CONVENT, LA —
OSHA Inspection: MOTIVA ENTERPRISES LLC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of MOTIVA ENTERPRISES LLC in 10700 LA. HWY. 44, CONVENT, LA 70723 (NAICS 324110). OSHA activity number 313030306.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MOTIVA ENTERPRISES LLC
- Site address
- 10700 LA. HWY. 44
- City
- CONVENT
- State
- LA
- ZIP
- 70723
- Mailing
- P.O BOX 37, CONVENT, LA 70723
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 324110
- SIC code (legacy)
- 2911
- Employees
- 500
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.27 F
- Issued
- Oct 27, 2010
- Abate by
- Nov 15, 2010
- Penalty
- Initial $7,000
General-duty citation text
29 CFR 1910.27(f): Fixed ladder(s) were not maintained in a safe condition: The employer is not maintaining fixed metal ladders in a safe condition, such as, but not limited to: a) The ladder from the ground to the E350 - 351 Steam Generator landing shakes when in use; b) The ladder from the ground, designated 70F 302 - 303 is not secured to a stationary object and shakes when in use; and, c) The ladder from the ground, designated 12307N70PS14G92LD1007, next to Pipe Support 308, shakes when in use. These hazards were most recently observed on August 26, 2010, at Motiva Enterprises LLC, Convent, La. 70723 in the H-Oil unit. Pursuant to 29 CFR 1903.19, within (10) calendar days of the abatement date listed in this citation, the employer must submit an abatement plan describing the actions it is taking to ensure that fixed ladders are maintained in a safe condition. The violation must be abated no later than 30 days from receipt of this citation.
Recent events (2)
- — J (S)
- — Z (S) $7000.00
1910.119 E03 VI
- Issued
- Oct 27, 2010
- Abate by
- Nov 15, 2010
- Penalty
- Initial $7,000
General-duty citation text
29 CFR 1910.119(e)(3)(vi): The employer did not address all human factors related to closing specific isolation valves during emergency situations when it conducted its PHA: The employer does not consider human factors in that the employer did not identify and evaluate the locations of DP-70 emergency isolation values/panels in the H-Oil unit that could potentially place employees in a hazardous situation during emergencies, exposing employees to fire and/or explosion. On or about May 05, 2010, and July 20, 2010, this violation was found at Motiva Enterprises LLC, Convent, LA where the following DP-70 valves/panels were observed throughout the H-Oil unit: -LCB 101 (Train 100 Emergency Isolation Valves) TRN-100 DP-70 -LCB 102 (DGA Pumps, C-101 Comp, P-130 & P-180 -LCB 103 (P-117, P-101, P-151 & P-201 -LCB 201 (Train 100 Emergency Isolation Valves) TRN-200 DP-70 -LCB 301 (Diesel product pump suction -LCB 302 (Diesel product pump suction -LCB 401 (EM Dump Valves, M/U Comp Pursuant to 29 CFR 1903.19 within 10 calendar days, the employer must submit an abatement plan describing the actions it is taking to ensure that locations of emergency isolation valves/panels (DP-70s) that must be closed in emergencies are identified and evaluated. The violation must be abated no later than 30 days from receipt of this citation.
