WICHITA, KS —
OSHA Inspection: METAL IMPROVEMENT INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of METAL IMPROVEMENT INC. in 1618 S. IDA, WICHITA, KS 67211 (NAICS 332811). OSHA activity number 312797145.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- METAL IMPROVEMENT INC.
- Site address
- 1618 S. IDA
- City
- WICHITA
- State
- KS
- ZIP
- 67211
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332811
- SIC code (legacy)
- 3398
- Employees
- 30
- Ownership type
- A
Citations
6 citations on file for this inspection.
5(a)(1)
- Issued
- Feb 20, 2009
- Abate by
- Feb 4, 2009
- Penalty
- Initial $1,275 · Current $1,275
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to falling load hazards: Industrial area - Employees were exposed to hazards of being struck by an overloaded hoist as it falls. A CM 1/2 Ton hoist did not have a load rating marked on the hoist clearly legible from the loading position as required by ANSI B30.11 1973 paragraph 11-1.1.2. Among other methods, one method of abating this hazard is to test load the hoist with 125 of its expected maximum load to determine its capacity and post that capacity on the hoist. 29 CFR 1903.19(c)(2) abatement of the above violation was verified at the time of inspection. No certification is required.tion
Recent events (2)
- — I (S) $1275.00
- — Z (S) $1275.00
1910.304 F05 V
- Issued
- Feb 20, 2009
- Abate by
- Feb 17, 2009
- Penalty
- Initial $1,275 · Current $1,275
Recent events (2)
- — I (S) $1275.00
- — Z (S) $1275.00
1910.305 B01
- Issued
- Feb 20, 2009
- Abate by
- Feb 17, 2009
- Penalty
- Initial $1,275 · Current $1,275
Recent events (2)
- — I (S) $1275.00
- — Z (S) $1275.00
1910.147 C04 I
- Issued
- Feb 20, 2009
- Abate by
- Feb 25, 2009
- Penalty
- Initial $10,000 · Current $10,000
Recent events (2)
- — I (R) $10000.00
- — Z (R) $10000.00
1910.303 B02
- Issued
- Feb 20, 2009
- Abate by
- Feb 17, 2009
Recent events (2)
- — I (O)
- — Z (O)
1910.303 F
- Issued
- Feb 20, 2009
- Abate by
- Mar 3, 2009
Recent events (2)
- — I (O)
- — Z (O)
More inspections at Metal Improvement INC.