TULSA, OK —
OSHA Inspection: SINCLAIR TULSA REFINING COMPANY
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of SINCLAIR TULSA REFINING COMPANY in 902 W. 25TH ST., TULSA, OK 74107 (NAICS 324110). OSHA activity number 312380512.
Where did this inspection happen?
- Establishment
- SINCLAIR TULSA REFINING COMPANY
- Site address
- 902 W. 25TH ST.
- City
- TULSA
- State
- OK
- ZIP
- 74107
- Mailing
- P.O. BOX 970, TULSA, OK 74101
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Last modified
- Data loaded
Establishment context
- NAICS code
- 324110
- SIC code (legacy)
- 2911
- Employees
- 260
- Ownership type
- A
Citations
52 citations on file for this inspection.
5(a)(1)
- Issued
- Abate by
- Penalty
- Initial $2250.00 · Current $2250.00
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to the hazard of falls and/or being struck-by or caught-by moving equipment where access to an elevator hoistway was not restricted: The employer does not ensure that elevators are installed, inspected, and maintained to ensure access to the hoistway is restricted to authorized personnel only. As a result, employees have access to the top of the elevator cars where they are exposed to falls in the elevator hoistway and/or being struck-by moving parts. This violation was observed on or about February 4, 2009, for the FCCU elevator car operating without a cover over the top emergency hatch. Among other methods, one feasible and acceptable means of abatement would be to ensure elevator equipment is installed, inspected and maintained in accordance with Safety Code for Elevators and Escalators, ASME A17.1, 1996 and current editions. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the steps that is taking to ensure compliance with ASME A17.1 such as required inspections and maintaining restricted and safe access to elevator hoistways.
5(a)(1)
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $4500.00
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees exposed to fall hazards when walking/working on the tops of tractor trailer tankers: The employer does not ensure that each employee working from the top of tractor trailer tankers with unprotected sides and edges is protected from falling by a personal fall arrest system (PFAS) or an appropriate custom-fit guardrail system. This violation was observed on or about February 10, 2009, for the Asphalt Loading Rack area where process operators and contract truck operators were not protected from the hazard of a fall of 10 feet to the concrete surface below. Among other methods, one feasible and acceptable means of abatement would be to ensure that employees performing work from the top of a tractor trailer tanker are protected from falls by a PFAS utilizing anchorages attached to existing overhead structure, or an equivalent means of fall protection. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the steps that is taking to ensure that employees working from the tops of tractor trailer tankers are protected from falls.
5(a)(1)
- Issued
- Abate by
- Penalty
- Initial $3150.00 · Current $3150.00
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer does not furnish employment and a place of employment which are free from recognized hazards that are causing or likely to cause death or serious physical harm to employees who were exposed to the hazard of burns from contact with hot equipment surfaces: The employer does not ensure that each employee is protected from contact with hot surfaces on process equipment. This violation was observed on or about March 19, 2009, along the north and east decks of the regenerator column on the 5th floor of the FCCU Complex where employees were exposed to skin burns from contact with equipment with surface temperatures of 325-335 degrees F, and which were not insulated or otherwise guarded to prevent bodily contact. Among other methods, one feasible and acceptable means of abatement would be to extend the external guardrails, as had been done similar area to prevent bodily contact with hot surfaces. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the steps that is taking to ensure that employees working around equipment with hot surfaces are protected from contact with the surfaces.
5(a)(1)
- Issued
- Abate by
- Penalty
- Initial $3150.00 · Current $3150.00
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to tripping hazards when walking/working on multiple levels of the FCCU structure where grating was detached and not level: The employer does not ensure that walking/working surfaces are level and free from tripping hazards. This violation was observed on or about March 13, 2009, on multiple levels of the FCCU structure where employees were exposed to tripping hazards where grating and metal decking was detached, not level, and contained holes. Among other methods, feasible and acceptable means of abatement includes repairing the floor levels with patches and welding techniques. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the steps that it is taking to ensure all walking/working surfaces are free from tripping hazards.
1910.23 A02
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $4500.00
General-duty citation text
29 CFR 1910.23(a)(2): Every ladderway floor opening or platform was not guarded by a standard railing, or swinging gate, or so offset that a person cannot walk directly into the opening: The employer does not ensure that ladderway floor openings are guarded by a standard railing, or equilavent means, to prevent employees from falling through the openings. This violation was observed on or about April 24, 2009, on multiple levels of the FCCU structure where employees walking/working in the vicinity of unguarded ladderway openings were exposed to fall hazards up to approximately 80 feet to the concrete and equipment surfaces below. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the steps that it is taking to ensure all ladderway openings are guarded.
1910.23 C01
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $4500.00
General-duty citation text
29 CFR 1910.23(c)(1): Open-sided floors or platforms four feet or more above adjacent floor or ground level were not guarded with standard railings (or equivalent) on all open sides; and toeboards where hazard exposures exist below: The employer does not ensure that open-sided floors and platforms are provided with standard railing or equivalent means of guarding: a) This violation was observed on or about March 19, 2009, in the FCCU where employees walking/working on a platform without guardrails around the regenerator were exposed to a fall hazard of approximately 18 to 20 feet to the grated surface below. b) This violation was observed on or about April 15, 2009, in the FCCU where employees walking/working on a platform without guardrails around the B-2 charge heater and blow- down crows nest were exposed to a fall hazard of approximately 25 feet to the concrete surface below. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit an abatement plan describing the steps it is taking to ensure guardrails are erected along all open-sided floors and platforms.
1910.23 C02
- Issued
- Abate by
General-duty citation text
29 CFR 1910.23(c)(2): Runways four feet or more above floor or ground level were not guarded by standard railings (or the equivalent): The employer does not ensure that open-sided platforms and walkways are provided with standard railings or equivalent means of guarding. This violation was observed on or about February 10, 2009, at the Asphalt Loading Rack where employees walking/working on a runway leading from the loading rack to the top of trailers, and not equipped with handrails or equivalent on an open side, were exposed to a fall hazard of approximately 10 feet to the concrete surface below. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the steps that it is taking to ensure all open- sided runways are guarded with standard railing or the equivalent.
1910.23 E01
- Issued
- Abate by
General-duty citation text
29 CFR 1910.23(e)(1): Standard railing(s) consisting of a top rail, intermediate rail and posts did not have a vertical height of 42 inches (106.7 cm) nominal from upper surface of top rail to floor, platform, runway, or ramp level: The employer does not ensure that top rails of standard guardrail systems are at least 42 inches in height. This violation was observed on or about February 10, 2009, for the Asphalt Loading Rack where the platform's guardrail system has a top rail height of 30.5 inches. Employees walking/working on the loading are exposed to a fall hazard of 10 feet to the concrete surface below. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the steps that it is taking to ensure all standard railings are 42 inches in height.
