WESTFIELD, NC —
OSHA Inspection: DOW ROOFING SYSTEMS LLC
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of DOW ROOFING SYSTEMS LLC in 1535 ELASTIC PLANT ROAD, WESTFIELD, NC 27053 (NAICS 326299). OSHA activity number 313060022.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- DOW ROOFING SYSTEMS LLC
- Site address
- 1535 ELASTIC PLANT ROAD
- City
- WESTFIELD
- State
- NC
- ZIP
- 27053
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 326299
- SIC code (legacy)
- 3069
- Employees
- 138
- Ownership type
- A
- Industry flags
- Manufacturing safety.
Citations
4 citations on file for this inspection.
95012901
- Issued
- Jul 23, 2009
- Abate by
- Sep 9, 2009
- Penalty
- Initial $2,275 · Current $2,275
General-duty citation text
North Carolina General Statute 95-0129(1) of the Occupational Safety and Health Act of North Carolina: The employer did not furnish each of his employees conditions of employment and a place of employment free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to fire and explosion hazards: a)establishment, mixing and recycling areas - the work tasks, including, but not limited to, scooping, dumping, mixing, and sweeping combustible dust, were not properly contained, nor properly handled. The area contained at least one-sixteenth inch of combustible dust (Polypropylene Resin and Resin dust) or greater over 25of the horizontal surfaces of equipment, floor, and the ventilation system duct work. There were various deficiencies in the attempt to control the combustible dust including, but not limited to, the following: the employer's housekeeping program was not effective in eliminating accumulated combustible dust on surfaces in the mixing area, ventilation system duct work, and baghouses, documentation and recordkeeping of air volume, air velocity, and equipment bonding and grounding was not available, including risk evaluation to determine the need of an fire detection system within the duct work or that the automatic sprinkler provided was acceptable, and electrical equipment was not appropriate for classified areas. The employer did not have a written Standing Operational Procedures (SOP) for the cleaning of bag house filters. REFERENCE: Combustible Dust Explosion Prevention Program CPL 03-00-008, and Standard for the Prevention of Fire and Dust Explosions from Manufacturing, Processing, and Handling of Combustible Particulate Solids NFPA 654. NOTE: Among other methods of abatement, one feasible and acceptable method to correct these hazards would be to follow the guidelines established in the Standard for the Prevention of Fire and Dust Explosions from Manufacturing, Processing, and Handling of Combustible Particulate Solids NFPA 654.
Recent events (2)
- — I (S) $2275.00
- — Z (S) $2275.00
1910.22 A01
- Issued
- Jul 23, 2009
- Abate by
- Aug 18, 2009
- Penalty
- Initial $2,275 · Current $2,275
Recent events (2)
- — I (S) $2275.00
- — Z (S) $2275.00
1910.145 C03
- Issued
- Jul 23, 2009
- Abate by
- Sep 9, 2009
- Penalty
- Initial $2,275 · Current $2,275
Recent events (2)
- — I (S) $2275.00
- — Z (S) $2275.00
1910.307 C02 I
- Issued
- Jul 23, 2009
- Abate by
- Jul 28, 2009
- Penalty
- Initial $2,275 · Current $2,275
Recent events (2)
- — I (S) $2275.00
- — Z (S) $2275.00
More inspections at DOW Roofing Systems LLC
View DOW Roofing Systems LLC's full OSHA safety record →
More inspections in this industry (NAICS 326299)
More inspections in NC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 313060022.