NEWBURGH HTS, OH —
OSHA Inspection: MCGEAN-ROHCO INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of MCGEAN-ROHCO INC. in 2910 HARVARD AVE., NEWBURGH HTS, OH 44105 (NAICS 325998). OSHA activity number 312564008.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MCGEAN-ROHCO INC.
- Site address
- 2910 HARVARD AVE.
- City
- NEWBURGH HTS
- State
- OH
- ZIP
- 44105
- Mailing
- 2910 HARVARD AVE., NEWBURGH HEIGHTS, OH 44105
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 325998
- SIC code (legacy)
- 2819
- Employees
- 55
- Ownership type
- A
Citations
1 citation on file for this inspection.
5(a)(1)
- Issued
- Feb 17, 2009
- Abate by
- Mar 22, 2009
- Penalty
- Initial $875
General-duty citation text
5(a)(1): Section 5 (a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm, including severe burns, to employees in that employees were exposed to the hazard of dust explosions, deflagration or other hazards from Chrome processing equipment: a)Processing area was not separated from other parts of the building due to openings in fire walls which did not have an approved self-closing fire door. b)Access doors were not bonded and grounded. c)A cyclone is not protected with explosion protection systems and is located inside the building. d)No devices to limit or prevent explosions in the spray dryer were provided. Among other methods, a feasible abatement method to correct this hazard is: Remove hold open devices on door and repair the latching device and install doors in other fire wall penetrations. Install bonding and grounding wires on all access doors in equipment. Relocate cyclone outside the building and install relief venting or other explosion suppression or prevention system. Install devices to prevent or limit the effects of explosions in the spray dryer. Installations and modifications should be done per requirements of the National Fire Protection Association (NFPA) 654 Standard for the Prevention of Fire and Dust Explosions from the Manufacturing, Processing and Handling of Combustible Solids and NFPA 69 Standard on Explosion Prevention Systems and NFPA 68 Guide for Venting Deflagrations.
Recent events (2)
- — I (S)
- — Z (S) $875.00
More inspections at Mcgean-Rohco INC.
View Mcgean-Rohco INC.'s full OSHA safety record →
More inspections in this industry (NAICS 325998)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 312564008.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.