OSHA Inspection: CALCASIEU REFINING CO.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of CALCASIEU REFINING CO. in 4359 W TANK FARM ROAD, LAKE CHARLES, LA 70605 (NAICS 324110). OSHA activity number 311529283.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CALCASIEU REFINING CO.
- Site address
- 4359 W TANK FARM ROAD
- City
- LAKE CHARLES
- State
- LA
- ZIP
- 70605
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (N)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 324110
- SIC code (legacy)
- 2911
- Employees
- 103
- Ownership type
- Private (A)
- Industry flags
- Manufacturing safety.
Citations
36 citations on file for this inspection.
1910.119 D02 ID
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $3,500 · Current $3,500
General-duty citation text
29 CFR 1910.119(d)(2)(i)(D): Process safety information pertaining to the technology of the process does not always include the safe upper and lower limits for such items as temperatures, pressures, flows or compositions: (a) This violation occurred on or about January 27, 2009, and times prior thereto, where the employer had not updated and documented, as part of the process safety information, the operating limits of the equipment for the #2 Crude Unit. Operators reviewing this information could not utilize the information to accurately meet process, safe upper and lower limits. These operating limits include safe upper and lower temperatures and flow rates such as; (1) The overhead #2 unit naphtha & exchangers E-215 and E-1N1-These were not listed in the process safety information provided. This section had been left blank. (2) The #2 Unit Kerosene Exit & Tray - The upper and lower operating temperature limits had been left blank in the process safety information provided. (3) The #2 Crude Unit Diesel Exit of the Tower - The values of lower and upper operating temperature had changed. The process safety information provided have listed 500 F and it is presently established at 520 F. The upper limit was labeled as 530 F and it is presently established at 560 F. (4) The #2 Unit Unstabilized Naphtha Draw to Treating (flow in BPD) - The process safety information provided shows the upper limit was depicted as 3,500 BPD and it is presently 5,500 BPD. (5) The #2 Unit Kerosene Pumparound (flow in BPD) - The lower limit was depicted in the process safety information as 5,000 BPD. It is presently 2,500 BPD. The upper limit was depicted in the process safety information as 17,000 BPD and it is presently established as 6,000 BPD. (6) The #2 Unit Diesel Pumparound (flow in BPD) - The lower limit was depicted in the process safety information as 10,000 BPD. It is presently established at 7,500 BPD. The upper limit was depicted on the process safety information as 18,000 BPD while it is presently at 12,000 BPD. (7) The #2 Unit Diesel Draw to Treating (flow in BPD) - The upper limit is presently at 5,000 BPD and the process safety information established it as 9,000 BPD. This exposed the employees to the hazards of fire and explosion. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that the operational limits are updated and documented as part of the process safety information.
1910.119 D03 IC
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $3,500 · Current $3,500
General-duty citation text
29 CFR 1910.119(d)(3)(i)(C): Process safety information pertaining to the equipment in the process did not include the electrical classification: This violation occurred on or about January 27, 2009, and times prior thereto, where the employer did not have electrical classification drawings for the area surrounding the F- 400 flare and knock out pot. The employer exposed employees to a fire and explosion hazard. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that drawings that detail all locations designated as hazardous (classified) are developed. These electrical classifications, the classified locations and classified areas surrounding the classified location need to be documented. This documentation shall be made available to those authorized to design, install, inspect, maintain, or operate electric equipment at the location.
1910.119 D03 ID
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $4,900 · Current $4,900
General-duty citation text
29 CFR 1910.119(d)(3)(i)(D): Process safety information pertaining to the equipment in the process does not include the relief system design and design basis: (a) This violation occurred on or about January 27, 2009, and times prior thereto, where the employer had no documentation on the relief system design and calculations based on a worst case scenario. The company falls under the PSM standard as it is a crude oil refining process that contains over 10,000 pounds of naphtha and over 10,000 pounds of liquefied natural gas (LPG) which are classified as flammable liquids and gases. A release of these materials from the process vessels could cause a catastrophic event where employees would suffer burns and/or death. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps that it is taking to ensure that the process safety information is collected for each pressure relief valve and utilized in the process hazard analysis and mechanical integrity program. (b) This violation occurred on or about January 27, 2009, and times prior thereto, where the employer failed to have the information for the materials of construction for PSV-255 included in their process safety information. This condition exposed employees to fire and explosion hazards. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with this standard including describing the action it is taking to ensure that the materials of construction are collected for each pressure relief valve and utilized in the process hazard analysis and mechanical integrity program.y
1910.119 D03 IF
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $3,500 · Current $3,500
General-duty citation text
