OSHA Inspection: MOTIVA ENTERPRISES LLC

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of MOTIVA ENTERPRISES LLC in LA HWY 70 & LA HWY 44, CONVENT, LA 70723 (NAICS 324110). OSHA activity number 311525349.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Motiva Enterprises LLC — free Get an email when a new federal OSHA severe-injury report for Motiva Enterprises LLC is published. One employer, no account, unsubscribe in one click.
Site address
LA HWY 70 & LA HWY 44
City
CONVENT
State
LA
ZIP
70723
Mailing
PO BOX 37, CONVENT, LA 70723
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Y
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
324110
SIC code (legacy)
2911
Employees
250
Ownership type
A

2 citations on file for this inspection.

1910.147 D03

Serious Gravity 03 1 instance 5 exposed
Issued
Dec 4, 2008
Abate by
Dec 16, 2008
Penalty
Initial $1,875 · Current $1,875
29 CFR 1910.147(d)(3): All energy isolating devices that were needed to
control the energy to
the machine or equipment were not physically located and operated in such
a manner as to
isolate the machine or equipment from the energy source(s):
Vacuum Pipe Still 2 (VPS-2). The employer did not ensure that the energy
isolation device
(TV139 with associated valves & piping) in the High Pressure Boiler Feed
Water Line was
closed to prevent backflow/leakage of high pressure water into the 600 psi
steam line between
83H101 (Charge Tower) and the  83D101 (Steam Desuperheater). This exposed
employees to
the sudden and un-expected release of steam and/or hot water at approx 240
deg F.
Recent events (2)
  • — J (S) $1875.00
  • — Z (S) $1875.00

1910.147 D05 II

Deleted Serious Gravity 03 1 instance 5 exposed
Issued
Dec 4, 2008
Abate by
Dec 16, 2008
29 CFR 1910.147(d)(5)(ii): Where there was a possibility of
re-accumulation of stored energy
to a hazardous level, verification of isolation was not continued until
the servicing or
maintenance was completed, or until the possibility of such accumulation
no longer existed:
Vacuum Pipe Still (VPS-2). The employer did not continually verify that
the 600 psi
steam line between 83H101 (Atmos. Tower Charge Heater) and 83D103
(Desuperheater)
remained isolated and the re-accumulation of steam and/or hot water was
not occuring
between the time that the unit was shut down and the blinding of the steam
lines was
accomplished. This exposed employees to the sudden and un-expected release
of steam
and/or hot water at approx 240 deg F.g