1910.101 A
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $4500.00
General-duty citation text
29 CFR 1910.101(a): The employer did not determine that compressed gas cylinders under his control were in a safe condition to the extent that could be determined by visual or other inspections: The employer does not ensure that compressed gas cylinders are maintained in a safe condition. This violation was observed on or about March 19, 2009, in the FCCU where employees were exposed to fire and/or explosion hazards while walking/working in and around the oxygen analyzer room where stored compressed gas cylinders lacked protective valve caps and were severely rusted on the bottom. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the steps that it is taking to ensure all compressed gas cylinders are stored and maintained in a safe condition.
1910.101 B
- Issued
- Abate by
General-duty citation text
29 CFR 1910.101(b): The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks was not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in Sec. 1910.6: The employer does not ensure that stored, compressed gas cylinders are properly secured to prevent tipping, placed so as not to become part of an electrical circuit, and labeled to identify the gases. This violation was observed on or about March 19, 2009, in the FCCU where employees were exposed to fire, explosion and struck-by hazards while walking/working in and around the oxygen analyzer room where stored, compressed gas cylinders were not secured to prevent tipping, were placed near open electrical boxes and were not labeled to identify the type of compressed gas. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the steps that it is taking to ensure all compressed gas cylinders are properly stored, marked and handled.
1910.119 D02 ID
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $4500.00
General-duty citation text
29 CFR 1910.119(d)(2)(i)(D): Process-safety information pertaining to the technology of the process did not include the safe upper and lower limits for such items as temperatures, pressures, flows or compositions: The employer does not develop process-safety information pertaining to the technology of the process. The FCCU Operating Manual does not specify the safe upper and lower limits for items such as temperatures, pressure, flows and/or compositions pertaining to the technology of the unit process; this violation was observed on or about February 4, 2009. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the steps it is taking to ensure the operating manual specifies process safety information (PSI) pertaining to the technology of the process to include the safe upper and lower limits for items such as temperatures, pressures, flows and/or compositions; the PSI shall be clear and easily referred to, such as tabular format.
1910.119 D02 II
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $4500.00
General-duty citation text
29 CFR 1910.119(d)(2)(ii): Where the original technical information no longer exists, process safety information pertaining to the technology of the process was not developed in conjunction with the process hazard analysis in sufficient detail to support the analysis: The employer does not develop process safety information pertaining to the technology of the process in conjunction with the process hazard analysis where the original technical information no longer exists. This violation was observed on or about February 4, 2009 in the Crude Unit, where the employer operates FA-24, an atmospheric blowdown drum, when there is incomplete original design and design basis information. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to develop process safety information pertaining to the technology of the process for FA-24, the Crude Unit atmospheric blowdown drum.own
1910.119 D03 ID
- Issued
- Abate by
General-duty citation text
29 CFR 1910.119(d)(3)(i)(D): Process safety information pertaining to the equipment in the process did not include the relief system design and design basis: The employer operates an atmospheric blowdown drum when there is incomplete original and updated design and design basis information. This violation was observed on or about February 4, 2009 in the Crude Unit, where the employer operates FA-24, an atmospheric blowdown drum, without complete original and updated design and design basis information. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to document original and updated design and design basis process safety information pertaining to FA-24, the Crude Unit atmospheric blowdown drum. Process safety information on the FA-24 blowdown drum must include design and design basis information such as, but not limited to, the physical and chemical properties of materials relieved to the blowdown drum, a definition of the loadings to be handled, the exit velocity of gasses/vapors released from the vent stack, design basis/worst case scenario for maximum liquid-vapor releases to the blowdown, the geographic locations of the devices and valves releasing to the blowdown, the design residence time of the vapor and liquid in the drum, the design basis for the vapor - liquid separation for the drum, the design basis for the exit velocities for the vent stack, and the nature of other, lesser hazards related to smaller releases not related to the design "worst-case" scenario such as the release of toxic (e.g., H2S) and corrosive chemicals.
1910.119 D03 IF
- Issued
- Abate by
General-duty citation text
29 CFR 1910.119(d)(3)(i)(F): The employer did not ensure written process safety information includes design codes and standards employed: The employer does not have written process safety information for design codes and standards employed for equipment such as, but not limited to, the instances provided below. The conditions were observed on or about February 4, 2009, and at times prior to and thereafter, at the Sinclair Tulsa Refinery. a)In the CDU: No design codes and standards used to construct and modify the FA-24 knockout (blowdown) drum. b)In the FCCU: No design codes and standards used to construct and operate positive pressure control system for the FCCU/Scanfiner/Alky Control Room. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the steps it is taking to ensure that the written process safety information is completed.
1910.119 D03 IB
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $4500.00
General-duty citation text
29 CFR 1910.119(d)(3)(i)(B): Process safety information pertaining to the equipment in the process did not include the piping and instrument diagrams (P&ID's): The employer does not ensure that the piping and instrument diagrams associated with process equipment are updated or validated to reflect current field design conditions. This violation was observed on or about February 4, 2009 in the FCCU in that: a) P&ID DWG. No. 11949-0-D representing FCC-015 piping circuit; the P&ID is not concurrent with actual field operation. b) P&ID DWG. No. 11950-0-D representing FCC-014 piping circuit; the P&ID is not concurrent with actual field operation. c) P&ID DWG. No. 11958-0-D, 11960-0-D, and 12280-0-D representing FCC-070 piping circuit; the P&ID is not concurrent with actual field operation. d) P&ID DWG. No. 11969-0-D representing FCC-112 piping circuit; the P&ID is not concurrent with actual field operation. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure the P&IDs are accurate, up-to-date and reflect actual field conditions.