29 CFR 1910.119(d)(3)(i)(F): Process safety information pertaining to the equipment does not include the design codes and standards employed: (a) This violation occurred on or about January 27, 2009, and times prior thereto, where the process safety information did not include the design of the pressure relieving system for the #2 Crude Unit and the entire facility. This would include the relief valves, the header system, the knock out pot and the flare. This condition exposed employees to fire and explosion hazards. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that process safety information is collected for each pressure relief valve, header system, knock out pot, and flare and is utilized in the process hazard analysis and mechanical integrity program. (b) This violation occurred on or about January 27, 2009, and times prior thereto, where the process safety information did not include the design codes for the following pressure vessels; 1)V-202 Crude Reflux Accumulator - The employer could not provide: Rerating Calculations (Code ASME) Heat Treatment Results (Code ASME) Post Weld Heat Treatment Results (Code API 510) Welding Performance Qualifications (PQR) (Code ASME) Welding Procedure Specification (WPS) (Code ASME) Repair & Alteration Reports (R-1) (Code API 510) 2)V-201 #2 Crude Unit Main Frac Tower - The employer could not provide: Manufacturers Data Report (U-1, U-2 Reports) (Code ASME) Heat Treatment Results (Code ASME) Post Weld Heat Treatment Results (Code API 510) Welding Performance Qualifications (PQR) (Code ASME) Welding Procedure Specification (WPS) (Code ASME) Thickness Measurement Locations (TML) (Code API 572) 3)E-211B Diesel Product Desalted Crude Heat Exchanger - The employer could not provide: Welding Performance Qualifications (PQR) (Code ASME) Repair & Alteration Reports (R-1) (Code ASME) 4)V-204 Diesel Stripper - The employer could not provide: Manufacturers Data Report (U-1, U-2 Reports)(Code ASME) Code Calculations (Code API) Rerating Calculations (Code ASME) Heat Treatment Results for vessel (Code API 510) MI/NDE Test Results (MT, UT, RT, etc) for vessel Post Weld Heat Treatment Results (Code API 510) TML Historical Readings (Code API 510) Welding Performance Qualifications (PQR) (Code ASME) Welding Procedure Specification (WPS) (Code ASME) Repair & Alteration Reports (R-1) (Code API 510) Failure to maintain the process safety information of the #2 Crude Unit pressure vessels could result in risk of exposure to fire and explosion to employees. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that an up-to-date evaluation is being conducted and that the process safety information is updated.
1910.119 D03 II
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $3,500 · Current $3,500
General-duty citation text
29 CFR 1910.119(d)(3)(ii): The employer does not document that the equipment in the process complied with recognized and generally accepted good engineering practices: (a) This violation occurred on or about January 27, 2009, and times prior thereto,where the employer did not comply with RAGAGEP (i.e. API 521 Sec. 4.3, 4.4, 4.5) when it failed to evaluate (e.g., calculations and/or plume dispersion model modeling) whether releases from relief system equipment discharged to safe locations. The worst case flammable vapor cloud scenario was not evaluated to determine if the pressure relief valve on the LPG Storage Tank 201 vented to a safe location. The LPG Tank has a maximum capacity of 72,700 gallons (water capacity) with a pressure relief valve located on the top of the pressure vessel. A parking area, abandoned administrative building, operator's break room, and operator's control room are within 236 feet of the LPG storage tank. This condition exposed employees to a fire and explosion hazard. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that LPG Tank 201 vents to a safe location. (b) This violation occurred on or about January 27, 2009, and times prior thereto, where the employer located its steam discharge for the pressure relief valve of steam line E-D- 2-118 eight inches from an employee work area. The discharge point was approximately four feet above the work location and plant steam is 135 Pounds. If the pressure relief valve functioned as designed scalding steam could be released into the employees work areas. Employees could suffer burns from the discharging steam plume. This condition exposed employees to the hazard of burns from steam. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that the pressure relief valve from steam discharge line E-D-2-118 does not discharge into an employee work area.
1910.119 E01
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $3,500 · Current $3,500
General-duty citation text
29 CFR 1910.119(e)(1): The process hazard analysis is not appropriate to the complexity of the process and does not identify, evaluate, and address the control of the hazards involved in the process: (a)This violation occurred on or about January 27, 2009, and times prior thereto, where the employer's process hazard analysis's conducted in 1994,1999 and 2009 for the LPG Storage Tank 201 (installed on July 1990) did not address whether or not the pressure relief valve vented to a safe location. The employer did not conduct a plume dispersion model or calculations of the worst case flammable vapor cloud scenario to determine if the pressure relief valve on the LPG Storage Tank 201 vented to a safe location. The LPG Tank has a maximum capacity of 72,700 gallons (water capacity) with a pressure relief valve located on the top of the pressure vessel. A parking area, abandoned administrative building and operators break room is within 236 feet of the LPG storage tank. This condition exposed employees to a fire and explosion hazard. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that LPG Tank 201 vents to a safe location and how this information will be included in the PHA.
1910.119 E03 II
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $3,500 · Current $3,500
General-duty citation text
29 CFR 1910.119(e)(3)(ii): The process hazard analysis did not identify any previous incident which had a likely potential for catastrophic consequences in the workplace: This violation occurred on or about January 27, 2009, and times prior thereto, where the employer's process hazard analysis (1995, 1997, 2001 and 2006) conducted for the #2 Crude Unit did not address any previous incidents which had a likely potential for a catastrophic consequence in the workplace. This condition exposed employees to a fire and explosion hazards. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that previous incidents that could have an effect on a covered process are collected and utilized in the process hazard analysis and mechanical integrity program.
