DES PLAINES, IL —
OSHA Inspection: ANCHOR MECHANICAL, INC.
Accident-driven inspection · Health discipline
At a glance
On , OSHA opened an accident-driven health inspection of ANCHOR MECHANICAL, INC. in 656 PEARSON ST., DES PLAINES, IL 60016 (NAICS 238220). OSHA activity number 312752249.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ANCHOR MECHANICAL, INC.
- Site address
- 656 PEARSON ST.
- City
- DES PLAINES
- State
- IL
- ZIP
- 60016
- Mailing
- 215 S. ABERDEEN, CHICAGO, IL 60607
What kind of inspection was it?
- Inspection type
- Accident-driven (A)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238220
- SIC code (legacy)
- 1711
- Employees
- 105
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.1000 A02
- Issued
- Jun 2, 2009
- Abate by
- Jul 20, 2009
- Penalty
- Initial $3,500 · Current $3,500
C730
Recent events (2)
- — F (S) $3500.00
- — Z (S) $3500.00
1910.1000 E
- Issued
- Jun 2, 2009
- Abate by
- Jul 20, 2009
C730
Recent events (2)
- — F (S)
- — Z (S)
5(a)(1)
- Issued
- Jun 2, 2009
- Abate by
- Jul 20, 2009
- Penalty
- Initial $3,500 · Current $2,000 Reduced
C730
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish a place of employment which was free from recognized hazards that were likely to cause death or serious physical harm to employees. An employee was exposed to increased levels of carbon monoxide when the employer failed to ensure that exhaust venting on heating boilers was properly maintained. a) On December 5, 2008, Anchor Mechanical, Inc. did not ensure that employees were furnished a place of employment which was free from recognized hazards that were causing or likely to cause death or serious physical harm to employees. An employee was exposed to approximately 786 parts per million (ppm) of carbon monoxide as an 8-hour TWA in a boiler room at the Metropolitan Square Condominiums in Des Plaines,IL when the exhaust ventilation for a boiler was not exhausting properly. Among others, one feasible and acceptable method to correct this hazard includes: following the Cleaning and Maintenance procedures for Lochinvar boilers as they pertain to exhaust ventilation and as outlined in the Lochinvar Installation and Service Manual. In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification. This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence of abatement, or other written records.
Recent events (2)
- — F (S) $2000.00
- — Z (S) $3500.00
1910.1000 E
- Issued
- Jun 2, 2009
- Abate by
- Jul 20, 2009
C730
Recent events (2)
- — F (S)
- — Z (S)
More inspections at Anchor Mechanical, INC.