1910.119 L04
- Issued
- Abate by
General-duty citation text
29 CFR 1910.119(l)(4): A change covered by 29 CFR 1910.119 (l) resulted in a change in the process safety information required by 29 CFR 1910.119(d) and the process safety information was not updated: The employer does not ensure process safety information (PSI) is updated as required by paragraph (d) of the PSM standard when the process is modified/changed. This violation was most recently discovered on or about February 4, 2009, and at times prior thereto and thereafter, when the employer did not update FCCU process flow diagrams (PFDs) or piping and instrument diagrams (P&IDs). The employer is deficient on PSI, such as, but not limited to, the following: a) PFD drawing 13326-D, Rev. A, current on February, 4, 2009; "7J-15A, 15C, 50" are depicted on the flow diagram as the wet gas compressors in service in the FCCU; 7J-15A and C are not in service. b) PFD drawing 13326-D, Rev. A, current on February, 4, 2009; equipment information on the PFD lists 7J-15A, 15C, 7J-42 and 7J-42M as wet gas compressors in service in the FCCU; wet gas compressors 7J-15A, 7J-15C, 7J-42 and 7J-42M are not in service. c) PFD drawing 13326-D, Rev. A., current on February, 4, 2009: a compressor dry drum, 7F-8, is depicted on the flow diagram upstream of the wet gas compressors in service in the FCCU; the compressor dry drum, 7F-8 is not in service. d) PFD drawing 13326-D, Rev. 0., updated on February, 19, 2009: equipment information on the PFD lists 7F-8 as the compressor dry drum in service in the FCCU; the compressor dry drum, 7F-8 is not in service. e) P&ID 11947-O-D, Rev. 3: P&ID depicts 7G-4, a catalyst removal cyclone, which was removed from the Unit, and does not depict the Donaldson Torit Baghouse added to the Unit after the cyclone was removed from service. f) The Plot Plan in the FCCU Operating Procedures Manual shows the locations of the J- 15A, J-15C, and J-42; this equipment is no longer on the Unit. g) The Plot Plan in the FCCU Operating Procedures Manual does not show the location of J- 50. h) In the FCCU Operating Procedures Manual, Section 307, the equipment description for catalyst recovery equipment in the FCCU Operating Manual has information on 7G-4, the Catalyst Disposal Cyclone, which was taken out of service in 2008. There is no description of the Baghouse that was installed on the Unit when the cyclone was taken out of service. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit an documentation showing that it is in compliance with the standard; in addition, an abatement plan must be submitted describing the steps it is taking to ensure all PFDs and P&IDs are accurate, up-to-date and depict all equipment existing in the field, as well as steps it is taking to ensure that PSI remains up-to-date and accurate. Every 30 days thereafter, the employer shall submit a progress report stating how many PFDs and P&IDs have been updated, how many still need to be updated, whether it is meeting the schedule set forth in its abatement plan, and if not why not; and whether it is maintaining the PFDs and P&IDs that have been updated.
1910.119 D03 II
- Issued
- Abate by
- Penalty
- Initial $6300.00 · Current $6300.00
General-duty citation text
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices (RAGAGEP): The employer does not ensure that process safety information pertaining to the equipment in the process contains documentation that all equipment complies with RAGAGEP. The conditions were observed, as noted in (a) through (c) below, on or about February 4, 2009, and at times prior to and thereafter, at the Sinclair Tulsa Refinery. a) In the CDU: The employer does not document that the FA-24 knockout drum vent stack complies with RAGAGEP where it does not determine vent stack height is appropriate according to radiant heat levels; does not determine mitigation measures for hazards other than vapor cloud explosion such as exposure to H2S; and does not ensure prevention of flashback by using a purging media other than steam. The FA-24 vent stack is not compliant with RAGAGEP such as API 521, Pressure-relieving and Depressuring Systems. b) In the FCCU: The new control building housing multiple refinery units (Scanfiner/FCCU/Alky) was designed for blast overpressures; however, the employer has not documented its compliance regarding the control room's role as a safe haven during emergency releases of flammable or toxic materials. The positive pressure control system lacks system equipment such as hydrocarbon or toxic (hydrogen sulfide) detectors to shut down the intake of contaminated air. The control room is not compliant with RAGAGEP such as API 752 Management of Hazards Associated with Location of Process Plant Buildings. c) In the FCCU: The employer does not document that atmospheric releases from relief system equipment, such as, relief valves on the E-1 Fractionator (309, 312, 358, 359, 2077, 2078, 2079, 2281, 2283, 2861), E-5 Splitter (2763, 2764), F-4 Fractionator Reflux Drum (2781, 2782), F-11 Debutanizer Reflux Drum (2765, 2766), F-12 Splitter Reflux Drum (2768, 2769) are discharged to safe locations in compliance with RAGAGEP such as API 521. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit an abatement plan describing the actions it is taking to ensure equipment in the process is compliant with RAGAGEP.
1910.119 D03 III
- Issued
- Abate by
- Penalty
- Initial $6300.00 · Current $6300.00
General-duty citation text
29 CFR 1910.119(d)(3)(iii): For existing equipment designed and constructed in accordance with codes, standards, or practices that are no longer in general use, the employer does not determine and document that equipment is designed, maintained, inspected, tested and operating in a safe manner: The employer does not have written process safety information for design, maintenance, inspection, testing and operations that determines and documents the safe use and operation of the Crude Unit control room. The control room conditions do not prevent infiltration of hydrocarbons or toxics, do not prevent struck-by hazards, do not prevent fire spread, and do not provide a safe location from blast overpressure conditions. The conditions were observed on or about February 4, 2009, and at times prior to and thereafter, at the Sinclair Tulsa Refinery. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the actions it is taking to ensure that the Crude Unit control room is designed, maintained, inspected, tested and operating in a safe manner.
1910.119 E01
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $4500.00
General-duty citation text
29 CFR 1910.119(e)(1): The process hazard analysis was not appropriate to the complexity of the process and did not identify, evaluate, and control the hazards of the process: The employer does not evaluate and control discharges of hydrocarbons to the atmosphere. This violation was observed on or about February 4, 2009, in the CDU where the employer fails to comprehensively evaluate the discharge of hot, heavier-than-air hydrocarbons from the vent stack of the FA-24 blowdown drum by means such as conducting a plume study. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the steps that it is taking to ensure that the discharge of hydrocarbons from the vent stack of the FA-24 blowdown drum is to a safe location.
1910.119 E03 V
- Issued
- Abate by
General-duty citation text
29 CFR 1910.119(e)(3)(v): The process hazard analysis (PHA) did not address facility siting: The employer does not address facility siting during PHA's regarding relief system equipment that discharges to atmosphere. This violation was observed on or about February 4, 2009, and at times prior thereto, for the 1995 Crude Unit PHA (and subsequent PHA revalidations) the employer does not consider the siting of its employees or facilities in relation to hydrocarbon releases from relief system equipment that discharges to the atmosphere. a) In the CDU: Work platforms within 50 feet of the discharge from the vent stack from FA- 24, blowdown drum, expose employees to fire and explosion from hydrocarbons and inhalation of toxic hydrogen sulfide. Heavier than air hydrocarbons can be released from the vent stack, collect at ground level, and cause vapor cloud explosions. b) In the CDU: Work platforms within 50 feet of the FA-1, atmospheric tower, relief valves expose employees to possible fire and explosion from hydrocarbon releases. c) In the CDU: FA-18, stabilizer tower, relieves to atmosphere near the crude unit heaters exposing employees to possible fire and explosion from hydrocarbon releases. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the steps that it is taking to ensure that the discharge of hydrocarbons from FA-24 blowdown drum, FA-1 atmospheric tower and FA-18 stabilizer tower is to a safe location.r
1910.119 E03 VI
- Issued
- Abate by
- Penalty
- Initial $6300.00 · Current $6300.00
General-duty citation text
29 CFR 1910.119(e)(3)(vi): The process hazard analysis did not address human factors: At the Fluid Catalytic Cracking Unit (FCCU): The employer does not identify or evaluate the possibility of human error in its PHA due to confusion when equipment described in a written procedure is not labeled/marked with an identifier in the field. This condition was specifically identified for operators accessing equipment in instances described below as (a), (b) and (c), but is not limited to equipment in these procedures. The conditions were present on or about February 4, 2009, and at times prior to and thereafter, at the Sinclair Tulsa Refinery. a) For procedure 1210 - Transfer of Catalyst from F-2 Used Catalyst Drum into Trucks. b) For procedure 1302 - Loss of Feed. c) For procedure 1305 - 250# Steam Failure. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard including describing the steps that it is taking to ensure that the human factors hazard analysis is effectively applied for PHA conducted at the refinery.