1910.119 E03 III
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $3,500 · Current $3,500
General-duty citation text
29 CFR 1910.119(e)(3)(iii): The process hazard analysis does not address the engineering and administrative controls applicable to the hazards and their interrelationship, such as, appropriate application of detection methodologies to provide early warning of releases. (a) This violation occurred on or about January 27, 2009, and times prior thereto, where the employer's process hazard analysis (1995, 1997, 2001 and 2006) conducted for the #2 Crude Unit did not address any controls and devices to provide early warning of releases. The Company has 6 LEL monitors (Sensor 1 to 6), 6 hydrogen sulfide monitors (A1-710, A1-710B, A1-712A A1-745, A1-106-N, A1-106S), 2 flare (F-400) pilot temperature transmitters ( Flare T1 and T2), 4 level transmitters ( 2 high level and 2 low level on 2 level gages (Flare Knock-out Pot D-514 and Flare Level Gage) which were not considered in the PHA's. This condition exposed employees to a fire and explosion hazards. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that the process safety information is collected for each detection device and utilized in the process hazard analysis and mechanical integrity program
1910.119 E03 V
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $3,500 · Current $3,500
General-duty citation text
29 CFR 1910.119(e)(3)(v): The process hazard analysis does not address facility siting: This violation occurred on or about January 27, 2009, and times prior thereto, where the employer failed to conduct a facility siting and risk study for the 2006 #2 Crude Unit PHA, the purpose being, to determine the destructive potential of escaping highly hazardous chemicals on employee occupied structures (i.e. vapor cloud release, vessel explosion). Failure to conduct this study could potentially expose employees to the hazards of fire and explosion. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that facility siting has adequately been addressed through a facility siting study which will be incorporated into the process hazard analysis.
1910.119 E03 VII
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $3,500 · Current $3,500
General-duty citation text
29 CFR 1910.119(e)(3)(vii) The process hazard analysis does not include a qualitative evaluation of a range of the possible safety and health effects of failure of controls on employees in the workplace: This violation occurred on or about January 27, 2009, and times prior thereto, where the employer's process hazard analysis (1995, 1997, 2001 and 2006) conducted for the #2 Crude Unit did not address a qualitative evaluation of the possible safety and health effects of failure of controls on employees in the workplace. This condition exposed employees to a fire and explosion hazard. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that control failure has adequately been addressed and will be incorporated into the process hazard analysis.
1910.119 E05
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $3,500 · Current $3,500
General-duty citation text
29 CFR 1910.119(e)(5): The employer does not establish a system to assure that the process hazard analysis team's recommendations are resolved in a timely manner and that the resolution is documented: This violation occurred on or about January 27, 2009, and times prior thereto, where the employer failed to document completion of safety and health recommendations resulting from process analyses conducted in 1995,1997, 2001 and 2006. This condition exposed employees to a fire and explosion hazard. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that all process hazard analysis's recommendations have been resolved and documented.
1910.119 E06
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $3,500 · Current $3,500
General-duty citation text
29 CFR 1910.119(e)(6): The employer does not update the PHA (update/revalidation) within five years of the initial PHA: This violation occurred on or about January 27, 2009, and times prior thereto, where the employer failed to consider in its PHA update/revaluations in 1997, 2001 and 2006 for the #2 Crude Unit, the throughput increase and any potential effects the increase might have on the adequacy of the current process, including the relief system. The #2 Crude Unit had a throughput increase from 15,000 barrels per day in 1995 to 17,000 barrels per day in 1997, from 17,000 barrels per day in 1997 to 21,000 barrels per day in 2001 and a throughput increase from 21,000 barrels per day in 2001 to 25,000 barrels per day in 2006. This condition exposed employees to a fire and explosion hazard. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that a process hazard analysis will evaluate throughput increase and relief system adequacy.
1910.119 L01
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
General-duty citation text
29 CFR 1910.119(l)(1): The employer does not establish and implement written procedures to manage changes to process chemicals, technology, equipment, and procedures; and, changes to facilities that affect a covered process: This violation occurred on or about January 27, 2009, and times prior thereto, where the employer's #2 Crude Unit had a throughput increase from 10,000 barrels per day in 1979 to 15,000 barrels per day in 1995. The # 2 Crude Unit had a throughput increase from 15,000 barrels per day in 1995 to 17,000 barrels per day in 1997. A written procedure to manage these changes was not implemented. This condition exposed employees to a fire and explosion hazard. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure a management of change procedure will be used to evaluate all throughput increase and relief system adequacy.
