hazards that were likely to cause death or serious physical harm to employees: a) On or about March 18, 2009 and at times prior ASI Piping Inc did not ensure that employees were protected from electrical hazards. The electrical system used for the turnaround demolition work was not inspected to assure the system to be free from recognizable hazards.
Recent events (2)
- · I (S) $3500.00
- · Z (S) $3500.00
1926.407 B
- Issued
- Jun 24, 2009
- Abate by
- Jun 29, 2009
General-duty citation text
29 CFR 1926.407(b): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not approved as intrinsically safe or approved for the hazardous (classified) location or safe for the hazardous (classified) location: a) On or about March 18, 2009 and at times prior ASI Piping did not ensure that employees were protected from electrical hazards. The crew doing demolition work on the Coker de-heading deck did use electrical equipment which was not approved for the electrical classification of this area. This included the tools, cords, and supply pendant used for the demolition crew.
Recent events (2)
- · I (S)
- · Z (S)
1926.416 A01
- Issued
- Jun 24, 2009
- Abate by
- Jun 29, 2009
- Penalty
- Current $3,500
General-duty citation text
29 CFR 1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by deenergizing and grounding the circuits or effectively guarding the circuits by insulation or other means: a) On or about march 18, 2009 and at times prior ASI Piping Inc. did not ensure that employees were protected from electrical hazards. The crew doing demolition work on the Coker de-heading floor did cutting work near live electrical circuitry. This resulted in damage to the electrical circuit. The electrical circuit was not protected from the demolition work.
Recent events (2)
- · I (S) $3500.00
- · Z (S)
1926.850 A
- Issued
- Jun 24, 2009
- Abate by
- Jun 29, 2009
- Penalty
- Initial $3,500 · Current $3,500
General-duty citation text
29 CFR 1926.850(a): Evidence in writing was not available that an engineering survey performed by a competent person had been performed prior to permitting employee(s) to start demolition operations: a) On or about March 18, 2009 and at times prior ASI Piping Inc. did not ensure that employees were protected from demolition hazards. No engineering survey was done to determine the stability of the walls being partially demolitioned.
Recent events (2)
- · I (S) $3500.00
- · Z (S) $3500.00
1926.850 D
- Issued
- Jun 24, 2009
- Abate by
- Jun 29, 2009
General-duty citation text
29 CFR 1926.850(d): Power, water, and utility services necessary to be maintained during demolition were not temporarily relocated or protected: a) On or about March 18, 2009 and at times prior ASI Piping Inc. did not ensure that employees were protected from demolition hazards. The electrical power lines positioned beside structural members to be removed were not relocated or protected in some other manner
Recent events (2)
- · I (S)
- · Z (S)
More inspections in this industry (NAICS 237120)
More inspections in MT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 311217921.