1910.119 E05
- Issued
- Abate by
- Penalty
- Initial $6300.00 · Current $6300.00
General-duty citation text
29 CFR 1910.119(e)(5): The employer did not establish a system to promptly address process hazard analysis (PHA) team findings and recommendations; assure that the recommendations are resolved in a timely manner and that the resolution is documented; document what actions are to be taken; complete actions as soon as possible; develop a written schedule of when these actions are to be completed; communicate the actions to operating, maintenance and other employees whose work assignments are in the process and who may be affected by the recommendations or actions: The employer does not establish a system to promptly address action items from the process hazard analysis. The employer violated this standard for multiple PHA's and PHA revalidations covering approximately 16 years. The employer violated this standard on or about February 4, 2009, and at times prior thereto, where the employer does not resolve action items from process hazard analysis in a timely manner. a) In the CDU: A PHA recommendation was made to install a high level alarm on the FA- 24 knockout drum in the initial 1995 PHA and subsequent PHA revalidations and was not installed until June 2008 (13 years). b) In the CDU: A PHA recommendation was made to investigate moving the vent line from the FA-24 knockout drum away from the atmospheric tower in the initial 1995 PHA and subsequent PHA revalidations; however, the vent line remains in the same condition. c) In the FCCU: The employer did not install H2S monitors to address the hazard of hydrogen sulfide identified in the 1995 PHA and subsequent PHA revalidations. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the steps that it is taking to ensure the findings, recommendations, and resolutions for process hazard analysis are promptly addressed. The employer must document what actions are to be taken, develop a written schedule of when the actions are to be completed, and communicate the actions to affected employees.
1910.119 F01 I
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $4500.00
General-duty citation text
29 CFR 1910.119(f)(1)(i): The employer did not develop and implement written operating procedures that provide clear instructions for safely conducting activities involved in each covered process consistent with process safety information: On or about February 4, 2009, and at times prior thereto, the employer does not develop detailed written operating procedures. These procedures, among others, are deficient: a) In the FCC Unit for Emergency Operating Procedure, Section 1314, D-2 Regenerator Low Temperature. b) In the FCC Unit for Emergency Operating Procedure, Section 1304, Cooling Water Failure. c) In the FCC Unit for Section 1301, General Emergency Shutdown Procedure. d) In the FCC Unit for Section 1303, Loss of Level in F-7 Condensate Tank. e) In the FCC Unit for Section 1302, Loss of Feed. f) In the FCC Unit for Section 1305, 250# Steam Failure. g) In the FCC Unit for Section 1310, Loss of Vacuum on C-11 Surface Condenser. h) In the FCC Unit for Section 1311, Leak in C-01 Flue Gas Cooler Tubes. i) In the FCC Unit for Section 1312, Leak in C-02 Slurry Cooler Tubes. j) In the FCC Unit for Section 1002, Normal Operations, Routine Activities. k) In the CDU, procedures for operations of the blowdown FA-24 Pursuant to 29 CFR 1903.19, within ten (10) days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps that it is taking to ensure that operating procedures have sufficient detail and specificity to provide clear operating steps.ing
1910.119 F01 IIA
- Issued
- Abate by
General-duty citation text
29 CFR 1910.119(f)(1)(ii)(A): The employer's written operating procedures did not contain detailed operating limits, consequences of deviation, and steps required to correct or avoid deviation: On or about February 4, 2009, and at times prior thereto, the employer does not develop detailed written operating procedures containing operating limits, consequences of deviation, and steps required to correct or avoid deviation. These procedures, among others, are deficient: a) In the FCC Unit for Emergency Operating Procedure, Section 1314, D-2 Regenerator Low Temperature. b) In the FCC Unit for Emergency Operating Procedure, Section 1304, Cooling Water Failure. c) In the FCC Unit for Section 1301, General Emergency Shutdown Procedure. d) In the FCC Unit for Section 1303, Loss of Level in F-7 Condensate Tank. e) In the FCC Unit for Section 1302, Loss of Feed. f) In the FCC Unit for Section 1305, 250# Steam Failure. g) In the FCC Unit for Section 1310, Loss of Vacuum on C-11 Surface Condenser. h) In the FCC Unit for Section 1311, Leak in C-01 Flue Gas Cooler Tubes. i) In the FCC Unit for Section 1312, Leak in C-02 Slurry Cooler Tubes. Pursuant to 29 CFR 1903.19, within ten (10) days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps that it is taking to ensure the development of detailed written operating procedures containing operating limits, consequences of deviation, and steps required to correct or avoid deviation.
1910.119 F03
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $4500.00
General-duty citation text
29 CFR 1910.119(f)(3): The operating procedures were not reviewed as often as necessary to assure that they reflect current operating practice, including changes that result from changes in process chemicals, technology, and equipment, or changes to facilities and the employer did not certify annually that the operating procedures are current and accurate: The employer does not review operating procedures as often as necessary to assure they are current, and does not certify annually that the operating procedures are current and accurate. The FCCU Operating Manual was last certified as current and accurate on January 23, 2008. After the certification in 2008, the Catalyst Disposal Cyclone, 7G-4, was taken out of service and a baghouse was installed on the Unit; Special Operating Procedure Section 1210 - Transfer of Catalyst from F-2 into Trucks was not updated to reflect changes in equipment, and the procedure did not reflect current operating practice with regard to the lineup of the discharge blowers to the catalyst truck. This violation was observed on or about February 4, 2009. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure operating procedures are maintained to reflect current operating practices, as well as current process chemicals, technology, equipment and facilities, as well as the steps it is taking to ensure operating procedures are certified current and accurate on an annual basis.