1910.119 F01
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $3,500 · Current $3,500
General-duty citation text
29 CFR 1910.119(f)(1): The employer does not develop and implement written operating procedures that provided clear instructions for safely conducting activities involved in each covered process consistent with the process safety information and which addressed the elements listed in 29 CFR 1910.119(f)(1)(i) through (f)(1)(iv): (a) This violation occurred on or about January 27, 2009, and times prior thereto, where the employer did not develop or implement operating procedures for the administrative control of Car Seal's installed on all relief valves within #2 Crude Unit. The company has Car Seals installed on all relief valves but does not have a regular inspection program to verify Car Seals are in place. The Car Seal program has never been monitored to assure it is effective and working as designed. This condition exposed employees to a fire and explosion hazard. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that pressure relief devices and the Car Seal Program are being operated effectively. (b)This violation occurred on or about January 27, 2009, and times prior thereto, where the employer did not develop written operating procedures in the #2 crude unit for all pressure relief valve discharge into the pressure relieving system. This condition exposed employees to a fire and explosion hazard. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that a written operating procedure is developed and implemented that details how pressure relief valve discharge, knock out pot operation and flare operations will be handled at the #2 Crude Unit.
1910.119 F01 IC
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $4,900 · Current $4,900
General-duty citation text
29 CFR 1910.119(f)(1)(i)(C): The employer's written operating procedures covering the steps for each operating phase does not address temporary operations: (a) This violation occurred on or about January 27, 2009, and times prior thereto, where the employer did not establish written operating procedures in the #2 Crude Unit for operation of the flare when the pilots have been extinguished. This condition exposed employees to a fire and explosion hazard. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that a written operating procedure is developed and implemented that details how operations will be handled when the flare pilots have been extinguished. (b) The employer violated this standard on or about January 27, 2009, and times prior thereto, where the employer did not establish written operating procedures in the #2 Crude Unit for the relighting of the flare if the pilots and flare should be extinguished. The flare is a component of the Calcasieu Refining Company's pressure relieving system. The flare has thermocouples, pilots and a manual relight system. The flare is designed to burn continuously. Operating procedures should outline the steps to take if these devices fail, and the procedure to manually re-light the flare. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that a written operating procedure is developed and implemented that details how operations will be handled if the flare should be extinguished.
1910.119 F01 IE
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
General-duty citation text
29 CFR 1910.119(f)(1)(i)(E): The employer's written operating procedures covering the steps for each operating phase does not address emergency operations: This violation occurred on or about January 27, 2009, and times prior thereto, where the employer did not establish written operating procedures in the #2 Crude Unit for knock out pot operation (D-514 Flare KO Drum) which is a component of the pressure relieving system. The knock out pot has three alarms low, high and high/high. The values assigned to these levels and the steps to take if the levels are exceeded were not detailed in the operating procedures. This condition exposed employees to a fire and explosion hazard. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that the written operating procedures for pumping out the knock out pot are developed and implemented.
1910.119 F01 II
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
General-duty citation text
29 CFR 1910.119(f)(1)(ii): The employer's written operating procedures do not provide clear instructions for safely conducting activities, consistant with the process safety information for the operating limits: (a) The employer violated this standard on or about January 27, 2009 and times prior thereto, where the employer failed to address the following operating limits of the #2 Crude Unit within the operating procedures. The employer was only able to provide one document titled; "Crude Standard Operating Limits/Consequences of Deviation" Subpoena item #57: 1) #2 Crude Tower V-201 - The upper and lower operating pressure had changed from what was indicated on the document. 2) The overhead #2 unit naphtha & exchangers E-215 and E-1N1- The operator provided the upper and lower limits. These were not listed in the document. This section had been left blank. 3) The #2 Unit Kerosene Exit & Tray - The operator filled in the blank with the updated upper and lower operating temperature limits. This information had been left blank. 4) The #2 Crude Unit Diesel Exit of the Tower - The values of lower and upper operating temperature had changed. The document listed 500 F as the lower limit and the operator provided that it was 520 F. The upper limit was labeled as 530 F and the operator provided that it was 560 F. 5) The #2 Unit Unstabilized Naphtha Draw to Treating (flow in BPD) - The document shows the upper limit was depicted as 3,500 BPD and the operator established that it was presently 5,500 BPD. 6) The #2 Unit Kerosene Pumparound (flow in BPD) - The lower limit was depicted as 5,000 BPD. The operator established it as 2,500 BPD. The upper limit was depicted as 17,000 BPD and the operator established it as 6,000 BPD. 7) The #2 Unit Diesel Pumparound (flow in BPD) - The lower limit was depicted as 10,000 BPD. The operator established that it is presently at 7,500. The upper limit was depicted as 18,000 BPD while the operator established that it is presently at 12,000 BPD. 8) The #2 Unit Diesel Draw to Treating (flow in BPD) - The upper limit is depicted at 5,000 BPD and the operator established it as presently 9,000 BPD. This condition exposed employees to a fire and explosion hazard. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that the operating procedures are beingrevised to reflect the present operating limits.ng
1910.119 F01 IV
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $4,900 · Current $4,900
General-duty citation text
29 CFR 1910.119(f)(1)(iv): The employer's written operating procedures do not address requirements for the safety systems and their functions: This violation occurred on or about January 27, 2009, and times prior thereto, where the employer failed to address the applicable safety systems (i.e. uninterruptible power supply, safety relief devices) within the operating procedures for the #2 Crude Unit. This condition exposed employees to a fire and explosion hazards. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that information pertaining to the safety systems integral in operating procedures are contained within the operating procedures.
