MANCHESTER, CT —
OSHA Inspection: GKN AEROSPACE NEW ENGLAND, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of GKN AEROSPACE NEW ENGLAND, INC. in 273 ADAMS STREET, MANCHESTER, CT 06040 (NAICS 336412). OSHA activity number 311761100.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- GKN AEROSPACE NEW ENGLAND, INC.
- Site address
- 273 ADAMS STREET
- City
- MANCHESTER
- State
- CT
- ZIP
- 06040
- Mailing
- 280 ADAMS STREET, MANCHESTER, CT 06040
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 336412
- SIC code (legacy)
- 3724
- Employees
- 91
- Ownership type
- A
Citations
25 citations on file for this inspection.
5(a)(1)
- Issued
- Aug 11, 2009
- Abate by
- Jan 1, 2011
- Penalty
- Initial $6,300 · Current $3,150 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to potential fire and explosion hazards: Grinding/Polishing Department: Combustible aluminum and titanium dust generated during finishing operations was not collected into a adequately designed dust collection system: 1.Finishing of aluminum and titanium parts was done at work benches that were not provided with a dust collection system or hood. Fugitive dust was allowed to migrate into the work area and settle on horizontal surfaces such as the floor, work bench and overhead light fixtures. NFPA 484, Section 6.3.2.1. 2.All grinding and polishing was collected into the same dust collection system. NFPA 484, Section 6.3.2.4 and 10.4.4.4. 3.The dust collector and associated ductwork was used for aluminum, titanium and Inconel grinding and polishing. Grinding of titanium and inconel introduced sparks into the dust collection system. NFPA 484, Section 6.3.2.6. 4.The dust collector and machines were not posted that they were for use with combustible metals and different type of metals were processed into the same dust collection system. NFPA 484, Section 6.3.2.6.1 and 10.4.4.5. 5.The sump of the RotoClone dust collector was not vented at all times. NFPA 484, Section 6.3.4.6 and 10.4.7.6.1. 6.The electrical supply for the grinding/polishing machinery was completely independent of the dust collection systems electrical supply and the machines could be run with the dust collector off or malfunctioning. NFPA 484, Sections 6.3.4.7.1, 6.3.4.7.2, 10.4.4.6.1 and 10.4.4.6.2. 7.Metal (steel) dust pans and brushes were used to clean work areas. A metal handled and bristled brush was provided for cleaning out the ductwork. NFPA 484, Sections 6.4.2.2 and 6.5.7.7.3. 8.A Hafco model HV-55-1510V portable air driven vacuum cleaner was provided to clean fugitive dust that was not approved or listed for use with combustible metal dust, was provided with a plastic hose and steel attachment parts. NFPA 484, Section 6.4.3. Among other abatement methods, one feasible and useful method to correct the hazard is to: 1.Review National Fire Protection Association (NFPA) Standard 484 Standard for Combustible Metals regarding the proper design, installation of use and dust collection systems for use with operations that generate combustible dust. 2.Ensure that all dust generating operations are segregated and provided with suitable dust collection equipment. Specific Abatement Documentation is Required
Recent events (4)
- — P (S) $3150.00
- — F (S) $3150.00
- — I (S) $3150.00
1910.22 A01
- Issued
- Aug 11, 2009
- Abate by
- Jan 1, 2011
- Penalty
- Initial $6,300 · Current $3,150 Reduced
Recent events (4)
- — P (S) $3150.00
- — F (S) $3150.00
- — I (S) $3150.00
1910.178 P01
- Issued
- Aug 11, 2009
- Abate by
- Sep 28, 2009
- Penalty
- Initial $1,350 · Current $675 Reduced
Recent events (3)
- — F (S) $675.00
- — I (S) $675.00
- — Z (S) $1350.00
1910.212 A01
- Issued
