STANLEY, WI —
OSHA Inspection: ACE ETHANOL,LLC
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of ACE ETHANOL,LLC in 815 W. MAPLE ST., STANLEY, WI 54768 (NAICS 325193). OSHA activity number 313180424.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ACE ETHANOL,LLC
- Site address
- 815 W. MAPLE ST.
- City
- STANLEY
- State
- WI
- ZIP
- 54768
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 325193
- SIC code (legacy)
- 2869
- Employees
- 40
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.23 C01
- Issued
- Oct 12, 2011
- Abate by
- Oct 17, 2011
- Penalty
- Initial $2,975 · Current $2,083 Reduced
General-duty citation text
29 CFR 1910.23(c)(1): Open sided floor(s) or platform(s) 4 feet or more above the adjacent floor or ground level were not guarded by standard railings (or the equivalent as specified in 29 CFR 1910.23(e)(3)(i) through (v)), on two sides: (a)Throughout Distillation B; There were unguarded platforms 4 feet or more above ground level, such as, but not limited to; 1. C-410A Beer Column A 2. C-420A Stripper Column A 3. C-430A Rectifier Column A Abatement note: Abatement documentation and certification are not required for this item.
Recent events (2)
- — I (S) $2082.50
- — Z (S) $2975.00
1910.119 D03 IB
- Issued
- Oct 12, 2011
- Abate by
- Oct 17, 2011
- Penalty
- Initial $2,975 · Current $2,083 Reduced
General-duty citation text
29 CFR 1910.119(d)(3)(i)(B): Process safety information pertaining to the equipment in the process did not include the piping and instrument diagrams (P&ID'S): (a)Reboiler E-410B in Distillation Building B; 1.The pressure indicator (PI) near valve V41170 indicated on P&ID 145-PI- 4101 was missing. 2.The pressure indicator (PI) near valve V41176 indicated in P&ID 145-PI- 4101 was missing. Abatement note: Corrected during inspection, employer sent in documentation of abatement.ion
Recent events (2)
- — I (S) $2082.50
- — Z (S) $2975.00
1910.119 J05
- Issued
- Oct 12, 2011
- Abate by
- Oct 17, 2011
- Penalty
- Initial $2,975 · Current $2,083 Reduced
General-duty citation text
29 CFR 1910.119(j)(5): The employer did not correct deficiencies in equipment that were outside acceptable limits (as defined by process information in 29 CFR 1910.119(d) before further use or in a safe and timely manner: (a)Reboiler E-410B in Distillation Building B; 1. The pressure indicator (PI) near valve V41186 indicated on P&ID 145-PI-4101 was non-functioning. 2. The pressure indicator (PI) near valve V41171 indicated on P&ID 145-PI-4101 was non-functioning. Abatement note: Corrected during inspection, the employer sent in documentation of abatement.ion
Recent events (2)
- — I (S) $2082.50
- — Z (S) $2975.00
More inspections at ACE Ethanol,Llc
View ACE Ethanol,Llc's full OSHA safety record →
More inspections in this industry (NAICS 325193)
More inspections in WI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 313180424.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.