1910.119 F03
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $4,900 · Current $4,900
General-duty citation text
29 CFR 1910.119(f)(3): The employer does not certify annually that the operating procedures are current and accurate: (a)This violation occurred on or about January 27, 2009, and times prior thereto, where the employer did not certify annually that the following operating procedures for the #2 Crude Unit were up-to-date: 1) Start-Up After Turnaround - Last reviewed: No date 2) #2 Unit Crude Tower Bottoms Transition from Circulation to Vacuum Unit Charge Feed Circuit - Last reviewed: No date, No name of certifier. 3) Transition #2 Crude Tower Bottoms from Vacuum Unit Charge To #2 Circulation Circuit - Last reviewed: No date, No name of certifier 4) #2 Crude Shutdown For Turnaround - Last reviewed: No date 5) Bypassing Crude Side of (E-207) #2 Crude Exchanger - Last reviewed: No date, No name of certifier 6) Initial Start-Up #2 Crude Unit - Last Reviewed: 1/22/07 7) Line Up Natural Gas to Fuel Gas KO Vessel (V-210) - Last Reviewed: 11/26/07 8) Emergency Shutdown Due to Loss of Steam - Last reviewed: 1/22/07 Failure to certify the operating procedures could risk employees to the hazards of fire and explosion. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that the operating procedures are annually reviewed and certified.
1910.119 F04
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $3,500 · Current $3,500
General-duty citation text
29 CFR 1910.119(f)(4): The employer did not develop and implement safe work practices for employees and contractor employees to provide for the control of hazards during operations such as lockout/tagout; confined space entry; opening process equipment or piping; and control over entrance into a facility by maintenance, contractor, laboratory, or other support personnel: This violation occurred on or about January 27, 2009, and times prior thereto, where the employer did not assure that non-intrinsically safe motorized equipment was not allowed to enter an area classified as Class 1 Division II. The company policy was that the classified area extended 20 feet from the base of the F-400 flare. Motorized vehicle tracks were noted within four feet of the F-400 flare base. This condition exposed employees to a fire and explosion hazard. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that drawings that detail all locations designated as hazardous (classified) are prepared and that electrical classifications, the classified location and classified areas surrounding the classified location are documented. The employer must also submit a plan showing that documentation shall be made available to those authorized to design, install, inspect, maintain, or operate electric equipment at the location. The employer must also develop and describe policies and procedures to prevent employees and contractors from entering classified areas with non-classified equipment.
1910.119 G01 I
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $3,500 · Current $3,500
General-duty citation text
29 CFR 1910.119(g)(1)(i): The employer does not initially train each employee, presently involved in operating a process, in an overview of the process and in the operating procedures as specified in 29 CFR 1910.119(f). (a) This violation occurred on or about January 27, 2009, and times prior thereto, where the employer did not initially train each employee presently involved in operating a process, in the operating procedures for the #2 Crude Unit pressure relief system which includes the pressure relief valves, the knockout pot and the flare. This condition exposed employees to a fire and explosion hazard. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that written operating procedures are developed and implemented that detail how pressure relief valve discharge, knock out pot operation and flare operations will be handled at the #2 Crude Unit. In addition operators of the unit must review the operating procedures, be trained on the procedures and the employer must ascertain if each employee involved in operating the process has received and understood the training.d
1910.119 J02
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $4,900 · Current $4,900
General-duty citation text
29 CFR 1910.119(j)(2): The employer does not establish and implement written procedures to maintain the on-going mechanical integrity of process equipment: (a) This violation occurred on or about January 27, 2009, and times prior thereto, where the employer failed to develop a written procedure for the inspection for corrosion under insulation for pressure vessels in Crude Unit #2. This condition exposed employees to a fire and explosion hazard. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that an inspection procedure for the determination of corrosion under insulation is developed and implemented. (b) This violation occurred on or about January 27, 2009, and times prior thereto, where the employer did not implement a Mechanical Integrity Procedure that required piping inspections to be based on a classification system that prioritizes piping inspections based on consequences of failure. Product piping circuits in Crude Unit #2 such as, but not limited to, Kerosene piping lines (3"-K-20176, 4"-K-20179, 4"-20193, and 3"-K-20201); Diesel piping lines (4"-D-20177, 3"-D-20178, 4"-D20194, 3"-D-20185, 8"-D-50360, and 8"-D-50361); Light Naphtha piping lines (6"-LN-20149, 4"-LN-20150, 3"-LN-20151, 3"-LN-20152, 3"-HN-20224 and 3"-HN-20225) were not given a consequence of failure classification (Class 1, Class 2 or Class 3) as prescribed by API 570 - Piping Inspection code to determine the extent and frequency of inspection. This condition exposed employees to a fire and explosion hazard. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that a piping inspection procedure is developed and implemented that ensures piping circuit mechanical integrity inspections include a consequence of failure classification system. (c) This violation occurred on or about January 27, 2009, and times prior thereto, where the employer did not have the complete owner's equipment manuals for pumps P202A&B-Overhead Reflux & Product Pumps, in Crude Unit #2 which provides minimum preventive maintenance requirements. This condition exposed employees to a fire and explosion hazards. (d) This violation occurred on or about January 27, 2009, and times prior thereto, where the employer did not have complete owner's equipment manuals for pumps P2HN1&P2HN2-Heavy Naphtha Pumps, Crude Unit which provides minimum preventive maintenance requirements. This condition exposed employees to a fire and explosion hazards. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that the owner's equipment manuals are being assembled in their entirety. (e) This violation occurred on or about January 27, 2009, and times prior thereto, where the employer did not outline the training and qualifications each employee would be required to have to maintain the on-going integrity of process equipment. There was no standard training program for I&E Technicians, mechanics and millwrights working in the covered process. This condition exposed employees to a fire and explosion hazard. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that the employer completely develops a written mechanical integrity program, that outlines in detail what training will be required and provided to I&E Technicians, mechanics and millwrights.