- Aug 11, 2009
- Abate by
- Dec 28, 2009
- Penalty
- Initial $1,800 · Current $900 Reduced
Recent events (3)
- — F (S) $900.00
- — I (S) $900.00
- — Z (S) $1800.00
1910.213 D01
- Issued
- Aug 11, 2009
- Abate by
- Aug 14, 2009
- Penalty
- Initial $2,250 · Current $1,125 Reduced
Recent events (3)
- — F (S) $1125.00
- — I (S) $1125.00
- — Z (S) $2250.00
1910.213 H01
- Issued
- Aug 11, 2009
- Abate by
- Aug 14, 2009
- Penalty
- Initial $2,250 · Current $1,125 Reduced
Recent events (3)
- — F (S) $1125.00
- — I (S) $1125.00
- — Z (S) $2250.00
1910.213 H04
- Issued
- Aug 11, 2009
- Abate by
- Aug 14, 2009
Recent events (2)
- — F (S)
- — Z (S)
1910.215 A01
- Issued
- Aug 11, 2009
- Abate by
- Aug 14, 2009
- Penalty
- Initial $3,150 · Current $1,575 Reduced
Recent events (3)
- — F (S) $1575.00
- — I (S) $1575.00
- — Z (S) $3150.00
1910.215 B09
- Issued
- Aug 11, 2009
- Abate by
- Mar 12, 2009
- Penalty
- Initial $1,147 · Current $574 Reduced
Recent events (3)
- — F (S) $573.50
- — I (S) $573.50
- — Z (S) $1147.00
1910.242 B
- Issued
- Aug 11, 2009
- Abate by
- Aug 14, 2009
- Penalty
- Initial $1,800 · Current $900 Reduced
Recent events (3)
- — F (S) $900.00
- — I (S) $900.00
- — Z (S) $1800.00
1910.304 A02
- Issued
- Aug 11, 2009
- Abate by
- Mar 12, 2009
- Penalty
- Initial $1,147 · Current $574 Reduced
Recent events (3)
- — F (S) $573.50
- — I (S) $573.50
- — Z (S) $1147.00
1910.304 G06 VI
- Issued
- Aug 11, 2009
- Abate by
- Aug 14, 2009
- Penalty
- Initial $2,250 · Current $1,125 Reduced
Recent events (3)
- — F (S) $1125.00
- — I (S) $1125.00
- — Z (S) $2250.00
1910.305 G01 IV
- Issued
- Aug 11, 2009
- Abate by
- Mar 12, 2009
- Penalty
- Initial $1,147 · Current $574 Reduced
Recent events (3)
- — F (S) $573.50
- — I (S) $573.50
- — Z (S) $1147.00
1910.307 B
- Issued
- Aug 11, 2009
- Abate by
- Jan 1, 2011
- Penalty
- Initial $6,300 · Current $3,150 Reduced
Recent events (4)
- — P (S) $3150.00
- — F (S) $3150.00
- — I (S) $3150.00
1910.332 B01
- Issued
- Aug 11, 2009
- Abate by
- Jan 29, 2010
- Penalty
- Initial $4,500 · Current $2,250 Reduced
Recent events (4)
- — P (S) $2250.00
- — F (S) $2250.00
- — I (S) $2250.00
1910.333 A
- Issued
- Aug 11, 2009
- Abate by
- Jan 29, 2010
- Penalty
- Initial $4,500 · Current $2,250 Reduced
Recent events (4)
- — P (S) $2250.00
- — F (S) $2250.00
- — I (S) $2250.00
1910.333 B02 I
- Issued
- Aug 11, 2009
- Abate by
- Jan 29, 2010
Recent events (4)
- — P (S)
- — F (S)
- — I (S)
1910.335 A01 I
- Issued
- Aug 11, 2009
- Abate by
- Jan 29, 2010
- Penalty
- Initial $4,500 · Current $2,250 Reduced
Recent events (4)
- — P (S) $2250.00
- — F (S) $2250.00
- — I (S) $2250.00
1910.335 A01 II
- Issued
- Aug 11, 2009
- Abate by
- Dec 28, 2009
Recent events (3)
- — F (S)
- — I (S)
- — Z (S)
1910.1200 H
- Issued
- Aug 11, 2009
- Abate by
- Dec 28, 2009
- Penalty
- Initial $2,250 · Current $1,125 Reduced
Recent events (3)
- — F (S) $1125.00
- — I (S) $1125.00
- — Z (S) $2250.00
1910.178 A06
- Issued
- Aug 11, 2009
- Abate by
- Sep 28, 2009
Recent events (2)
- — F (O)
- — Z (O)
1910.184 F01
- Issued
- Aug 11, 2009
- Abate by
- Sep 28, 2009
Recent events (2)
- — F (O)
- — Z (O)
1910.213 B03
- Issued
- Aug 11, 2009
- Abate by
- Aug 14, 2009
Recent events (2)
- — F (O)
- — Z (O)
1910.219 E03 I
- Issued
- Aug 11, 2009
- Abate by
- Aug 14, 2009
Recent events (2)
- — F (O)
- — Z (O)
1910.242 A
- Issued
- Aug 11, 2009
- Abate by
- Aug 14, 2009
Recent events (2)
- — F (O)
- — Z (O)
More inspections at GKN Aerospace NEW England, INC.
View GKN Aerospace NEW England, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 336412)
More inspections in CT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 311761100.