Recent events (2)
- — J (S)
- — Z (S) $7000.00
1910.119 E05
- Issued
- Oct 27, 2010
- Abate by
- Nov 8, 2010
- Penalty
- Initial $7,000 · Current $5,000 Reduced
General-duty citation text
29 CFR 1910.119(e)(5): The employer did not establish a system to promptly address the team's findings and recommendations to assure that the recommendations were resolved in a timely manner and that the resolution was documented: a) The employer does not ensure that hazardous conditions, as determined by Hazard analysis, are promptly addressed in a reasonable and timely manner. On or about December 3, 2004 until present, the employer failed to address employee (i.e. operator) exposure after determining that employee operators housed in the Operator Control House #3 were exposed above the threshold of acceptable risk in the event of a vapor cloud explosion. This exposed these employees to the hazards of fire and explosion. Pursuant to 20 CFR 1903.19, within (10) calendar days of the abatement date listed in this citation, the employer must submit an abatement plan describing the actions it is taking to ensure that it addressing the hazardous facility siting location of Operator Control House #3. The violation must be abated no later than 30 days from receipt of this citation. b) The employer does not ensure that resolutions to the process hazard analysis team's findings and recommendations is established. This violation was found on July 05, 2010, at Motiva Enterprises LLC, Convent, LA, when the employer did not document resolutions to findings and recommendations and/or recorded inappropriate answers before closing the action items. For example, several PHA team's findings and recommendations from the H-Oil Unit 2003 and 2007 are still unresolved or status is unknown and/or not complete. Such items include , but are not limited to: 1) 2003 PHA, Node 122; 2) 2003 PHA, Node 152; 3) 2003 PHA, Node 147; 4) 2003 PHA, Node 153; 5) 2003 PHA, Node 175; 6) 2007 PHA, Node 110.1.1.2.1; 7) 2007 PHA, Node 113.1.2.2.1; and 8) 2007 PHA, Node 121.13.1.1.1. Pursuant to 29 CFR 1903.19 within 10 calendar days, the employer must submit an abatement plan describing the actions it is taking to ensure that appropriate resolutions are determined and documented for each findings and recommendations addressed from the 2003 and 2007 PHA. The violation must be abated no later than 30 days from receipt of this citation.
Recent events (2)
- — J (S) $5000.00
- — Z (S) $7000.00
1910.119 F01 ID
- Issued
- Oct 27, 2010
- Abate by
- Nov 15, 2010
- Penalty
- Initial $7,000 · Current $5,000 Reduced
General-duty citation text
29 CFR 1910.119(f)(1)(i)(D): The employer's written operating procedures covering the steps for each operating phase did not address emergency shutdown including the conditions under which emergency shutdown is required, and the assignment of shutdown responsibility to qualified operators to ensure that emergency shutdown executed in a safe and timely manner: The employer does not have written Emergency Shutdown Procedures (ESPs) for safe and timely shutdown of the H-Oil Unit in the event of emergency situations that may include, but are not limited to, the failure of process equipment, loss of electrical power, loss of instrumentation, loss of containment, severe weather condition, fire, explosion, etc. This condition exposed employees to a fire and/or explosion hazard. This hazard was most recently observed on or about May 21, 2010 at Motiva Enterprises LLC, Convent, LA. Pursuant to 29 CFR 1903.19, within (10) calendar days of the abatement date listed in this citation, the employer must submit an abatement plan describing the actions it is taking to ensure that Emergency Shutdown Procedures (ESPs) are developed, written, and implemented when required. The violation must be abated no later than 30 days from receipt of this citation.
Recent events (2)
- — J (S) $5000.00
- — Z (S) $7000.00
1910.119 O01
- Issued
- Oct 27, 2010
- Abate by
- Nov 15, 2010
- Penalty
- Initial $2,500
General-duty citation text
29 CFR 1910.119(o)(1): The employer did not verify that the procedures and practices developed under the standard were adequate and were being followed: The employer does not ensure in the self audit that a representative number of pressure vessel inspection records are included to verify that the vessel inspection procedures are adequate and are being followed. On or about August 9, 2010, at Motiva Enterprises LLC, Convent, LA. the employer had failed to ensure that pressure vessel inspection records were included in the self audit. This exposed employees to hazards of fire and explosion. Pursuant to 20 CFR 1903.19, within (10) calendar days of the abatement date listed in this citation, the employer must submit an abatement plan describing the actions it is taking to ensure that it addressing the analysis of pressure vessel inspection records as a part of the compliance audit process.
Recent events (2)
- — J (S)
- — Z (S) $2500.00
1910.157 E03
- Issued
- Oct 27, 2010
- Abate by
- Nov 8, 2010
- Penalty
- Initial $2,500 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check: The employer does not ensure that all portable fire extinguishers provided for employee use in the H-Oil Unit receive an annual maintenance check. Portable fire-fighting equipment, such as, but not limited to, Ansul Red Line Class ABC fire extinguishers (H-Oil ID #045, #047, and #082) had past due inspection tags of June 2009, over a year without an internal examination by a certified inspector. This hazard was most recently observed on or about July 19, 2010 at Motiva Enterprises LLC, Convent, LA. Pursuant to 29 CFR 1903.19, within (10) calendar days of the abatement date listed in this citation, the employer must submit an abatement plan describing the actions it is taking to ensure that all portable fire extinguishers receive an annual maintenance check before being made available for employee use. The violation must be abated no later than 30 days from receipt of this citation.