1910.119 J04 I
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $4,900 · Current $4,900
General-duty citation text
29 CFR 1910.119(j)(4)(i): Inspections and tests were not performed on process equipment to maintain its mechanical integrity: a) This violation occurred on or about January 27, 2009, and times prior thereto, where the employer failed to inspect, per the manufacturer's recommendations, P205A-Service Pre-fractionation Overhead Reflux Pump, Serial # P58514-01/02 in Crude Unit #2, mechanical seal for wear, wear rings, or worn surfaces; the impeller for cavitation damage, extreme corrosion on the casing and casing cover; seal flush piping for any foreign material or blockages. b) This violation occurred on or about January 27, 2009, and times prior thereto, where the employer did not inspect P218A-Light Naphtha Product Pump, serial #05RLCP006601001/02 in Crude Unit #2 mechanical seal for wear, wear rings for grooved or worn surfaces, the impeller for cavitation damage, extreme corrosion on the casing and casing cover, seal flush piping for any foreign material or blockages, and the driver as per the manufacturer's recommendations. This condition exposed employees to a fire and explosion hazard. Pursuant to 29 CFR 1903.19(d), within 10 days of the calendar date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that the appropriate inspection and testing is being implemented for pumps.
1910.119 J04 II
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $4,900 · Current $4,900
General-duty citation text
29 CFR 1910.119(j)(4)(ii): Inspections and testing procedures performed on process equipment to maintain its mechanical integrity, did not follow recognized and generally accepted good engineering practices: (a) This violation occurred on or about January 27, 2009, and at times prior thereto, where the employer did not inspect all piping circuits in Crude Unit #2, such as but not limited to, Kerosene piping lines (3"-K-20176, 4"-K-20179, 4"-20193, and 3"-K-20201); Diesel piping lines (4"-D-20177, 3"-D-20178, 4"-D-20194, 3"-D-20185, 8"-D-50360, and 8"-D-50361); Light Naphtha piping lines (6"-LN-20149, 4"-LN-20150, 3"-LN- 20151, 3"-LN-20152, 3"-LN-20153, and 3"-LN-20158); and Heavy Naphtha piping lines (6"-HN-20222, 6"-HN-20223; 3"-HN-20224, and 3"-HN-20225) for Corrosion-Under- Insulation (CUI) as prescribed by API 570 -Piping Inspection Code. This condition exposed employees to a fire and explosion hazard. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that all CUI inspections are being properly documented. b) This violation occurred on or about January 27, 2009, and at times prior thereto, where the employer did not establish thickness measurement location (TMLs) for injection points in Crude Unit #2, such as but not limited to injection points: &CR-IP2 (Neutrilizer) and 2CR-IP3 (Filmer) as prescribed by API 570 - Piping Inspection Code. This condition exposed employees to a fire and explosion hazard. Pursuant to 29 CFR 1903(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that all CUI inspections are being properly documented. (c) This violation occurred on or about January 27, 2009, and at times prior thereto, where the employer failed to use qualified inspectors to inspect process piping in Crude unit #2 as required by API 570, Section 4.2, API Authorized Piping Inspector Qualification and Certification and as specified in CRC's work procedure for piping inspections. This condition exposed employees to a fire and explosion hazard. (d) This violation occurred on or about January 27, 2009, and at times prior thereto, where the employer failed to ensure that inspectors performing ultrasonic thickness (UT) testing on piping in Crude Unit #2 were UT Level II, UT Level III, or UTT certified to inspect process piping as per American Society for Nondestructive Testing (ASNT) document SNT-TC-1A and met the requirements as described in CRC's work procedure for performing baseline thickness measurements. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that site piping inspectors are properly trained and certified.
1910.119 J04 III
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $4,900 · Current $4,900
General-duty citation text
maintain its mechanical integrity, is not consistent with applicable manufacturers' recommendations and good engineering practices, and more frequently if determined to be necessary by prior operating experience: (a) This violation occurred on or about January 27, 2009, and at times prior thereto, where the employer did not inspect piping in Crude Unit #2, including the following existing crude oil pipe lines: 4"-C-20104-B2_1-H2", 4"-C-20125-B2_1-H2", 3"-C-20214- B2_1-H2" and 4"-C-20124-B2_1-H3", with the frequency as prescribed by API 570 - Piping Inspection Code. This condition exposed employees to a fire and explosion hazards. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that inspections for process piping systems are performed on the prescribed/recommended frequency as per API 570.
