OSHA Inspection: DIDION MILLING, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of DIDION MILLING, INC. in 501 S. WILLIAMS STREET, CAMBRIA, WI 53923 (NAICS 311211). OSHA activity number 313135675.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- DIDION MILLING, INC.
- Site address
- 501 S. WILLIAMS STREET
- City
- CAMBRIA
- State
- WI
- ZIP
- 53923
- Mailing
- P.O. BOX 495, CAMBRIA, WI 53923
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (N)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311211
- SIC code (legacy)
- 2041
- Employees
- 110
- Ownership type
- Private (A)
Citations
1 citation on file for this inspection.
5(a)(1)
- Issued
- Jan 5, 2011
- Abate by
- Jun 20, 2013
- Penalty
- Initial $6,300 · Current $3,465 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that caused or were likely to cause death or serious physical harm. Employees were exposed to the hazards associated with dust explosion, deflagration or other fire hazards. Didion Milling Inc, filter collectors where located inside: a) 6th floor filters (NE, NC, NW, SW, SE) did not have explosion protective system b) packaging room expander filter did not have explosion protective system. c) pneumatic conveyor couplings were not bonded to the ducts. AMONG OTHER METHODS, ONE FEASIBLE AND ACCEPTABLE ABATEMENT METHOD TO CORRECT THESE HAZARDS IS to comply with the National Fire Protection Association (NFPA) Chapter 61 "Prevention of Fires and Dust Explosion in Agriculture and Food Processing Facilities, 2008 edition. 6.1 Explosion prevention, relief and venting as used in this standard, shall encompass the design and installation of devices and system to vent the gases and over pressure resulting from a combustion explosion occurring in equipment, rooms, buildings, or other enclosures so that damaged in minimized. 6.3.1 Equipment requiring explosion prevention shall be protected by containment, suppression, inerting or explosion venting. 10.4.3 Dust collectors shall be located outside of buildings and shall be protected in accordance with section 6.3. 11.2.2 Bonding and grounding shall be electrically conductive. NFPA 69 "Standard on Explosion Prevention System" 2008 edition; NFPA 68 "Standard on Explosion Protection by Deflagration Venting" 2007 edition. ABATEMENT DOCUMENTATION REQUIRED PER 29 CFR 1903.19(d) Abatement Schedule: Step 1-A combination of administrative controls shall be implemented as an interim protective measure until feasible engineering and administrative controls can be permanently implemented. Step 2-A written detailed plan of abatement shall be submitted to the Area Director outlining a schedule for the implementation of engineering and/or administrative measures to control employee exposure to the hazardous condition as referenced in this citation. This plan shall include, at a minimum, target dates for the following actions which must be consistent with the abatement dates required by this citation: 1)Evaluation of engineering/administrative control options 2)Selection of optimum control methods and completion of design 3)Procurement, installation, and operation of selected control measures 4)Testing and acceptance or modification/redesign of controls; All proposed control measures shall be approved for each particular use by a competent certified safety professional, professional engineer, or other technically qualified person Step 3-Abatement shall have been completed by the implementation of feasible engineering and administrative controls upon verification of their effectiveness in achieving compliance. Date by Which Violation Must be Abated: STEP - 1 02/07/11 Date by Which Violation Must be Abated: STEP - 2 03/09/11 Date by Which Violation Must be Abated: STEP - 3 04/08/11
Recent events (3)
- · P (S) $3465.00
- · I (S) $3465.00
- · Z (S) $6300.00
More inspections at Didion Milling, INC.
View Didion Milling, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 311211)
More inspections in WI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 313135675.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.