BILLINGS, MT —
OSHA Inspection: COLSTRIP ELECTRIC, INC.
Unprogrammed Other inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Other safety inspection of COLSTRIP ELECTRIC, INC. in 401 SOUTH 23RD STREET, BILLINGS, MT 59101 (NAICS 238210). OSHA activity number 311217939.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- COLSTRIP ELECTRIC, INC.
- Site address
- 401 SOUTH 23RD STREET
- City
- BILLINGS
- State
- MT
- ZIP
- 59101
- Mailing
- P O BOX 1934, COLSTRIP, MT 59323
What kind of inspection was it?
- Inspection type
- Unprogrammed Other (I)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- SIC code (legacy)
- 1731
- Employees
- 35
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.119 H03 II
- Issued
- Jun 25, 2009
- Abate by
- Jul 3, 2009
- Penalty
- Initial $875 · Current $875
General-duty citation text
29 CFR 1910.119(h)(3)(ii): The contract employer did not assure that each employee was instructed in the applicable provisions of the emergency action plan: a. On or about February 23, 2009 and at times prior Colstrip Electric Inc did not ensure that employees were protected from explosion/fire/chemical exposure hazards. The employees were not properly instructed concerning provisions of CFR 1910.38 Emergency Action Plans. 1. CFR 1910.38(c)(2): Calls for types of evacuations and exit route assignments. The employees were not given clear instructions on types of evacuations and specific techniques (wind direction and strength) to be used in making a safe escape. They were also not given a clear exit route when moved around the plant 2. CFR 1910.38(d): Calls for a distinctive signal for each purpose. The employees did not know how many signals or what each distinctive alarm meant.
Recent events (2)
- — I (S) $875.00
- — Z (S) $875.00
1926.407 B
- Issued
- Jun 25, 2009
- Abate by
- Jun 30, 2009
- Penalty
- Initial $875 · Current $875
General-duty citation text
29 CFR 1926.407(b): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not approved as intrinsically safe or approved for the hazardous (classified) location or safe for the hazardous (classified) location: a) On or about March 17, 2009 and at times prior Colstrip Electric Inc. as the exposing/creating contractor, did not ensure that employees/workers were protected from electrical hazards. The crew doing demolition work on the Coker de-heading deck did use electrical equipment which was not approved for the electrical classification of this area. This included the conduit bender, cords, and supply pendant used by the demolition crews. The pendant was installed in the classified area by Colstrip Electric Inc. electricians.
Recent events (2)
- — I (S) $875.00
- — Z (S) $875.00
More inspections at Colstrip Electric, INC.
View Colstrip Electric, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in MT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 311217939.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.