1910.119 J04 IV
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $4,900 · Current $4,900
General-duty citation text
29 CFR 1910.119(j)(4)(iv): The documentation of the inspection or test that been performed on process equipment to maintain its mechanical integrity does not identify the date of the inspection or test, the serial number or other identifier of the equipment on which the inspection or test was performed, a description of the inspection or test, and the results of the inspection or test: (a) This violation occurred on or about January 27, 2009, and times prior thereto, where the employer performed a vibration analysis and did not have the name of the person performing the analysis and interpretation of the results for the P218A-Light Naphtha Product Pump, in Crude Unit #2. This condition exposed employees to a fire and explosion hazards. (b) This violation occurred on or about January 27, 2009, and times prior thereto, where the employer performed a vibration analysis and did not have the name of the person performing the analysis and the interpretation of the results for the P205A-Service Pre- Fractionation Overhead Product Pump, in Crude Unit #2. This condition exposed employees to a fire and explosion hazards. (c) This violation occurred on or about January 27, 2009, and at times prior thereto, where the employer did not have the original thickness measurements needed to calculate short-term and long-term corrosion rates for existing piping circuits in Crude Unit #2 such as, but not limited to, Kerosene piping lines (3"-K-20176, 4"-K-20179, 4"-20193, and 3"-K-20201); Diesel piping lines (4"-D-20177, 3"-D-20178, 4"-D-20194, 3"-D- 20185, 8"-D-50360, and 8"-D-50361); Light Naphtha piping lines (6"-LN-20149, 4"-LN- 20150, 3"-LN-20151, 3"-LN-20152, 3"-LN-20153, and 3"-LN-20158); and Heavy Naphtha piping lines (6"-HN-20222, 6"-HN-20223; 3"-HN-20224, and 3"-HN-20225) as prescribed by API 570 - Piping Inspection Code. This condition exposed employees to a fire and explosion hazard. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that the Inspection and Testing of pumps and piping circuits are being properly documented.
1910.119 M04 V
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $3,500 · Current $3,500
General-duty citation text
29 CFR 1910.119(m)(4)(v): The report prepared at the conclusion of the investigation of an incident which resulted in, or could have reasonably resulted in a catastrophic release of highly hazardous chemical in the workplace, does not include any recommendations resulting from the investigation team: This violation occurred on or about January 27, 2009, and times prior thereto, where the employer did not develop recommendations for the incident that occurred on March 21, 2006, in the #2 Crude Unit that required an incident investigation as outlined in 1910.119(m). This condition exposed employees to a fire and explosion hazard. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that all incidents in a covered process which resulted in, or could reasonably have resulted in a catastrophic release of a highly hazardous chemical in the workplace are investigated and meet the requirements outlined in 1910.119(m).
1910.119 N
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $3,500 · Current $3,500
General-duty citation text
29 CFR 1910.119(n): The employer's emergency action plan does not include procedures for handling small releases: (a) This violation occurred on or about January 27, 2009, and at times prior thereto, where the employer did not include a detailed procedure in its EAP that instructs employees on how to distinguish between small releases/spills and large releases/spills and what actions to take in the event that an incident occurs. The roles and responsibilities for employees designated as Local Responders when responding to spills/releases of hazardous and/or flammable materials in process units, such as but not limited to Crude Unit #2, were not clearly defined by the employer. This condition exposed employees to a fire and explosion hazard. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that procedures are in place to handle small or large spills/releases that may occur at the facility. (b) The employer violated this standard on or about January 27, 2009, and at times prior thereto, where the employer's Emergency Action Plan (EAP) did not include a plan to designate and train employees to assist in the safe and orderly evacuation of other employees and ensure that emergency evacuation procedures were being effectively followed. 29 CFR 1910.119(n) requires that the employer has an EAP in accordance with the provisions of 29 CFR 1910.38. Pursuant to 29 CFR 1903.19(d), within 10 days of the receipt of this citation, the employer must submit an abatement plan describing the action it is taking to ensure that safe and orderly evacuations of employees is to be performed in the event of an emergency situation.
1910.119 O04
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $3,500 · Current $3,500
General-duty citation text
29 CFR 1910.119(o)(4): The employer does not determine and document an appropriate response to each of the findings of the compliance audit required by 29 CFR 1910.119(o)(1), and document that the deficiencies have been corrected: This violation occurred on or about January 27, 2009, and times prior thereto, where Calcasieu Refining Company performed a compliance audit in 1998 and September 2001 and did not document that all the deficiencies observed in the audit were corrected. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that a system is in place to correct all compliance audit deficiencies in a timely fashion and follow the corrections from start to completion.