1910.119 F04
- Issued
- Abate by
- Penalty
- Initial $6300.00 · Current $6300.00
General-duty citation text
29 CFR 1910.119(f)(4): The employer did not develop and implement safe work practices for opening process equipment: The employer does not ensure that safe work practices are used when opening process equipment. This violation occurred on or about February 4, 2009, and times thereafter, in the refinery where employees were potentially exposed to the hazard of burns from contact with hot product/steam, chemical inhalation and/or physical contact with chemicals while opening and working on process equipment such as, pump repair, replacement of packing, installation of piping, and repair of float columns. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure specific procedures for draining, purging and steaming of process equipment and piping are developed and implemented, as well as describing the steps it is taking to ensure energy isolation procedures are developed and implemented which specifically detail and identify all equipment (valves, blinds, piping, etc.) affected/involved in the procedure (for example, through the use of unique identifiers and P&ID's).
1910.119 H02 IV
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $4500.00
General-duty citation text
29 CFR 1910.119(h)(2)(iv): The employer did not ensure that contract employees follow the host employer's safe work practices when entering, exiting, or working in the covered process areas: The employer does not ensure contractors are properly signed in/out of the FCCU to allow effective personnel accounting and emergency evacuation/rescue procedures. This violation was observed on or about March 19, 2009, in the FCCU where employees and contractors were exposed to the hazards of fire, explosion and toxic releases while working in the FCCU. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the steps that is taking to ensure that contractors are signing in and out of process units.
1910.119 H02 V
- Issued
- Abate by
- Penalty
- Initial $6300.00 · Current $6300.00
General-duty citation text
29 CFR 1910.119(h)(2)(v): The employer did not periodically evaluate the performance of contract employers in fulfilling their obligations as specified in paragraph 1910.119(h)(3): The employer does not ensure that the equipment used by contractors is evaluated for safe use, such as Bond Painting's use of bares wires and a 12 volt battery to power fuel pumps. This violation was observed on or about April 15, 2009, in the refinery, where employees and contractors were exposed to the hazard of flash fire and explosions due to a contractor's use of spark producing equipment in the process units. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the steps that is taking to ensure that an evaluation of contractor equipment is conducted.
1910.119 J02
- Issued
- Abate by
- Penalty
- Initial $6300.00 · Current $6300.00
General-duty citation text
29 CFR 1910.119(j)(2): The employer did not establish and implement written procedures to maintain the on-going mechanical integrity of process equipment: The employer does not have written procedures or implemented actions for the on-going mechanical integrity of equipment such as the instances provided below. The conditions were observed on or about February 4, 2009, and at times prior to and thereafter, at the Sinclair Tulsa Refinery. a) In the CDU: High level alarm installed on the FA-24 blowdown drum is not included in the inspection, testing, and maintenance program. b) At the refinery: The employer's Mechanical Integrity Procedure does not address anomalous inspection data, such as the unresolved anomalous inspection data for FCCU piping circuits FCC-070 and FCC-112. c) In the FCCU: At the FCCU/Scanfiner/Alky Control Room, the differential pressure gauge and alarm for the positive pressure control system is not in the inspection, testing and maintenance program. d) In the FCCU: The employer does not develop and implement written procedures for the inspection and testing and preventative maintenance of equipment, instrumentation, alarms and controls employed and designed to prevent process safety hazardous situations from occurring such as, SLV-0057, SLV-0058, SLV-0059, SLV-0060, SLV-0074, SLV-0075, Emergency Feed Valves V-2 and V-3 in feed lines 2A and 2B, valves V-4 and V-5 in blowdown lines from feed heater outlet, HC-0212, HC-0209, FC-0135, PDI-0076, PDI- 0053, PDI-0055, PI-006, PC-0230, and PC-0155. e) At the refinery: The employer does not develop and implement a work order system to maintain the on-going mechanical integrity of process equipment. The lack of a work order system has allowed deficiencies in relief and vent systems and devices when the line supplying steam to the Crude Unit FA-24 atmospheric blowdown vent line froze and broke, and was not repaired for an undetermined period of time, at least greater than one year. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that the written mechanical integrity program is complete and implemented and includes loop and function testing of critical equipment.
1910.119 J04 IV
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $4500.00
General-duty citation text
29 CFR 1910.119(j)(4)(iv): The employer did not document each inspection and test that had been performed on process equipment to maintain its mechanical integrity: The employer does not document inspections and tests of process equipment such as FCCU slide valves. This violation was most recently observed on or about February 4, 2009, when the employer did not document testing of safety critical equipment listed in Section 902, of the FCCU Operating Manual. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure inspection and testing is documented as required by this paragraph.
1910.119 J05
- Issued
- Abate by
- Penalty
- Initial $6300.00 · Current $6300.00
General-duty citation text
29 CFR 1910.119(j)(5): The employer did not correct deficiencies in equipment that are outside acceptable limits (defined by the process safety information in paragraph (d) of this section) before further use or in a safe and timely manner when necessary means are taken to assure safe operation: The employer does not ensure employees are protected from falling chunks of fireproofing and fire/explosion/toxic hazards where fireproofing material is not maintained in good repair. This violation was observed on or about February 4, 2009 throughout the battery limits of the Crude Unit (CDU) and Fluid Catalytic Cracking Unit (FCCU), fireproofing for structural steel supporting process equipment was found to be cracked, falling apart, missing, deteriorating and generally in a state of disrepair for areas such as the pipe rack vertical support members (CDU), vertical structure supports at debutanizer structure (CDU), base shoe type supports at EA-23 (CDU), and various portions of the steel structure supporting the FCCU regenerator (multiple stories high). The fire control and disaster mitigation design purpose of the fireproofing is not effective due to its state of disrepair. Further, the condition presents avenues for corrosive elements to impart deteriorating action on underlying structural steel and presents overhead falling object hazards from falling chunks of fireproofing. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the actions it is taking to ensure fireproofing material is maintained and structural steel supporting process equipment is properly protected from fire and corrosion. IN THE ALTERNATIVE: Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees exposed to the hazard of struck-by, fire, explosion and toxic inhalation associated with the deterioration of fireproofing material on structural supporting steel in refinery process units. Among other methods, feasible and acceptable abatement of this hazard includes the installation, maintenance, repair and inspection of fireproofing materials for structural steel in accordance with standards such as UL 1709, API 2218, NFPA, manufacturer of fireproofing material, equipment engineering standards and common industry practice.
1910.119 K01
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $4500.00
General-duty citation text
29 CFR 1910.119(k)(1): The employer did not issue a hot work permit for hot work operations conducted on or near a covered process: a) March 19, 2009, in the FCCU, where employees are exposed to the hazard of flash fires while using spark producing, or non-intrinsically safe, equipment such as cameras without conducting atmospheric testing and issuing a hot work permit. b) April 20, 2009, in the refinery, where a contractor's use of spark producing equipment, such as Bond Painting's use of bare wires connected to a 12-volt battery to supply power for fuel pumps, exposing employees and contractors to the hazard of flash fire and explosions. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the steps that is taking to ensure the issuance of hot work permits for all hot work operations conducted in the refinery units.
