READING, PA —
OSHA Inspection: BIRCHCRAFT KITCHENS
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of BIRCHCRAFT KITCHENS in 425 RICHMOND STREET, READING, PA 19605 (NAICS 337110). OSHA activity number 312504715.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BIRCHCRAFT KITCHENS
- Site address
- 425 RICHMOND STREET
- City
- READING
- State
- PA
- ZIP
- 19605
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 337110
- SIC code (legacy)
- 2434
- Employees
- 28
- Ownership type
- A
- Industry flags
- Manufacturing health.
Citations
1 citation on file for this inspection.
5(a)(1)
- Issued
- Oct 21, 2009
- Abate by
- Dec 6, 2012
- Penalty
- Initial $875 · Current $610 Reduced
E200
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to the potential hazard of fire and explosion: (a)West Side of Building (Outside) - The MAC dust collection system, model number 144MCF255, used to collect class II wood dust from the planar, table saws and sanders did not have a backflash damper, on or about June 17, 2009. (b)West Side of the Building (Outside) - The exhaust air duct from the MAC dust collection system, model number 144MCF255, was recycled back into the building during the winter months. The system was not equipped with an isolation device such as but not limited to a high-speed abort gate, on or about June 17, 2009. (c)North Side of the Building (Outside) - The dust collection system(cyclone) on top of the storage bin did not have deflagration venting, on or about June 17, 2009. ABATEMENT NOTE: Among other methods, one feasible and acceptable method to correct the hazard is to comply with the National Fire Protection Association (NFPA 664), Standard for the Prevention of Fires and Explosions in Wood Processing and Woodworking facilities"-2007 as it applies to your operations and equipment including but not limited to: A.Equip the MAC dust collection system with a backflash damper, designed and installed in accordance with National Fire Protection Agency(NFPA) 664. B.Install deflagration vents on the cyclone in accordance with National Fire Protection Agency(NFPA) 664. C.The exhaust air recycled back to the building shall be equipped with a high-speed abort gate to intercept any burning material before entering the plant as listed in Paragraph 8.2.2.6.2 of NFPA 664. VERIFICATION REQUIRED
Recent events (5)
- — I $17000.00
- — Z $26250.00
- — P (S) $610.00
More inspections at Birchcraft Kitchens
View Birchcraft Kitchens's full OSHA safety record →
More inspections in this industry (NAICS 337110)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 312504715.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.