1910.165 B02
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $3,500 · Current $3,500
General-duty citation text
29 CFR 1910.165(b)(2): The employee alarm can not be perceived above ambient noise or light levels by all employees in the affected portions of the workplace: This violation occurred on or about January 27, 2009, and times prior thereto, where the employer failed to maintain an audible alarm system used to notify employees of fires and other emergency situations. The alarm system could not be heard in the north and south maintenance shops. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that an employee alarm system is in-place that is capable of being perceived above ambient noise levels by all employees in all the affected portions of the workplace.
1910.119 C02
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $700 · Current $700
General-duty citation text
29 CFR 1910.119(c)(2): The employer does not consult with employees and their representative on the development of the Mechanical Integrity (MI) element requirements of process safety management: This violation occurred on or about January 27, 2009, and at times prior thereto, where the employer did not consult employees when it developed the Mechanical Integrity (MI) element requirements. The employer could not demonstrate that there was a dialogue between management and employees, in which the employer encouraged employee participation and responded to employees' concerns and suggestions as it related to the development and implementation of the company's MI program. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with this standard, including describing how it will consult with employees on the development of the MI element of PSM.
1910.119 H02 I
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $700 · Current $700
General-duty citation text
29 CFR 1910.119(h)(2)(i): The employer, when selecting a contractor, does not obtain and evaluate information regarding the contract employer's safety performance and programs: This violation occurred on or about January 27, 2009, and at times prior thereto, where the employer did not obtain and evaluate all contractor's (such as, but not limited to, Ron Williams Construction, Inc.) safety information and programs before allowing them to work on or near process units. Through work request forms initiated by CRC, employees of Ron Williams Construction perform various maintenance and construction activities throughout the facility, in and around PSM covered processes including Crude Unit #2. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that all evaluations of contractors' safety information and programs are being maintained and properly documented.
1910.119 H02 V
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
General-duty citation text
29 CFR 1910.119(h)(2)(v): The employer does not periodically evaluate the performance of contract employers in fulfilling their obligations as specified in 29 CFR 191.119(h)(3): This violation occurred on or about January 27, 2009, and at times prior thereto, where the employer did not periodically evaluate the performance of all contractors (such as, but not limited to, Ron Williams Construction, Inc.) to ensure that the contractors were complying with all contract employer responsibilities required when working in covered process areas at the site, including Crude Unit #2. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that all performance requirements stipulated under 29 CFR 1910.119(h)(3) are completed and maintained.(3)
1910.119 H02 VI
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $700 · Current $700
General-duty citation text
29 CFR 1910.119(h)(2)(vi): The employer does not maintain a contract employee injury and illness log related to contractor's work in process areas: (a) This violation occurred on or about January 27, 2009, and at times prior thereto, where the employer failed to maintain information/documentation on all contract employee injuries and/or illnesses occurring in process areas at the site from years 2006 to present. CRC did not maintain copies of Ron Williams Construction, Inc.'s OSHA 300 Logs or document all their employee' injury/illness cases occurring in process units such as, but not limited to, Crude Unit #2. To abate this violation, the employer must maintain contractor's OSHA 300 Logs and/or a listing documenting all contract employees' injuries and illnesses occurring in the workplace. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that a log of all contractor employees' injuries and/or illnesses occurring at CRC are being properly documented and maintained.
1910.119 M01
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $700 · Current $700
General-duty citation text
29 CFR 1910.119(m)(1): The employer does not investigate each incident which results in, or can reasonably result in, a catastrophic release of a highly hazardous chemicals in the workplace: (a) This violation occurred on or about January 27, 2009, and times prior thereto, where the employer did not investigate incidents on September 10, 2004, March 21, 2006, and September 13, 2007 in the #2 Crude Unit that required an incident investigation as outlined in 1910.119(m). This condition exposed employees to a fire and explosion hazard. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps that it is taking to ensure that a complete investigation, as outlined in 1910.119(m), is conducted for all incidents that may have resulted in a catastrophic release of highly hazardous chemicals.
1910.119 O01
- Issued
- Jul 27, 2009
- Abate by
- Aug 13, 2009
- Penalty
- Initial $700 · Current $700
General-duty citation text
29 CFR 1910.119(o)(1): The employer does not certify that it has evaluated compliance with the provisions of 29 CFR 1910.119 at least every three years to verify that the procedures and practices developed under this standard are adequate and are being followed: (a) This violation occurred on or about January 27, 2009,and times prior thereto,where the employer performed a compliance audit in September 2001 but did not perform compliance audits in September of 2004 and September of 2007. This condition exposed employees to a fire and explosion hazard. (b) This violation occurred on or about January 27, 2009, and times prior thereto, where the employer did not develop or implement an audit program for the Car Seals installed on all relief valves. The company has Car Seals installed on all relief valves but does not have a regular inspection program to verify Car Seals are in place. The Car Seal program has never been monitored to assure it is effective and working as designed. This condition exposed employees to a fire and explosion hazard. To abate this violation, the employer must ensure that compliance audits are conducted every three years to verify that the procedures and practices developed under the OSHA standard are adequate and are being followed. Pursuant to 29 CFR 1903.19(d), within 10 calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure a compliance audit will be conducted every three years.
More inspections in this industry (NAICS 324110)
More inspections in LA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 311529283.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.