1910.119 L01
- Issued
- Abate by
- Penalty
- Initial $6300.00 · Current $6300.00
General-duty citation text
29 CFR 1910.119(l)(1): The employer does not implement written procedures to manage changes to process chemicals, technology, equipment, and procedures: a) For the Crude Distillation Unit: On or about February 4, 2009, and at times prior thereto, the employer does not implement management of change procedures for increasing the charge to the unit. b) On or about February 4, 2009, and at times prior thereto, the employer does not implement management of change procedures for the application of cooling steam to hot spots on the FCCU D-2 Regenerator shell. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure written management of change procedures are implemented to manage changes to process chemicals, technology, equipment, procedures and changes to facilities that affect a covered process.
1910.119 L02 I
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $4500.00
General-duty citation text
29 CFR 1910.119(l)(2)(i): The written procedures to manage changes did not assure that the technical basis for the proposed change was addressed prior to any change: The employer does not assure written MOC procedures address the technical basis for proposed changes prior to implementation of the change; MOC 96-034, "Install New Wet Gas Compressor" does not detail and address the technical basis for the change for the J-50 Wet Gas Compressor installed in the FCCU in 1997. Pursuant to 29 CFR 1903.19, the employer must submit an abatement plan within ten (10) calendar days describing the steps it is taking to ensure MOC specify and address the technical basis for changes, ensuring the procedure details and addresses items such as, but not limited to, what is to be changed, what is to be achieved by the change, and why the change is safe to make. The employer must also review all MOC procedures that must be retained for the life of the process due to their incorporation into part of the Process Safety Information (those MOC's addressing chemicals and equipment that will/have become part of the Process Safety Information (PSI) , thus giving the employer a documented record of the original design and design intent of the covered process and also providing a record of all changes to the process that are of importance to those responsible for safe operation and maintenance and to those that may need to consider future changes to the process). Every 30 days thereafter, the employer shall submit a progress report stating how many MOC have been updated, how many still need to be updated, whether it is meeting the schedule set forth in its abatement plan, and if not why not; and whether it is ensuring all subsequent MOCs address the technical basis for the change prior to making the change.
1910.119 L02 II
- Issued
- Abate by
General-duty citation text
29 CFR 1910.119(l)(2)(ii): The written procedures to manage changes did not assure that the impact of the change on safety and health was addressed prior to any change: The employer did not address the impact of change on safety and health prior to implementing the change; the employer failed to address the impact of installing a new wet gas compressor (J-50) in the FCCU prior to the equipment's installation. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the abatement date listed in this citation, the employer must submit an abatement plan describing the actions it is taking to ensure that the impact of change on safety and health is being addressed and that recommendations are resolved. The employer must also review all MOC procedures and assure that the impact of the change on safety and health has been addressed. Within twenty- five (25) calendar days of the abatement date listed in this citation, the employer shall submit a progress report stating how many MOC procedures do not address the safety and health impact of changes. Every 30 days thereafter, the employer shall submit a progress report stating how many have been updated and how many still need to be updated; of those that have been updated, the employer must also report on how many recommendations have been resolved, how many resolutions require corrective action, and how many corrective actions have been completed, and how the employer is assuring that the impact of change on safety and health is addressed prior to the implementation of any changes.
1910.119 L03
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $4500.00
General-duty citation text
29 CFR 1910.119(l)(3): Employees involved in operating a process and maintenance and contract employees whose job tasks will be affected by a change in the process were not informed of, and trained in, the change prior to start-up of the process or affected part of the process: The employer does not inform and train contract employees whose job tasks will be affected by a change in process prior to the start-up of a process or affected part of the process. This violation most recently occurred on or about February 5, 2009 when contract employees were not informed and trained on the installation of LEL monitors on the road way designed to notify vehicles of the potential hazard of a flammable atmosphere near the perimeter of the Wet Gas Compressor and to prevent the introduction of ignition sources to a flammable atmosphere. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date listed of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that the management of change equipment instructions and procedures are communicated to all affected personnel.
1910.119 M05
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $4500.00
General-duty citation text
29 CFR 1910.119(m)(5): The employer did not establish a system to promptly address and resolve the incident report findings and recommendations. Recommendations and corrective actions were not documented: On or about February 4, 2009, and at times prior thereto, the employer does not have a system to track incident resolution and recommendations. The recommendations and corrective actions are not always documented or completed in a timely manner. a) In the FCCU: Incident 04-006 - No confirmation or documentation that recommendation #3 was completed. b) In the FCCU: Incident 06-003 - Recommendation #1 was not completed for over seven months. No confirmation or documentation that recommendation #2 was completed. c) In the FCCU: Incident 07-014 -No documentation on recommendations #2-5. It is not clear from the documentation provided that recommendation #6 was resolved in a timely manner. Recommendation #7 was not instituted for 21 months. d) In the FCCU: Incident 07-025 - Recommendations #1-3 were not resolved for seven months. e) In the FCCU: Incident 07-004 - Recommendations not completed for over 11 months. Pursuant to 29 CFR 1903.19, within ten (10) days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps that it is taking to ensure that incident report findings and recommendations are promptly addressed and resolved and ensure that recommendations and corrective actions are documented.
1910.119 N
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $4500.00
General-duty citation text
29 CFR 1910.119(n): The employer did not establish and implement an emergency plan for the entire plant in accordance with the provisions of 29 CFR 1910.38: a) The windsock by the main entrance was torn and not in proper operating condition, exposing employees to possible smoke or chemical inhalation, explosions and fires. This violation was observed on or about February 10, 2009, at the Sinclair Tulsa Refinery. b) The windsock by the main entrance was not illuminated at night, exposing night shift employees to possible smoke or chemical inhalation, explosions and fires. This violation was observed on or about April 2, 2009, at the Sinclair Tulsa Refinery. c) Windsocks could not be seen from all points within the Crude Unit, exposing employees to possible smoke or chemical inhalation, explosions and fires. This violation was observed on or about April 1, 2009 at the Sinclair Tulsa Refinery. d) Emergency procedures do not evaluate and provide for use of control rooms at the FCCU and CDU as safe havens or shelter in place locations where operators are required to stay in the control rooms to take mitigating actions during emergency upset conditions; employees are exposed to smoke or chemical inhalation, explosions and fires where control rooms are not equipped with toxic or hydrocarbon detection systems, life support systems such as supplied air, and self-contained breathing apparatus are not maintained in sufficient quantity for the personnel exposed. e) The employer does not include a procedure in its emergency action plan/emergency response plan that instructs employees on how to distinguish between small releases and spills versus large releases or spills; and what employee actions are required in both instances. This violation was observed on or about February 4, 2009, where refinery personnel and the employer's emergency plans could not provide procedures for handling small releases. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps it is taking to ensure that windsocks are maintained in proper operation condition, windsocks are illuminated at night, and are in plain sight from all points within the refinery, and emergency actions for all personnel are properly determined with provisions for emergency equipment. In addition, the employer must describe the steps it is taking to ensure the emergency action plan/emergency response plan describes the various hazardous substances on site that have the potential to cause an emergency; defines the types of releases that could potentially require an emergency response and defines what types of releases would not be an emergency; instructs employees on how to distinguish between small releases and spills versus large releases and spills; instructs employees on required actions in both instances; and ensures employees are trained on the actions they are to take.
