CHARLOTTE, NC —
OSHA Inspection: A&D ENVIRONMENTAL SERVICES, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of A&D ENVIRONMENTAL SERVICES, INC. in 200 HAWTHORNE LANE & ELIZABETH AVE, CHARLOTTE, NC 28204 (NAICS 541690). OSHA activity number 311532774.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- A&D ENVIRONMENTAL SERVICES, INC.
- Site address
- 200 HAWTHORNE LANE & ELIZABETH AVE
- City
- CHARLOTTE
- State
- NC
- ZIP
- 28204
- Mailing
- PO BOX 484/2718 UWHARRIE RD, HIGH POINT, NC 27261
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 541690
- SIC code (legacy)
- 8748
- Employees
- 65
- Ownership type
- A
- Industry flags
- Construction safety.
Citations
5 citations on file for this inspection.
95012901
- Issued
- Oct 4, 2007
- Abate by
- Oct 10, 2007
- Penalty
- Initial $2,100 · Current $2,100
General-duty citation text
North Carolina General Statute 95-129(1) of the Occupational Safety and Health Act of North Carolina: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to flammable vapors, fire hazards and explosion: a) at the construction site, in the process of removing 8000-gallon gasoline tanks, the employer did not ensure all ignition sources of fire and/or explosion had been eliminated or controlled by the following requirements: (1) removal of residue from the tanks; (2) purging of flammable vapors from the tanks; and (3) plugging tank openings to 1/4 inch. Reference: National Fire Protection Association (NFPA) 30, Chapter 21, Storage of Liquids in Tanks - Requirement for All Storage Tanks, Section 21.7.4.3 - Removal from Service of Underground Storage Tanks & Section 21.7.4.3.4 - Removal and Disposal. Among other methods, the feasible and acceptable method to abate these hazards is to utilize the dry ice method as recommended by the American Petroleum Institute (API) by adding 1-1/2 to 2 pounds of Dry Ice per 100 gallons of tank capacity to ensure flammable vapors are below the lower explosive limit (LEL). Reference: UST REMOVAL GUIDEBOOK, OKLAHOMA CORPORATION COMMISSION, PETROLEUM STORAGE TANK DIVISION, July, 2004.
Recent events (2)
- — I (S) $2100.00
- — Z (S) $2100.00
1926.152 I06
- Issued
- Oct 4, 2007
- Abate by
- Oct 10, 2007
- Penalty
- Initial $2,100 · Current $1,800 Reduced
Recent events (2)
- — I (S) $1800.00
- — Z (S) $2100.00
1926.251 B01
- Issued
- Oct 4, 2007
- Abate by
- Oct 10, 2007
- Penalty
- Initial $1,050 · Current $700 Reduced
Recent events (2)
- — I (S) $700.00
- — Z (S) $1050.00
1926.251 B06 I
- Issued
- Oct 4, 2007
- Abate by
- Oct 15, 2007
1926.251 B06 II
- Issued
- Oct 4, 2007
- Abate by
- Oct 15, 2007
More inspections at A&D Environmental Services, INC.
View A&D Environmental Services, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 541690)
More inspections in NC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 311532774.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.