Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,197,549Inspections Most recent open 2026-08-27 Last loaded 2026-08-31

OSHA Inspection: NC STATE UNIVERSITY - PHYSICAL PLANT

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of NC STATE UNIVERSITY - PHYSICAL PLANT in 2411 YARBOROUGH DRIVE, RALEIGH, NC 27695 (NAICS 611310). OSHA activity number 312455280.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch NC State University - Physical Plant for free Get an email when a new federal OSHA severe-injury report for NC State University - Physical Plant is published. One employer, no account, unsubscribe in one click.
Site address
2411 YARBOROUGH DRIVE
City
RALEIGH
State
NC
ZIP
27695
Mailing
CAMPUS BOX 8007, RALEIGH, NC 27695
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
Non-union (N)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
611310
SIC code (legacy)
8221
Employees
11000
Ownership type
State government (C)
Industry flags
Manufacturing health.

8 citations on file for this inspection.

95012901

Serious 1 instance 10 exposed
Issued
Apr 8, 2009
Abate by
May 26, 2009
Penalty
Initial $1,925 · Current $1,444 Reduced
North Carolina General Statute 95-129(1) of the Occupational Safety and
Health Act of North Carolina:
The employer did not furnish each of his employees conditions of
employment and a place of employment free
from recognized hazards that were causing or likely to cause death or
serious physical harm  to employees, in
that employees were exposed to steam hazards that could result in thermal
burns.
a)NC State University, facilities department - where employees were
exposed to ruptures in the
steam pipe system when required to work with steam lines. The steam lines
have an internal
pressure of 150 PSIG and a temperature of approximately 365 degrees
Fahrenheit.
Abatement Note:
One feasible and acceptable abatement method is to develop written
operation and maintenance
procedures for piping systems deemed necessary to ensure safe facility
operations.
Reference: ASME B31.1 - 2007 Power Piping, Chapter VII Operation and
Maintenance.
Recent events (2)
  • · F (S) $1443.75
  • · Z (S) $1925.00

95012901

Serious 1 instance 1 exposed
Issued
Apr 8, 2009
Abate by
May 26, 2009
Penalty
Initial $1,925 · Current $1,444 Reduced
North Carolina General Statute 95-129(1) of the Occupational Safety and
Health Act of North Carolina:
The employer did not furnish each of his employees conditions of
employment and a place of employment free
from recognized hazards that were causing or likely to cause death or
serious physical harm to employees, in
that employees were exposed to steam hazards that could result in thermal
burns.
a)NC State University, facilities department - where employees were
exposed to thermal burns
when required to perform testing on the steam traps. The steam lines have
an internal pressure
of 150 PSIG and a temperature of approximately 365 degrees Fahrenheit.
Abatement Note:
One feasible and acceptable abatement method is to develop written test
procedures for steam traps
deemed necessary to ensure safe facility operations.
Reference: ASME PTC 39-2005 Steam Traps, Performance Test Codes, Section
3.ction
Recent events (2)
  • · F (S) $1443.75
  • · Z (S) $1925.00

1910.147 C04 I

Other-than-serious 1 instance 10 exposed
Issued
Apr 8, 2009
Abate by
May 26, 2009
Recent events (2)
  • · F (O)
  • · Z (S)

95012901

Other-than-serious 1 instance 8 exposed
Issued
Apr 8, 2009
Abate by
Apr 13, 2009
Penalty
Initial $962
29 CFR 1910.252(a)(1)(i):  When the object to be welded or cut could not
be readily moved, all movable
fire hazards in the vicinity were not taken to a safe place:
a)maintenance shed - where employees do stick and mig welding on steel
pipes, valves,
etc. was within 7 feet of where, moveable fire hazards such as
approximately 5 gas-
powered trash pumps, were being stored.
Abatement Note:
One feasible and acceptable abatement method is to relocate the gasoline
powered trash pumps or the
welding operations.
Recent events (2)
  • · F (O)
  • · Z (S) $962.00

1910.146 C05 IC

Deleted Serious 1 instance 1 exposed
Issued
Apr 8, 2009
Abate by
May 26, 2009
Penalty
Initial $1,925
Recent events (2)
  • · F (S)
  • · Z (S) $1925.00

1910.146 C05 IIC

Serious 4 instances 1 exposed
Issued
Apr 8, 2009
Abate by
May 26, 2009
Penalty
Current $1,444
Recent events (2)
  • · F (S) $1443.75
  • · Z (S)

1910.146 C05 IIE1

Serious 1 instance 1 exposed
Issued
Apr 8, 2009
Abate by
May 26, 2009
Recent events (2)
  • · F (S)
  • · Z (S)

1910.146 C05 IIF

Serious 4 instances 1 exposed
Issued
Apr 8, 2009
Abate by
May 26, 2009
Recent events (2)
  • · F (S)
  • · Z (S)

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 312455280.