1910.119 O04
- Issued
- Abate by
- Penalty
- Initial $6300.00 · Current $6300.00
General-duty citation text
29 CFR 1910.119(o)(4): The employer did not promptly determine and document an appropriate response to each of the findings of the compliance audit, and document that deficiencies have been corrected: On or about February 4, 2009, and at times prior thereto, compliance audit items are not corrected and documented. These items were carried over from the 2003 compliance audit to the 2006 compliance audit. a) P&Ids need updating. b) Lack of evaluation of contract employer's safety performance and programs. c) Pre-startup safety reviews have not been documented for all modifications. d) Lack of written maintenance procedures. e) Some of the MOCs do not include evidence to indicate that the impact of the change on safety and health was adequately evaluated. f) Not all training completed for MOCs. g) Incident investigations not initiated within 48 hours. h) Lack of documentation that incident investigation recommendations have been resolved. i) A formal training program for maintenance and inspection. Pursuant to 29 CFR 1903.19, within ten (10) days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps that it is taking to ensure that recommendations of compliance audits are resolved and that defiencies identified are corrected.
1910.157 C04
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $4500.00
General-duty citation text
29 CFR 1910.157(c)(4): Portable fire extinguishers were not maintained in a fully charged and operable condition: The employer does not ensure that fire extinguishers are maintained in good operating condition. This violation was observed on or about February 10, 2009, at the asphalt loading rack where a fire extinguisher was covered in asphalt, exposing employees to the hazard of burns and smoke inhalation. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the steps that is taking to ensure that fire extinguishers are inspected and maintained in proper operating condition.
1910.165 B03
- Issued
- Abate by
- Penalty
- Initial $3150.00 · Current $3150.00
General-duty citation text
29 CFR 1910.165(b)(3): The employer did not have an employee alarm system that was distinctive and recognizable as a signal to evacuate the work area or to perform actions designated under the emergency action plan: The employer does not ensure that a distinctive alarm system is in place to warn of leaks, spills, or severe weather. This violation was observed on or about March 6, 2009, where the lack of a distinctive alarm exposes employees to the hazards of fire, explosion, toxic inhalation, flying debris and hazardous chemicals during refinery emergency events. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the steps that is taking to ensure that distinctive and recognizable alarms are in place that distinguish between chemical leaks, spills, fires or inclement weather.t
1910.165 D02
- Issued
- Abate by
General-duty citation text
29 CFR 1910.165(d)(2): The employer did not test the reliability and adequacy of non- supervised employee alarm systems every two months: The employer does not ensure that unit alarms are operating properly by conducting a test at least once every two months. This violation was observed on or about March 18, 2009, in the FCCU at the Sinclair Tulsa Refinery, where a test/sounding of the unit alarm last occurred around October of 2007. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps that it is taking to ensure unit alarms are tested at least once every two months.
1910.176 C
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $4500.00
General-duty citation text
29 CFR 1910.176(c): Storage areas were not kept free from accumulation of materials that constituted hazards from tripping, fire, explosion or pest harborage: The employer does not ensure that hazardous chemicals are properly stored. This violation was observed on or about May 5, 2009, in the Bechtel Building, where organic peroxides were not stored in a climate-controlled area at temperatures recommended by the chemical manufacturer, exposing employees to the hazard of fire and explosion. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps that it is taking to ensure proper storage of hazardous chemicals.
1910.303 B01
- Issued
- Abate by
- Penalty
- Initial $1800.00 · Current $1800.00
General-duty citation text
29 CFR 1910.303(b)(1): Electric equipment was not free from recognized hazards likely to cause death or serious physical harm to employees: The employer does not ensure that electrical equipment is free from recognized hazards. This violation was observed on or about April 24, 2009, for instances such as: a) In the Bechtel Building: Electrical outlet near the entrance door was cracked and broken. b) In the FCCU Regenerator structure analyzer room: Electrical boxes left open exposing equipment with lack of electrical insulation. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the steps that is taking to ensure that electrical installations are maintained free from recognized hazards.
1910.307 C
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $4500.00
General-duty citation text
29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location: The employer does not ensure that hazardous (classified) locations contain only equipment that is intrinsically safe or otherwise safe for the location. a) Violation was observed in the FCCU on or about March 19, 2009, in the oxygen analyzer room where live electrical wiring in an electrical panel was not maintained in a enclosed intrinsically safe electrical panel. b) Violation was observed in the CDU on or about February 4, 2009, in the Crude Unit Control Room where standard household appliances (stove, coffee maker, refrigerator) and standard electrical installations were used in a Class 1, Division II hazardous location. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the steps that is taking to ensure that hazardous locations are equipped with safe electrical equipment and installations.
1910.1026 D02 V
- Issued
- Abate by
- Penalty
- Initial $2250.00 · Current $2250.00
General-duty citation text
29 CFR 1910.1026(d)(2)(v): When periodic monitoring indicated that employee exposures were below the action level, the result was not confirmed by the result of another monitoring taken at least seven days later: In the weld shop: On or about February 4, 2009, and at times prior thereto, the employer does not conduct the required follow up monitoring after personal monitoring on August 28, 2007, for employees welding, cutting, grinding, and pipe fitting chromium-containing alloy steel revealed an exposure to hexavalent chromium over the PEL of 5 micrograms per cubic meter of air, calculated as an 8-hour time-weighted average. After followup monitoring on October 1 and 2, 2007, for two employees, the employer does not confirm the result by subsequent monitoring at least seven days later. Pursuant to 29 CFR 1903.19, within ten (10) days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps that it is taking to ensure that periodic monitoring for hexavalent chromium is conducted as required.
1910.1026 M01 I
- Issued
- Abate by
General-duty citation text
29 CFR 1910.1026(m)(1)(i): The employer did not maintain an accurate record of all air monitoring conducted to comply with the requirements of this section: In the weld shop: On or about February 4, 2009, and at times prior thereto, the employer did not maintain personal sampling records for employees engaged in welding, cutting, grinding, and pipe fitting chromium-containing alloy steel. Six employees were sampled and only three monitoring records were provided. Records that were provided in response to the OSHA subpoena did not contain social security numbers or duration of sampling. Pursuant to 29 CFR 1903.19, within ten (10) days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps that it is taking to ensure that employees with possible exposure to hexavalent chromium are trained.
