Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: BROOKLYN BOTTLING CO. OF MILTON, NY INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of BROOKLYN BOTTLING CO. OF MILTON, NY INC. in 643 SOUTH ROAD, MILTON, NY 12547 (NAICS 312111). OSHA activity number 311979975.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Brooklyn Bottling CO. of Milton, NY INC. — free Get an email when a new federal OSHA severe-injury report for Brooklyn Bottling CO. of Milton, NY INC. is published. One employer, no account, unsubscribe in one click.
Site address
643 SOUTH ROAD
City
MILTON
State
NY
ZIP
12547
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Y
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
312111
SIC code (legacy)
2086
Employees
100
Ownership type
A

3 citations on file for this inspection.

5(a)(1)

Serious Gravity 03 1 instance 30 exposed
Issued
Dec 30, 2009
Abate by
Feb 3, 2010
Penalty
Initial $1,125 · Current $1,125
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish a place of employment which was free from recognized hazards that
were causing or
likely to cause death or serious physical harm to employees in that:
employees were exposed to
inhalation and burn hazards resulting from an uncontrolled release of
anhydrous ammonia.
(a)Anhydrous ammonia refrigeration system, on or about 7/1/09:
Refrigeration system was
not adequately designed, installed, and maintained to protect employees
from an
uncontrolled release of anhydrous ammonia vapor.
Abatement note:  Among others, one feasible means of abatement for this
hazard is to
ensure that the anhydrous ammonia refrigeration system complies with the
requirements
of ANSI/ASHRAE-15 1994, Safety Code for Mechanical Refrigeration and
ASME/IIAR
2-2008, Equipment, Design, and Installation of Closed-Circuit Ammonia
Mechanical
Refrigerating Systems, and ensure the following conditions are corrected:
*Safety relief valve discharge pipe on high pressure ammonia receiver did
not
extend above the roofline and was not located a distance of at least 20
feet from
any window or ventilation opening; pipe discharge was located just outside
open
window(s) in the production area (IIAR-2 2008, section 11.3.6.3).
*Penetrations/pipe runs through walls were not sealed to prevent passage of
escaping refrigerant to other parts of the building (IIAR-2 2008, section
13.3.1.9).
*Compressor room exhaust ventilation fan discharge on exterior wall was
located
several feet below open window(s) in the production area (IIAR-2 2008,
section
13.2.3.11).
*Valves and controls in compressor room were not identified with durable
signs
having letters more than 0.5 inch in height designating: valves or
switches
for
controlling refrigerant flow, ventilation, and compressor(s) (ASHRAE 15,
section
11.2.2).
*Two self-contained breathing apparatus (SCBA) were not located immediately
outside of the compressor room (ASHRAE 15, section 11.6).
*Emergency shutdown procedures, including precautions to be observed in
case of
a breakdown or leak, were not displayed on a card or sign located as near
as
possible to the refrigerant compressor(s) (ASHRAE 15, section 11.8).
*Welded repairs to refrigerant piping were not done to appropriate
specifications
(IIAR-2 2008, section 10.1).
Pursuant to 29 CFR 1903.19(c), the employer must provide certification to
OSHA
that this violation has been abated within 10 calendar days of the "Date
by which
Violation Must be Abated".

1910.134 F02

Serious Gravity 03 1 instance 5 exposed
Issued
Dec 30, 2009
Abate by
Jan 7, 2010
Penalty
Initial $1,125 · Current $1,125

1910.151 C

Serious Gravity 03 1 instance 5 exposed
Issued
Dec 30, 2009
Abate by
Jan 7, 2010
Penalty
Initial $1,125 · Current $1,125