Recent events (2)
- — J (S) $1000.00
- — Z (S) $2500.00
1910.1200 F05 I
- Issued
- Oct 27, 2010
- Abate by
- Nov 8, 2010
- Penalty
- Initial $2,500 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.1200(f)(5)(i): The employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the identity of the hazardous chemical(s) contained therein: The employer does not ensure that all H-Oil Unit process vessels containing highly hazardous chemicals (HHCs) are properly labeled. H-Oil vessels such as but not limited to, Train 100 and 200 Second Stage Reactors (70F-102, 70F-202), Reactor Effluent Cold Condensing Drum (70F- 205), and Circulation Oil Surge Drum (70F-509) were not adequately labeled with contents contained therein and/or with legible identification numbers in accordance with this standard or with Motiva's Standard Instruction No. 525: Hazard Communication Policy. This hazard was most recently observed on or about July 20, 2010 at Motiva Enterprises LLC, Convent, LA. Pursuant to 29 CFR 1903.19, within (10) calendar days of the abatement date listed in this citation, the employer must submit an abatement plan describing the actions it is taking to ensure that all process vessels are marked with legible identification numbers or appropriate chemical labels/descriptions. The violation must be abated no later than 30 days from receipt of this citation
Recent events (2)
- — J (S) $1000.00
- — Z (S) $2500.00
1910.119 J05
- Issued
- Oct 27, 2010
- Abate by
- Nov 15, 2010
- Penalty
- Initial $35,000 · Current $7,000 Reduced
General-duty citation text
29 CFR 1910.119(j)(5): The employer did not correct deficiencies in equipment that were outside acceptable limits (as defined by process information in 29 CFR 1910.119(d)) before further use or in a safe and timely manner: a) The employer does not ensure that all pressure gauges and indicator lights on emergency isolation valve panel boards are operational. Throughout the H-Oil Unit there are isolation valve panel boards such as, but not limited to, LCB 101, LCB-102, LCB-103, LCB-201, LCB-301, LCB-302, and LCB 401 with non-functioning indicator lights and broken and/or faulty pressure gauges. As a result of this condition, Outside Operators are unable to properly identify which valves are open or close by viewing the panel board and in the event of an emergency would have to physically check the valves throughout the unit, exposing them to a fire and/or explosion hazards. This hazard was most recently observed on or about May 5, 2010 and July 20, 2010 at Motiva Enterprises LLC, Convent, LA. b) The employer does not ensure that corroded/rusted out drain block valves and drain piping for H-Oil vessel 70F-312 (Second Stage Compressor Knockout Drum) are repaired and/or replaced for safe operation. This hazard was most recently observed on or about July 20, 2010 and August 25, 2010 at Motiva Enterprises LLC, Convent, LA. Pursuant to 29 CFR 1903.19, within (10) calendar days of the abatement date listed in this citation, the employer must submit an abatement plan describing the actions it is taking to ensure that all deficient equipment is in fully operational condition. The violation must be abated no later than 30 days from receipt of this citation. MOTIVA ENTERPRISES LLC WAS PREVIOUSLY CITED FOR A VIOLATION OF THE THIS OCCUPATIONAL SAFETY AND HEALTH STANDARD OR ITS EQUIVALENT STANDARD 1910.119(j)(5) WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 311522601, CITATION NUMBER 1, ITEM NUMBER 8, ISSUED ON AUGUST 21, 2008, WITH RESPECT TO A WORKPLACE LOCATED AT 15536 RIVER RD, NORCO, LA 70079.
Recent events (2)
- — J (R) $7000.00
- — Z (R) $35000.00
More inspections at Motiva Enterprises LLC
View Motiva Enterprises LLC's full OSHA safety record →
More inspections in this industry (NAICS 324110)
More inspections in LA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 313030306.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.