1910.1028 E02 I
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $4500.00
General-duty citation text
29 CFR 1910.1028(e)(2)(i): The employer who has a place of employment covered under paragraph (a)(1) of this section did not monitor each of these workplaces and work operations to determine accurately the airborne concentrations of benzene to which employees may be exposed: On or about February 4, 2009, and at times prior thereto, a) In all refinery units: for operating employees engaged in draining, purging and steaming to eliminate hydrocarbons from process vessels, equipment and related piping in preparation for maintenance. b) In all refinery units: for maintenance employees repairing process vessels, equipment and related piping. Pursuant to 29 CFR 1903.19, within ten (10) days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps that it is taking to ensure that employees with possible exposure to benzene are monitored for that exposure.
1910.1028 E03 II
- Issued
- Abate by
General-duty citation text
29 CFR 1910.1028(e)(3)(ii): When the monitoring required by paragraph (e)(2)(i) of this section reveals employee overexposure above the permissible exposure level, the employer did not repeat such monitoring for each such employee at least every six (6) months: On or about February 4, 2009, and at times prior thereto, a) In all refinery units: for operating employees engaged in draining, purging and steaming to eliminate hydrocarbons from process vessels, equipment and related piping in preparation for maintenance. b) In all refinery units: for maintenance employees repairing process vessels, equipment and related piping. c) On or about October 2007, multiple employees at the OIF unit and Crude Unit were exposed to over 0.66 ppm as calculated for a 12-hour TWA. Pursuant to 29 CFR 1903.19, within ten (10) days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps that it is taking to ensure that periodic monitoring for benzene is conducted as required.
1910.1028 K01
- Issued
- Abate by
General-duty citation text
29 CFR 1910.1028(k)(1): The employer did not establish and maintain an accurate record of all measurements required by paragraph (e) of this section, in accordance with 29 CFR 1910.1020: On or about February 4, 2009, and at times prior thereto, a) In the crude distillation unit: for employees engaged during a process unit shutdown in draining, purging and steaming to eliminate hydrocarbons from process vessels, equipment and related piping. Twelve employees were sampled and only four monitoring records were provided. b) In the OIF unit: for employees engaged during a process unit shutdown in draining, purging and steaming to eliminate hydrocarbons from process vessels, equipment and related piping. Thirty-one employees were sampled and only thirteen monitoring records were provided. c) In the Alky/Poly/Penex unit: for employees engaged during a process unit shutdown in draining, purging and steaming to eliminate hydrocarbons from process vessels, equipment and related piping. Twenty-six employees were sampled and no monitoring records were provided. Records that were provided in response to the OSHA subpoena did not contain social security numbers, type of respiratory protection, or duration of sampling. Pursuant to 29 CFR 1903.19, within ten (10) days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps that it is taking to ensure that employee monitoring records for benzene are complete and maintained in accordance with 29 CFR 1910.1020.
1910.1200 G08
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $4500.00
General-duty citation text
29 CFR 1910.1200(g)(8): The employer did not ensure that material safety data sheets (MSDS) were readily accessible during each work shift to employees when they are in their work areas: On or about February 4, 2009, and at times prior thereto, the employer did not make material safety data sheets available to employees. Pursuant to 29 CFR 1903.19, the employer must submit an abatement plan within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the steps that it is taking to ensure that material safety data sheets are readily accessible during each work shift to employees when they are in their work areas.
1910.119 E05
- Issued
- Abate by
- Penalty
- Initial $63000.00 · Current $63000.00
General-duty citation text
SINCLAIR TULSA REFINING COMPANY WAS PREVIOUSLY CITED FOR VIOLATION OF THIS OCCUPATIONAL SAFETY AND HEALTH STANDARD OR ITS EQUIVALENT STANDARD, 29 CFR 1910.119(e)(5), WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 308062280, CITATION 1, ITEM 2, ISSUED ON SEPTEMBER 7, 2005 FOR THE WORKSITE LOCATED AT 902 W. 25TH STREET, TULSA, OKLAHOMA. 29 CFR 1910.119(e)(5): The employer does not promptly address process hazard analysis (PHA) findings and recommendations; assure that the recommendations are resolved in a timely manner and that the resolution is documented; document what actions are to be taken; complete actions as soon as possible; develop a written schedule of when these actions are to be completed; communicate the actions to operating, maintenance and other employees whose work assignments are in the process and who may be affected by the recommendations or actions: At the Crude Unit: The employer does not promptly address PHA recommendations intended to protect employees from fire, flammable hydrocarbon releases with ignition sources and toxic hydrogen sulfide releases. PHA recommendations the employer fails to resolve include, but are not limited to, the instances provided below. The conditions were present on or about February 4, 2009, and at times prior to and thereafter, at the Sinclair Tulsa Refinery. a)In the 1995 CDU PHA Electrical Analysis: Electrical classification system exists to prevent electrical equipment from creating fires. Division 2 areas include the control room. To declassify the control room, several steps will have to be takenthe control room would need to be pressurized with fresh air or at least given a positive purge of fresh air. b)In the 1995 CDU PHA Safety Analysis: Investigate adding combustible gas and H2S monitors with alarms to the pumps rooms and around the control room. Investigate pressurizing the control room and adding a loss of pressure alarm. Pursuant to 29 CFR 1903.19, within 10 calendar days of the abatement date listed in this citation, the employer must submit an abatement plan describing the actions it is taking to ensure that the Crude Unit PHA recommendations are resolved and documented fully. The violations must be abated no later than 90 days from receipt of this citation.
More inspections in this industry (NAICS 324110)
TORRANCE, CA—2026-07-15 00:00:00
TORRANCE REFINING COMPANY LLC
NOME, TX—2026-07-13 00:00:00
EXXON MOBIL OIL CORPORATION
EL SEGUNDO, CA—2026-06-30 00:00:00
CHEVRON U.S.A. INC.
EL SEGUNDO, CA—2026-06-30 00:00:00
CHEVRON U.S.A. INC.
TRAINER, PA—2026-06-26 00:00:00
MONROE ENERGY, LLC
More inspections in OK
TULSA, OK—2026-07-15 00:00:00
LA UNION 7 LLC
STILLWATER, OK—2026-07-13 00:00:00
LATSHAW DRILLING COMPANY
BROKEN ARROW, OK—2026-07-10 00:00:00
AMERICAN WHEATLEY
TINKER AFB, OK—2026-07-09 00:00:00
U.S. DEPARTMENT OF DEFENSE, TINKER AIR FORCE BASE
OCHELATA, OK—2026-07-08 00:00:00
WALMART, INC.
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 312380512.